Baseline Building Fan System Summary
The baseline building fan system is summarized in this section. See [bookref id="hvac-mapping"] for the HVAC baseline building system mapping.
Total baseline building fan system power for the baseline building fan systems is given in [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007 and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] for ASHRAE Standard 90.1-2001. In these tables, "cfms" is the supply fan air flow at peak design conditions. This is calculated for the baseline building with the sizing procedure described in [bookref id="calculation-process-for-tax-deductions-and-green-building-ratings"] and [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. This brake horsepower includes the supply fan, the return fan, and exhaust fans. Exhaust fans include kitchen hoods, toilets, fume hoods, and other miscellaneous fans that operate at design conditions.
[table title="Baseline Building Fan System – ASHRAE Standard 90.1-2007" id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"]
System Types 1-2 | System Types 3-4 | System Types 5-8 | |
Brake Horsepower (bhp) | Not applicable | 0.00094 x cfms + A | 0.0013 x cfms + A |
Fan Motor Efficiency (hm) | Not applicable | ASHRAE Standard 90.1-2007, Table 10.8 | ASHRAE Standard 90.1-2007, Table 10.8 |
Fan Power (W) | 0.3 x cfms | (bhp x 746)/$\eta$m | (bhp x 746)/$\eta$m |
The term “A” for system types 3-8, is calculated based on equipment in the proposed design using the procedure in Table 6.5.3.1.1B of ASHRAE Standard 90.1-2007. This accounts for various additional fan pressure drops associated with special conditions. |
[table title="Baseline Building Fan System – ASHRAE Standard 90.1-2001" id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"]
Fan Size | System Types 1-4 | System Types 5-8 | |
Nameplate Horsepower (nhp) | < 20,000 cfm | 0.0012 x cfms + Pfilter + Pprocess + Prelief | 0.0017 x cfms + Pfilter + Pprocess + Prelief |
=> 20,000 cfm | 0.0011 x cfms + Pfilter + Pprocess + Prelief | 0.0015 x cfms + Pfilter + Pprocess + Prelief | |
Fan Motor Efficiency (hm) | ASHRAE Standard 90.1-2001, Table 10.2 | ASHRAE Standard 90.1-2001, Table 10.2 | |
Brake Horsepower (bhp) | nhp x $\eta$m | nhp x $\eta$m | |
Fan Power (W) | (bhp x 746)/ $\eta$m | (bhp x 746)/ $\eta$m | |
The terms Pfilter, Pprocess, and Prelief account for additional pressure drop. These are based on features in the proposed design such as special filtration, process fans, and relief or return fans. See Section 6.3.3.1 of ASHRAE Standard 90.1-2001 and the associated User's Manual for details on how to calculate these adders. |
When the proposed design has exhaust fans (toilets or kitchens), return fans, or fume hood exhaust systems, the baseline building has the same systems. The brake horsepower determined from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] is allocated to these baseline building fan systems proportionally to the allocation in the proposed design. The allocation of brake horsepower to the supply fan, the return and any exhaust or fume hood fans is based on the ratios described below.
