3.7.3.3 Return/Relief Fans

90.1-2016 BM

Baseline building systems 3 through 8 and 11 through 13, shall have a return/relief fan when the proposed design has a return/relief fan fan.

 

Plenum Zone

Applicability

Any system with return ducts or return air plenum

Definition

A reference to the thermal block that serves as return plenum or where the return ducts are located

Units

Text, unique

Input Restrictions

As designed

Baseline Rules

Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum, otherwise, the return air ducts are assumed to be located in the space.

 

Return Air Path

Applicability

Any system with return ducts or return air plenum

Definition

Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit.

Units

List (see above)

Input Restrictions

As designed

Baseline Rules

Applicable when the baseline building has a return fan. For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and 11 through 13, when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be same as proposed design.

 

Return/Relief Air Rated Capacity

Applicability

All systems with a return or relief fan

Definition

The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below).

Units

cfm

Input Restrictions

As designed

Baseline Rules

Applicable when the baseline building has a return fan. The return fan air Rated Capacity shall be equal to 90% of the baseline building supply fan capacity or the baseline building supply fan capacity less the minimum outdoor air, whichever is larger. The two special cases apply.

  • For systems serving laboratory spaces, airflow rate shall be based on a supply-air-to-room temperature setpoint difference of 17°F or the required ventilation air or makeup air, whichever is greater.
  • If the proposed design HVAC system airflow rate based on latent loads is greater than the design airflow rate based on sensible loads, then the same supply-air-to-room-air humidity ratio difference (gr/lb) used to calculate the proposed design airflow shall be used to calculate design airflow rates for the baseline building design.

 

Return/Relief Fan Brake Horsepower

Applicability

Any system with return or relief fans that uses the brake horsepower method

Definition

The design shaft brake horsepower of the return/relief fan(s)

Units

Brake horsepower (bhp)

Input Restrictions

As designed

Baseline Rules

Applicable when the baseline building has a return fan. The bhp of the return fan shall be the fan system brake horsepower (see Table 3.7.3-1) times the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design.

 

Return/Relief Design Static Pressure

Applicability

Any system with return or relief fans that uses the static pressure method

Definition

The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations.

Units

Inches of water column (in. H20)

Input Restrictions

As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified.

Baseline Rules

The baseline Return/Relief Design Static Pressure shall be equal to the return/relief fan brake horsepower divided by the constant 6,356 and an assumed fan efficiency of 65%.

 

Return/Relief Fan Efficiency

Applicability

Any system with return or relief fans that uses the static pressure method

Definition

The efficiency of the fan at design conditions

Units

Unitless

Input Restrictions

As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified.

Baseline Rules

65%

 

Return/Relief Motor Efficiency

Applicability

All return fans, except those specified using the power-per-unit-flow method

Definition

The full-load efficiency of the motor serving the supply fan

Units

Unitless

Input Restrictions

As designed. Not applicable when the power-per-unit-flow method is used.

Baseline Rules

For baseline systems 1, 2, 9 and 10, motor efficiency shall be 80%. For other systems, the minimum value from Table 3.7.3-3 shall be used.

 

Motor Position

Applicability

All return fans

Definition

The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream.

Units

List (see above)

Input Restrictions

As designed.

Baseline Rules

In the air stream

 

Fan Part-Flow Power Curve

Applicability

All return fans for variable flow fan systems.

Definition

A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow.

Units

Unitless ratio

Input Restrictions

As designed. The default fan curve shall be selected from COMNET Appendix H for the type of fan specified in the proposed design.

Baseline Rules

Not applicable for baseline building systems 1-, 9, 10, 12 and 13. The default curve for VSD fans shall be used for baseline building systems 5-8 that have a return/relief fan. The default shall be taken from COMNET Appendix H.

 

Return/Relief Fan Power Index

Applicability

Any system with a return fan

Definition

The supply fan power per unit of flow

Units

kW/cfm

Input Restrictions

As specified in the manufacturers’ literature

Baseline Rules

Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined from Table 3.7.3-2. This power is then multiplied by the return fan ratio.

