Fan System Modeling Method |
|
---|---|
Applicability |
All fan systems |
Definition |
Software commonly models fans in three ways.
The latter two methods are commonly used for VAV and other larger fan systems. |
Units |
List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions |
As designed. The power-per-unit-flow method shall be used when no fan performance data are available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules |
The baseline building fan system for Systems 1, 2, 9, and 10 is specified using the power-per-unit-flow method. For systems 3-8 and 11-13, the break horsepower method shall be used for the baseline building. |
Supply Fan Design Air Rated Capacity |
|
---|---|
Applicability |
All fan systems |
Definition |
The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units |
cfm |
Input Restrictions |
As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules |
The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the return air for zones. The design supply air flow rate is the larger of the flow rate required to meet space conditioning requirements and the required ventilation flow rate. (The ventilation requirements may dictate supply air flow rate requirements for laboratory spaces and other spaces with special process requirements.) The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. For laboratory spaces, the design air flow rate calculation shall be based on a 17 degree temperature differential rather than 20. For baseline systems 9 and 10, the design air flow rate calculation shall be based on the temperature difference between a supply air temperature setpoint of 105 °F and the design space heating temperature setpoint, the minimum outdoor air flow rate or the airflow rate required to comply with applicable codes, whichever is greater. If the proposed design includes a fan(s) to provide non-mechanical cooling (ventilation only), the baseline building design shall include a separate fan to provide non-mechanical cooling, sized and controlled the same as the proposed building design. |
Fan Control Method |
|||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All fan systems |
||||||||||||||||||||
Definition |
A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
||||||||||||||||||||
Units |
List (see above) |
||||||||||||||||||||
Input Restrictions |
As designed |
||||||||||||||||||||
Baseline Rules |
Prescribed based on the baseline building HVAC system type. See the table below
|
Supply Fan Brake Horsepower |
|
---|---|
Applicability |
All fan systems, except those specified using the power-per-unit-flow method |
Definition |
The design shaft brake horsepower of the supply fan(s). Fans for parallel fan-powered boxes are not included in fan power calculations. |
Units |
Horsepower (hp) |
Input Restrictions |
As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not required. |
Baseline Rules |
See Table 3.7.3-2 |
Supply Fan Static Pressure |
|
---|---|
Applicability |
All fan systems, except those specified using the power-per-unit-flow method |
Definition |
The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units |
Inches of water column (in. H20) |
Input Restrictions |
As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules |
Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use the brake horsepower modeling method. |
Supply Fan Efficiency |
|
---|---|
Applicability |
All fan systems, except those specified using the power-per-unit-flow method |
Definition |
The efficiency of the fan at design conditions |
Units |
Unitless |
Input Restrictions |
As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules |
Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use the brake horsepower modeling method. |
Supply Motor Efficiency |
|
---|---|
Applicability |
All supply fans, except those specified using the power-per-unit-flow method |
Definition |
The full-load efficiency of the motor serving the supply fan |
Units |
Unitless |
Input Restrictions |
As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules |
Table 3.7.3-4. |
Table 3.7.3-4 – Nominal Efficiency for Electric Motors (%)
Horsepower |
Efficiency |
Horsepower |
Efficiency |
Horsepower |
Efficiency |
1 |
85.5 |
15 |
92.4 |
75 |
95.4 |
1.5 |
86.5 |
20 |
93.0 |
100 |
95.4 |
2 |
86.5 |
25 |
93.6 |
125 |
95.4 |
3 |
89.5 |
30 |
93.6 |
150 |
95.8 |
5 |
89.5 |
40 |
94.1 |
>= 200 |
95.8 |
7.5 |
91.7 |
50 |
94.5 |
|
|
10 |
91.7 |
60 |
95.0 |
|
|
Fan Position |
|
---|---|
Applicability |
All supply fans |
Definition |
The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units |
List (see above) |
Input Restrictions |
As designed. |
Baseline Rules |
Draw through |
Motor Position |
|
---|---|
Applicability |
All supply fans |
Definition |
The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units |
List (see above) |
Input Restrictions |
As designed. |
Baseline Rules |
In the air stream |
Fan Part-Flow Power Curve |
|||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All variable flow fan systems |
||||||||||||||||||||||||
Definition |
A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. |
||||||||||||||||||||||||
Units |
Unitless ratio |
||||||||||||||||||||||||
Input Restrictions |