Supply Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of supply fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Return Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of return fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Exhaust Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of exhaust fan brake horsepower in the proposed design to total fan system brake hp for the proposed design at design conditions. Exhaust fans include toilet exhaust, kitchen hoods and other miscellaneous exhaust. Fume hood exhaust is treated separately. |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors. In the event that a common exhaust system serves thermal blocks that are served by different HVAC systems, the brake horsepower shall be divided in proportion to design cfm. |
Baseline Rules | Same as proposed design |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules | The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. |
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable to variable air volume systems Based on the prescribed system type. Refer to the HVAC System Map in [bookref id="hvac-mapping"]. |
[table title="Baseline Building Fan Control Method" id="baseline -bilding-fan-control-method"]
Baseline building System | Fan Control Method |
System 1 – PTAC | Constant volume |
System 2 – PTHP | Constant volume |
System 3 – PSZ-AC | Constant volume |
System 4 – PSZ-HP | Constant volume |
System 5 – Packaged VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 6 – Packaged VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
System 7 – VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 8 – VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Baseline Rules | See [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007 and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] for ASHRAE Standard 90.1-2001. These tables give the baseline building fan system brake horsepower. The brake horsepower for the supply fan is this value times the Supply Fan Ratio (see above). |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 or Table 10.2 of ASHRAE Standard 90.1-2001 |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Draw through |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
[table title="Fan Curve Default Values" id="fan-curve-default-values"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 with no adjustment for static pressure setpoint reset. |
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
||||
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007 and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] for ASHRAE Standard 90.1-2001. This power is then multiplied by the supply fan ratio. |
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum, otherwise, the return air ducts are assumed to be located in the space. |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be same as proposed design. |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The return fan air Rated Capacity shall be equal to the baseline building supply fan capacity less exhaust air flow. |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The bhp of the return fan shall be the fan system brake horsepower (see [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"]) times the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 or Table 10.2 of ASHRAE Standard 90.1-2001 |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 that have a return/relief fan. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007 and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] for ASHRAE Standard 90.1-2001. This power is then multiplied by the return fan ratio. |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks. The baseline building has exhaust fans when the proposed design has exhaust fans. The exhaust air flow is the same for the baseline building and the proposed design.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Baseline Rules | The baseline building exhaust fan control shall generally be the same as the proposed design. For laboratories that have exhaust flow of 5,000 cfm or more, the baseline building exhaust flow shall vary in response to scheduled fume hood exhaust and lab zone airflow schedules. Fume hood exhaust flow control shall be the same as design, and general exhaust (relief) shall be VSD. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Baseline Rules | Same as the proposed design |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | The bhp for the baseline building is the total system fan horsepower from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] or [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] times the exhaust fan ratio. |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 or Table 10.2 of ASHRAE Standard 90.1-2001 |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Baseline Rules | The baseline building fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |
Baseline Rules | The fan system power from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] or [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] |
Baseline Building Fan System Summary
The baseline building fan system is summarized in this section. See [bookref id="hvac-mapping"] for the HVAC baseline building system mapping.
Total baseline building fan system power for the baseline building fan systems is given in [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"]. In this table, "cfms" is the supply fan air flow at peak design conditions. This is calculated for the baseline building with the sizing procedure described in [bookref id="calculation-process-for-tax-deductions-and-green-building-ratings"] and [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. This brake horsepower includes the supply fan, the return fan, and exhaust fans. Exhaust fans include kitchen hoods, toilets, fume hoods, and other miscellaneous fans that operate at design conditions.
[table title="Baseline Building Fan System – ASHRAE Standard 90.1-2007" id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"]
System Types 1-2 | System Types 3-4 | System Types 5-8 | |
Brake Horsepower (bhp) | Not applicable | 0.00094 x cfms + A | 0.0013 x cfms + A |
Fan Motor Efficiency (hm) | Not applicable | ASHRAE Standard 90.1-2007, Table 10.8 | ASHRAE Standard 90.1-2007, Table 10.8 |
Fan Power (W) | 0.3 x cfms | (bhp x 746)/$\eta$m | (bhp x 746)/$\eta$m |
The term “A” for system types 3-8, is calculated based on equipment in the proposed design using the procedure in Table 6.5.3.1.1B of ASHRAE Standard 90.1-2007. This accounts for various additional fan pressure drops associated with special conditions. |
When the proposed design has exhaust fans (toilets or kitchens), return fans, or fume hood exhaust systems, the baseline building has the same systems. The brake horsepower determined from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] is allocated to these baseline building fan systems proportionally to the allocation in the proposed design. The allocation of brake horsepower to the supply fan, the return and any exhaust or fume hood fans is based on the ratios described below.