 

90.1-2019

System design supply airflow rates for the baseline building design shall be based on a supply-air-to room-air temperature difference of 20°F or the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is greater. For systems 3, 4, and 11 through 13, if return or relief fans are specified for systems serving the corresponding zones in the proposed design, the baseline building design shall also be modeled with fans serving the same functions. For systems 5 through 8, if return or relief fans are specified in the proposed building, then the baseline systems serving the corresponding zones will be modeled with a return/relief fan.

 

Plenum Zone

Applicability

Any system with return ducts or return air plenum

Definition

A reference to the thermal zone that serves as return plenum or where the return ducts are located

Units

Text, unique

Input Restrictions

As designed

Baseline Building

Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum; otherwise, the return air ducts are assumed to be located in the space.

 

Return Air Path

Applicability

Any system with return ducts or return air plenum

Definition

Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit.

Units

List (see above)

Input Restrictions

As designed

Baseline Building

For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and 11 through 13 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be the same as proposed design.

 

Return/Relief Air Rated Capacity

Applicability

All systems with a return or relief fan

Definition

The design airflow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below).

Units

cfm

Input Restrictions

As designed

Baseline Building

Applicable when the baseline building has a return fan. Return or relief fans shall be sized for the baseline system supply fan air quantity less the minimum outdoor air, or 90% of the supply fan air quantity, whichever is larger.

 

Return/Relief Fan Brake Horsepower

Applicability

Any system with return or relief fans that uses the brake horsepower method

Definition

The design shaft brake horsepower of the return/relief fan(s)

Units

Brake horsepower (bhp)

Input Restrictions

As designed

Baseline Building

Applicable when the baseline building has a return fan. The bhp of the return fan shall be the system fan brake horsepower multiplied by the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design.

 

Return/Relief Design Static Pressure

Applicability

Any system with return or relief fans that uses the static pressure method

Definition

The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations.

Units

Inches of water column (in. H2O gauge)

Input Restrictions

As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified.

Baseline Building

Return fan static pressure = (Return fan BHP x 6356 x 0.65)/cfm return

 

Return/Relief Fan Efficiency

Applicability

Any system with return or relief fans that uses the static pressure method

Definition

The efficiency of the fan at design conditions; this is the static efficiency and does not include the efficiency loss of the motor

Units

Unitless

Input Restrictions

As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified.

Baseline Building

65%

 

Return/Relief Motor Efficiency

Applicability

All return fans, except those specified using the power-per-unit-flow method

Definition

The full-load efficiency of the motor serving the supply fan

Units

Unitless

Input Restrictions

As designed. Not applicable when the power-per-unit-flow method is used.

Baseline Building

For baseline systems 1, 2, 9, 10, 12, and 13 is 80%. For baseline systems 3 through 8 and 11, fan motor efficiency is determined from Table G3.9.1 of Standard 90.1-2019 for the next motor size greater than the bhp calculated, through the process described above, using a totally enclosed fan motor at 1800 rpm.

 

Motor Position

Applicability

All return fans

Definition

The position of the supply fan motor relative to the cooling air stream. The choices are in the air stream or out of the air stream.

Units

List (see above)

Input Restrictions

As designed

Baseline Building

In the air stream

 

Fan Part-Flow Power Curve

Applicability

All return fans for variable flow fan systems

Definition

A part-load power curve that represents the percentage full-load power draw of the return fan as a function of the percentage full-load airflow

Units

Unitless ratio

Input Restrictions

As designed. The default fan curve shall be selected from Equation (10) and Table 57 for the type of fan specified in the proposed design.

Baseline Building

Not applicable for baseline building systems 1 through 4. The curve for “Multi zone VAV with static pressure reset curve” shall be used for baseline building systems 5 through 8 and system 11.

 

Return/Relief Fan Power Index

Applicability

Any system with a return fan

Definition

The return fan power per unit of flow

Units

kW/cfm

Input Restrictions

As specified in the manufacturers’ literature

Baseline Building

Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 53. This power is then multiplied by the return fan ratio.