General
Humidifier Type | |
Applicability | Optional humidifier |
---|---|
Definition | The type of humidifier employed. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Humidistat Maximum Setting | |
Applicability | Systems with humidity control |
---|---|
Definition | The control setpoint for dehumidification |
Units | Percent (%) |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Humidistat Minimum Setting | |
Applicability | Systems with humidity control |
---|---|
Definition | The control setpoint for humidification |
Units | Percent (%) |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Desiccant
Desiccant Type | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | Describes the configuration of desiccant cooling equipment The following configurations for desiccant systems are allowed:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Desiccant Control Mode | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The method of controlling the operation of the desiccant unit. For liquid-based systems this can be either:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Desiccant Air Fraction | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The fraction of the supply air that passes through the desiccant unit. Typically either the minimum outside air fraction or all of the air passes through the desiccant system. |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Desiccant Heat Source | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The source of heat that is used to dry out the desiccant. This can be either:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Liquid Desiccant Performance Curves | ||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | Systems with liquid-based desiccant dehumidification | |||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A set of performance curves that apply to liquid desiccant systems. (6.7.7-1) $$ D\!ESC\!\!-\!\!T\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-2) $$ D\!ESC\!\!-\!\!W\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-3) $$ D\!ESC\!\!-\!\!Gas\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-4) $$ D\!ESC\!\!-\!\!kW\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ where
[table title="Liquid Desiccant Unit Performance Curves" id="liquid-desiccant-unit-performance-curves"]
|
|||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | As designed, default to values in [bookref id="liquid-desiccant-unit-performance-curves"] | |||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Not applicable |
Desiccant Dewpoint Temperature Setpoint | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The setpoint dewpoint temperature of the air leaving the desiccant system |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 50°F. |
Baseline Rules | Not applicable |
Desiccant Heat Exchanger Effectiveness | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The effectiveness of a sensible heat exchanger used with a desiccant system |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Desiccant Heat Exchanger Pressure Drop | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The pressure drop across a sensible heat exchanger used with a desiccant system |
Units | in. H2O |
Input Restrictions | As designed. Defaults to 1.0 in. H2O |
Baseline Rules | Not applicable |
Minimum volume setpoint shall be 50% of the maximum design airflow rate, the minimum ventilation outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is larger. Fan volume shall be reset from 100% airflow at 100% cooling load to minimum airflow at 50% cooling load. Supply air temperature setpoint shall be reset from minimum supply air temperature at 50% cooling load and above to space temperature at 0% cooling load. In heating mode supply air temperature shall be modulated to maintain space temperature, and fan volume shall be fixed at the minimum airflow.
General
Humidifier Type |
|
---|---|
Applicability |
Optional humidifier |
Definition |
The type of humidifier employed. Choices include1 :
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
The baseline building shall have humidification if the proposed design does, but the system shall be non-adiabatic. For systems serving computer rooms, the baseline shall nt have reheat for the purpose of humidification. |
Humidistat Maximum Setting |
|
---|---|
Applicability |
Systems with humidity control |
Definition |
The control setpoint for dehumidification |
Units |
Percent (%) |
Input Restrictions |
As designed |
Baseline Rules |
Same as the proposed design |
Humidistat Minimum Setting |
|
---|---|
Applicability |
Systems with humidity control |
Definition |
The control setpoint for humidification |
Units |
Percent (%) |
Input Restrictions |
As designed |
Baseline Rules |
Same as proposed design |
Desiccant
Desiccant Type |
|
---|---|
Applicability |
Systems with desiccant dehumidification |
Definition |
Describes the configuration of desiccant cooling equipment
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
Not applicable |
Desiccant Control Mode |
|
---|---|
Applicability |
Systems with desiccant dehumidification |
Definition |
The method of controlling the operation of the desiccant unit. For liquid-based systems this can be either:
For solid-based systems the following configurations are possible:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
Not applicable |
Desiccant Air Fraction |
|
---|---|
Applicability |
Systems with desiccant dehumidification |
Definition |
The fraction of the supply air that passes through the desiccant unit. Typically either the minimum outside air fraction or all of the air passes through the desiccant system. |
Units |
Ratio |
Input Restrictions |
As designed |
Baseline Rules |
Not applicable |
Desiccant Heat Source |
|
---|---|
Applicability |
Systems with desiccant dehumidification |
Definition |
The source of heat that is used to dry out the desiccant. This can be either:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
Not applicable |
Desiccant Dewpoint Temperature Setpoint |
|
---|---|
Applicability |
Systems with desiccant dehumidification |
Definition |
The setpoint dewpoint temperature of the air leaving the desiccant system |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed. Defaults to 50°F. |
Baseline Rules |
Not applicable |
Desiccant Heat Exchanger Effectiveness |
|
---|---|
Applicability |
Systems with desiccant dehumidification |
Definition |
The effectiveness of a sensible heat exchanger used with a desiccant system |
Units |
Ratio |
Input Restrictions |
As designed |
Baseline Rules |
Not applicable |
Desiccant Heat Exchanger Pressure Drop |
|
---|---|
Applicability |
Systems with desiccant dehumidification |
Definition |
The pressure drop across a sensible heat exchanger used with a desiccant system |
Units |
in. H2O |
Input Restrictions |
As designed. Defaults to 1.0 in. H2O |
Baseline Rules |
Not applicable |
- 1This information is taken from http://www.dac-hvac.com/ask-rick-what-is-adiabatic-humidification/. The biggest advantages of Adiabatic Humidifiers are: energy savings, precise humidity control, simple technology. The disadvantages are longer absorption distances (more length need in an air handling unit), requires preheat of supply air, typically requires RO water, compressed air required on air/water systems.