Supply Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of supply fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Return Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of return fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Exhaust Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of exhaust fan brake horsepower in the proposed design to total fan system brake hp for the proposed design at design conditions. Exhaust fans include toilet exhaust, kitchen hoods and other miscellaneous exhaust. Fume hood exhaust is treated separately. |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors. In the event that a common exhaust system serves thermal blocks that are served by different HVAC systems, the brake horsepower shall be divided in proportion to design cfm. |
Baseline Rules | Same as proposed design |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules | The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. |
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable to variable air volume systems Based on the prescribed system type. Refer to the HVAC System Map in [bookref id="hvac-mapping"]. |
[table title="Baseline Building Fan Control Method" id="baseline -bilding-fan-control-method"]
Baseline building System | Fan Control Method |
System 1 – PTAC | Constant volume |
System 2 – PTHP | Constant volume |
System 3 – PSZ-AC | Constant volume |
System 4 – PSZ-HP | Constant volume |
System 5 – Packaged VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 6 – Packaged VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
System 7 – VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 8 – VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Baseline Rules | See [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007. These tables give the baseline building fan system brake horsepower. The brake horsepower for the supply fan is this value times the Supply Fan Ratio (see above). |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Draw through |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
[table title="Fan Curve Default Values" id="fan-curve-default-values"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 with no adjustment for static pressure setpoint reset. |
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
||||
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007. This power is then multiplied by the supply fan ratio. |
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum, otherwise, the return air ducts are assumed to be located in the space. |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be same as proposed design. |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The return fan air Rated Capacity shall be equal to the baseline building supply fan capacity less exhaust air flow. |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The bhp of the return fan shall be the fan system brake horsepower (see [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"]) times the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 that have a return/relief fan. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007. This power is then multiplied by the return fan ratio. |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks. The baseline building has exhaust fans when the proposed design has exhaust fans. The exhaust air flow is the same for the baseline building and the proposed design.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Baseline Rules | The baseline building exhaust fan control shall generally be the same as the proposed design. For laboratories that have exhaust flow of 5,000 cfm or more, the baseline building exhaust flow shall vary in response to scheduled fume hood exhaust and lab zone airflow schedules. Fume hood exhaust flow control shall be the same as design, and general exhaust (relief) shall be VSD. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Baseline Rules | Same as the proposed design |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | The bhp for the baseline building is the total system fan horsepower from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] times the exhaust fan ratio. |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Baseline Rules | The baseline building fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |
Baseline Rules | The fan system power from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] |
Baseline Building Fan System Summary
The baseline building fan system is summarized in this section. See Figure 6.1.2-1 for the HVAC baseline building system mapping.
Total baseline building fan system power for the baseline building fan systems is given in Table 6.7.3-1. In this table, "cfms" is the supply fan air flow at peak design conditions. This is calculated for the baseline building with the sizing procedure described in Figure 2.4-1. This brake horsepower includes the supply fan, the return fan, and exhaust fans. Exhaust fans include kitchen hoods, toilets, fume hoods, and other miscellaneous fans that operate at design conditions.
Table 6.7.3-1: Baseline Building Fan System – ASHRAE Standard 90.1 2010
System Types 1-2 | System Types 3-4 | System Types 5-8 | System Types 9-10 | |
Brake Horsepower (bhp) | Not applicable | 0.00094 x cfms + A | 0.0013 x cfms + A | Not Applicable |
Fan Motor Efficiency (hm) | Not applicable | ASHRAE Standard 90.1-2007, Table 10.8 | ASHRAE Standard 90.1-2007, Table 10.8 | Not Applicable |
Fan Power (W) | 0.3 x cfms | (bhp x 746)/$\eta$m | (bhp x 746)/$\eta$m | 0.3 x cfms OR 0.054 x CFMnmc |
The term “A” for system types 3-8, is calculated based on equipment in the proposed design using the procedure in Table 6.5.3.1.1B of ASHRAE Standard 90.1-2010. This accounts for various additional fan pressure drops associated with special conditions. *CFMnmc is the baseline non-mechanical cooling fan airflow in cfm. This alternate equation is only used if there is a non-mechanical cooling system in place. |
When the proposed design has exhaust fans (toilets or kitchens), return fans, or fume hood exhaust systems, the baseline building has the same systems. The brake horsepower determined from Table 6.7.3-1 is allocated to these baseline building fan systems proportionally to the allocation in the proposed design. The allocation of brake horsepower to the supply fan, the return and any exhaust or fume hood fans is based on the ratios described below.