As designed. If data is unavailable, a default fan curve shall be selected from COMNET Appendix H for the fan type used in the proposed design. (Equation 3.7.3-1)
$$Greater\ of$$ $$PLR = a+b\cdot FanRatio+c\cdot FanRatio^{2}+d\cdot FanRatio^{3}$$ $$PLR=PowerMin$$ where
|
||||||||||||||||||||||||
Baseline Rules |
Only applicable baseline building systems 5-8 and 11. The part load for the baseline building fan shall be determined from either Table 3.7.3-6 for Equation 3.7.3-1 with a = .0013, b = 0.1470, c = 0.9506 and d = 0.0998. Table 3.7.3-5 Baseline Building VSD Performance
|
Supply Fan kW |
|||||
---|---|---|---|---|---|
Applicability |
Fan systems that use the power-per-unit-flow method |
||||
Definition |
The supply fan power per unit of flow. |
||||
Units |
kW/cfm |
||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (Equation 3.7.3-2) $$Fan_{kW}=0.365\times \frac{Q_{rated}}{30,000}$$ where
|
||||
Baseline Rules |
Applicable to baseline systems 1, 2, 9, and 10. See Table 3.7.3.2 |
Fan System Modeling Method |
|
---|---|
Applicability |
All fan systems |
Definition |
Software commonly models fans in three ways. The simple method is for the user to enter the electric power per unit of flow (W/cfm). This method is commonly used for unitary equipment and other small fan systems. A more detailed method is to model the fan as a system whereby the static pressure, fan efficiency, and motor efficiency are specified at design conditions. A third method is to specify brake horsepower at design conditions instead of fan efficiency and static pressure. This is a variation of the second method whereby brake horsepower is specified in lieu of static pressure and fan efficiency. |
Units |
List: Power-Per-Unit-Flow, Design Pressure Drop, or Brake Horsepower |
Input Restrictions |
As designed |
Baseline Building |
Systems 1, 2, 9, and 10 should use power per unit flow if allowed by the software. If not allowed used one of the other methods as described in Table 54. All other baseline system shall use the brake horsepower method. If that method is not available, static pressure method should be used. |
Supply Fan Design Air Rated Capacity |
|
---|---|
Applicability |
All fan systems |
Definition |
The design airflow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units |
cfm |
Input Restrictions |
As designed |
Baseline Building |
The software shall automatically size the system airflow to meet the baseline building loads based on
The baseline system airflow is determined by the load to be met by the airflow and the 20°F (11°C) temperature difference. The loads to be used would be the design load as determined by the sizing runs specified in Section G3.1.2.2, not the cooling or heating capacity of the system as determined using the sizing factors, also specified in G3.1.2.2. Using the system cooling and heating capacity will result in oversized baseline system airflows and energy cost because of the oversizing factors used in G3.1.2.2. See additional discussion in Section 3.6.5.1 for VAV systems. spaces with special process requirements.) The supply fan design airflow rate shall be the sum of the calculated design airflow for the thermal zones served by the fan system.
For laboratory spaces, the design airflow rate calculation shall be based on a 17°F temperature differential rather than 20°F. For baseline systems 9 and 10, the design supply airflow rates shall be based on the temperature difference between a SAT setpoint of 105°F and the design space heating temperature setpoint, the minimum outdoor airflow rate or the airflow rate required to comply with applicable codes, whichever is greater. If the proposed design HVAC system airflow rate based on latent loads greater than the same based on sensible loads, then the same supply-air-to-room humidity ratio difference (gr/lb) used to calculate the proposed design airflow should be used to calculate the design airflow rates for the baseline building. |
Fan Control Method |
|
---|---|
Applicability |
All fan systems |
Definition |
A description of how the supply (and return/relief) fan(s) is controlled. The options include:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
Based on the baseline system type, summarized in Table 55 |
Table 55. Baseline Building Fan Control Method
System No. |
System Type |
Fan Control |
System 1 |
Package terminal air conditioner |
Constant volume |
System 2 |
Packaged terminal heat pump |
Constant volume |
System 3 |
Packaged roof top air conditioner |
Constant volume |
System 4 |
Packaged roof top heat pump |
Constant volume |
System 5 |
Packaged rooftop VAV with reheat |
Variable volume, variable speed drive (VSD) |
System 6 |
Packaged rooftop VAV with PFP boxes and reheat |
Variable volume, VSD |
System 7 |
Packaged rooftop VAV with reheat |
Variable volume, VSD |
System 8 |
VAV with parallel fan-powered boxes and reheat |
Variable volume, VSD |
System 9 |
Warm air furnace, gas fired |
Constant volume |
System 10 |
Warm air furnace, electric |
Constant volume |
System 11 |
Single zone VAV |
Variable volume, VSD |
System 12 |
Single zone system (CHW and HW boiler) |
Constant volume |
System 13 |
Single zone system (CHW and electric resistance) |
Constant volume |
Supply Fan Brake Horsepower |
|
---|---|
Applicability |
All fan systems, except those specified using the power-per-unit-flow method |
Definition |
The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the supply fan kW is supplied. |
Units |
Horsepower (hp) |
Input Restrictions |
As designed. If this building descriptor is specified for the proposed design, then the static pressure and fan efficiency are not required. |
Baseline Building |
Fans for parallel fan-powered boxes are not included in fan power calculations. Table 53 of this document gives the baseline building fan system brake horsepower. The brake horsepower for the supply fan is this value times the supply fan ratio (see above). |
Supply Fan Static Pressure |
|
---|---|
Applicability |
All fan systems, except those specified using the power-per-unit-flow method |
Definition |
The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units |
Inches of water column (in. H2O) |
Input Restrictions |
As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Building |
The baseline building is defined by Table 53. This approach only works if the system has only a supply fan. If return/exhaust fans are also present in the system, then the supply fan bhp needs to be calculated and divided amongst the supply, return, and exhaust fans. |
Supply Fan Efficiency |
|
---|---|
Applicability |
All fan systems, except those specified using the power-per-unit-flow method |
Definition |
The efficiency of the fan at design conditions; this is the static efficiency and does not include motor losses |
Units |
Unitless |
Input Restrictions |
As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Building |
The baseline supply fan efficiency shall be 65%. |
Supply Motor Efficiency |
|||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All supply fans, except those specified using the power-per-unit-flow method |
||||||||||||||||||||||||||||||||||||||||
Definition |
The full-load efficiency of the motor serving the supply fan |
||||||||||||||||||||||||||||||||||||||||
Units |
Unitless |
||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. Not applicable when the power-per-unit-flow method is used. |
||||||||||||||||||||||||||||||||||||||||
Baseline Building |
For systems 1, 2, 9, and 10, motor efficiency is assumed to be 80%. The motor efficiency for systems 3 through 8 is determined from Table G3.9.1 of ASHRAE Standard 90.1-2019 (Table 56 below). Table 56. Minimum Nominal Efficiency for Electric Motors (%)
|
Fan Position |
|
---|---|
Applicability |
All supply fans |
Definition |
The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
Draw through |
Motor Position |
|
---|---|
Applicability |
All supply fans |
Definition |
The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
In the air stream |
Fan Part-Flow Power Curve |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All variable flow fan systems |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Definition |
A part-load power curve that represents the percentage full-load power draw of the supply fan as a function of the percentage full-load airflow. The curve is typically represented as a cubic equation with an absolute minimum power draw specified. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units |
Unitless ratio |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
The fan curve shall be selected from Equation (10) and Table 57 for the type of fan specified in the proposed design.
Where: PLR = Ratio of fan power at part load conditions to full load fan power PowerMin = Minimum fan power ratio FanRatio = Ratio of cfm at part-load to full-load cfm a, b, c and d = Constants from Table 57 Table 57. Fan Curve Default Values
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Building |
Not applicable for baseline building systems 1 through 4. Baseline systems 5 through 8 will use the curve for “Multi zone VAV with fixed static pressure setpoint” curve. System 11 shall use the “Single zone VAV fan” curve. Constant volume fans are used for systems 9, 10, 12, and 13 and hence the descriptor is not applicable. |
Supply Fan Power Index (kW/cfm) |
|
---|---|
Applicability |
Fan systems that use the power-per-unit-flow method |
Definition |
The supply fan power per unit of flow |
Units |
kW/cfm |
Input Restrictions |
As designed or specified in the manufacturers’ literature |
Baseline Building |
Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 53 of this document. This power is then multiplied by the supply fan ratio. |
Static Pressure Reset Controls |
|
---|---|
Applicability |
All VAV fan systems. Baseline systems 5 through 8. |
Definition |
Static pressure reset controls, reset the fan static pressure for VAV systems-based zone damper position. For systems with DDC of individual zone boxes reporting to the central control panel, static pressure setpoint shall be reset based on the zone requiring the most pressure. |
Units |
Unitless |
Input Restrictions |
As designed. If static pressure reset is implemented in the proposed system, the curve for “Multi zone VAV with static pressure reset curve” shall be used. |
Baseline Building |
Not applicable for baseline building systems 1 through 4 or 9, 10, 11, 12, and 13. The curve for “Multi Zone VAV with VSD and fixed SP setpoint”’ shall be used for baseline building systems 5 through 8. |