This section addresses:
General
Humidifier Type | |
Applicability | Optional humidifier |
---|---|
Definition | The type of humidifier employed. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Humidistat Maximum Setting | |
Applicability | Systems with humidity control |
---|---|
Definition | The control setpoint for dehumidification |
Units | Percent (%) |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Humidistat Minimum Setting | |
Applicability | Systems with humidity control |
---|---|
Definition | The control setpoint for humidification |
Units | Percent (%) |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Desiccant
Desiccant Type | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | Describes the configuration of desiccant cooling equipment The following configurations for desiccant systems are allowed:
|
Units | List (see above) |
Input Restrictions | As designed |
Desiccant Control Mode | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The method of controlling the operation of the desiccant unit. For liquid-based systems this can be either:
|
Units | List (see above) |
Input Restrictions | As designed |
Desiccant Air Fraction | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The fraction of the supply air that passes through the desiccant unit. Typically either the minimum outside air fraction or all of the air passes through the desiccant system. |
Units | Ratio |
Input Restrictions | As designed |
Desiccant Heat Source | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The source of heat that is used to dry out the desiccant. This can be either:
|
Units | List (see above) |
Input Restrictions | As designed |
Liquid Desiccant Performance Curves | ||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | Systems with liquid-based desiccant dehumidification | |||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A set of performance curves that apply to liquid desiccant systems. (6.7.7-1) $$ D\!ESC\!\!-\!\!T\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-2) $$ D\!ESC\!\!-\!\!W\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-3) $$ D\!ESC\!\!-\!\!Gas\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-4) $$ D\!ESC\!\!-\!\!kW\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ where
[table title="Liquid Desiccant Unit Performance Curves" id="liquid-desiccant-unit-performance-curves"]
|
|||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | As designed, default to values in [bookref id="liquid-desiccant-unit-performance-curves"] |
Desiccant Dewpoint Temperature Setpoint | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The setpoint dewpoint temperature of the air leaving the desiccant system |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 50°F. |
Desiccant Heat Exchanger Effectiveness | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The effectiveness of a sensible heat exchanger used with a desiccant system |
Units | Ratio |
Input Restrictions | As designed |
Desiccant Heat Exchanger Pressure Drop | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The pressure drop across a sensible heat exchanger used with a desiccant system |
Units | in. H2O |
Input Restrictions | As designed. Defaults to 1.0 in. H2O |
General
Humidifier Type | |
Applicability | Optional humidifier |
---|---|
Definition | The type of humidifier employed. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Humidistat Maximum Setting | |
Applicability | Systems with humidity control |
---|---|
Definition | The control setpoint for dehumidification |
Units | Percent (%) |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Humidistat Minimum Setting | |
Applicability | Systems with humidity control |
---|---|
Definition | The control setpoint for humidification |
Units | Percent (%) |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Desiccant
Desiccant Type | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | Describes the configuration of desiccant cooling equipment The following configurations for desiccant systems are allowed:
|
Units | List (see above) |
Input Restrictions | As designed |
Desiccant Control Mode | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The method of controlling the operation of the desiccant unit. For liquid-based systems this can be either:
|
Units | List (see above) |
Input Restrictions | As designed |
Desiccant Air Fraction | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The fraction of the supply air that passes through the desiccant unit. Typically either the minimum outside air fraction or all of the air passes through the desiccant system. |
Units | Ratio |
Input Restrictions | As designed |
Desiccant Heat Source | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The source of heat that is used to dry out the desiccant. This can be either:
|
Units | List (see above) |
Input Restrictions | As designed |
Liquid Desiccant Performance Curves | ||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | Systems with liquid-based desiccant dehumidification | |||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A set of performance curves that apply to liquid desiccant systems. (6.7.7-1) $$ D\!ESC\!\!-\!\!T\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-2) $$ D\!ESC\!\!-\!\!W\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-3) $$ D\!ESC\!\!-\!\!Gas\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ (6.7.7-4) $$ D\!ESC\!\!-\!\!kW\!\!-\!\!FTW = a + b \times T + c \times T^2 + d \times w + e \times w^2 + f \times T \times w$$ where
[table title="Liquid Desiccant Unit Performance Curves" id="liquid-desiccant-unit-performance-curves"]
|
|||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | As designed, default to values in [bookref id="liquid-desiccant-unit-performance-curves"] |
Desiccant Dewpoint Temperature Setpoint | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The setpoint dewpoint temperature of the air leaving the desiccant system |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 50°F. |
Desiccant Heat Exchanger Effectiveness | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The effectiveness of a sensible heat exchanger used with a desiccant system |
Units | Ratio |
Input Restrictions | As designed |
Desiccant Heat Exchanger Pressure Drop | |
Applicability | Systems with desiccant dehumidification |
---|---|
Definition | The pressure drop across a sensible heat exchanger used with a desiccant system |
Units | in. H2O |
Input Restrictions | As designed. Defaults to 1.0 in. H2O |