Supply Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of supply fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Return Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of return fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Exhaust Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of exhaust fan brake horsepower in the proposed design to total fan system brake hp for the proposed design at design conditions. Exhaust fans include toilet exhaust, kitchen hoods and other miscellaneous exhaust. Fume hood exhaust is treated separately. |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors. In the event that a common exhaust system serves thermal blocks that are served by different HVAC systems, the brake horsepower shall be divided in proportion to design cfm. |
Baseline Rules | Same as proposed design |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules |
The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system.
|
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable to variable air volume systems Based on the prescribed system type. Refer to the HVAC System Map in Figure 6.1.2-1. |
Table 6.7.3-2: Baseline Building Fan Control Method
Baseline building System | Fan Control Method |
System 1 – PTAC | Constant volume |
System 2 – PTHP | Constant volume |
System 3 – PSZ-AC | Constant volume |
System 4 – PSZ-HP | Constant volume |
System 5 – Packaged VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 6 – Packaged VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
System 7 – VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 8 – VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
System 9 – Heating and Ventilation | Constant Volume |
System 10 – Heating and Ventilation | Constant Volume |
*Effective 1/1/2012, all air-conditioning equipment and air-handling units with dx cooling and a cooling capacity greater than or equal to 110,000 Btu/h that serve single zones shall have supply fans controlled by two-speed motors or variable speed drives. At cooling demands less than or equal to 50% , the supply fan controls shall reduce the airflow to no greater than the larger of the following: 1)1/2 of the full fan speed or 2)the minimum outdoor air. |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Baseline Rules | See Table 6.7.2-1 for ASHRAE Standard 90.1-2007. These tables give the baseline building fan system brake horsepower. The brake horsepower for the supply fan is this value times the Supply Fan Ratio (see above). |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Draw through |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and Table 6.7.3-3 for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
Table 6.7.3-3:Fan Curve Default Values
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 with no adjustment for static pressure setpoint reset. |
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
||||
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 6.7.3-1 for ASHRAE Standard 90.1-2007. This power is then multiplied by the supply fan ratio. |
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum, otherwise, the return air ducts are assumed to be located in the space. |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be same as proposed design. |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The return fan air Rated Capacity shall be equal to the baseline building supply fan capacity less exhaust air flow. |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The bhp of the return fan shall be the fan system brake horsepower (see Table 6.7.3-1) times the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and Table 6.7.3-3 for the type of fan specified in the proposed design. |
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 that have a return/relief fan. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 6.7.3-1 for ASHRAE Standard 90.1-2007. This power is then multiplied by the return fan ratio. |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks. The baseline building has exhaust fans when the proposed design has exhaust fans. The exhaust air flow is the same for the baseline building and the proposed design.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules |
Same as the proposed design except that baseline building kitchen exhaust rate may not exceed the maximum levels defined by ASHRAE 90.1-2010, Table 6.5.7.1.3.
|
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Baseline Rules |
The baseline building exhaust fan control shall generally be the same as the proposed design. For laboratories that have exhaust flow of 5,000 cfm or more, the baseline building exhaust flow shall vary in response to scheduled fume hood exhaust and lab zone airflow schedules. Fume hood exhaust flow control shall be the same as design, and general exhaust (relief) shall be VSD.
If a kitchen zone design exhaust rate is greater than 5,000 cfm, the baseline building system serving the kitchen shall be system type 5 or 7 with a demand ventilation system on 75% of the exhaust air. The system shall reduce exhaust and replacement air system airflow rates by 50% for one half of the kitchen occupied hours. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Baseline Rules | Same as the proposed design |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | The bhp for the baseline building is the total system fan horsepower from Table 6.7.3-1 times the exhaust fan ratio. |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and Table 6.7.3-3 for the type of fan specified in the proposed design. |
Baseline Rules | The baseline building fan curve shall be selected from Equation (6.7.3-1) and Table 6.7.3-3 for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |
Baseline Rules | The fan system power from Table 6.7.3-1. |
This section addresses:
This section addresses:
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules | The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. |
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
[table title="Fan Curve Default Values" id="fan-curve-default-values"]
|
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules | The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. |
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
[table title="Fan Curve Default Values" id="fan-curve-default-values"]
|
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |