3.7 HVAC Secondary Systems

This group of building descriptors relate to the secondary HVAC systems. There is not a one-to-one relationship between secondary HVAC system components in the proposed design and the baseline building since the baseline building system is determined from building type, size and heating source. Appendix A shows the applicability of each building descriptor for the eight baseline building systems. Depending on the nature of the proposed design, any of the building descriptors could apply.

90.1-2016 BM

This group of building descriptors relate to the secondary HVAC systems. There is not a one-to-one relationship between secondary HVAC system components in the proposed design and the baseline building since the baseline building system is determined from building type, size and heating source. See Table 3.1-1, 3.1-2 and 3.1-3. Additional detail on the baseline building systems is provided in the tables below.  Depending on the nature of the proposed design, any of the building descriptors could apply.

Table 3.7-1: Baseline Building System Type

Baseline Building System

System Type

System 1 – PTAC

Single Zone Heating and Cooling

System 2 – PTHP

Single Zone Heating and Cooling

System 3 – PSZ-AC

Single Zone Heating and Cooling

System 4 – PSZ-HP

Single Zone Heating and Cooling

System 5 – Packaged VAV with Reheat

Single Duct VAV

System 6 – Packaged VAV with PFP boxes

Single Duct VAV

System 7 – VAV with Reheat

Single Duct VAV

System 8 – VAV with PFP boxes

Single Duct VAV

System 9 – Heating and Ventilation

Constant Volume Heat/Vent (no cooling)

System 10 – Heating and Ventilation

Constant Volume Heat/Vent (no cooling)

System 11. SZ–VAV

Single-zone VAV

System 12. SZ-CV-HW

Single zone with hot water heat

System 13. SZ-CV-ER

Single zone with electric resistance heat

 

Table 3.7-2: Summary of Baseline Building Secondary HVAC System Properties

System

Fan Control

Economizer

Cooling Type

Cooling Efficiency.

Minimum Supply T.

Heating Type

Heating Efficiency

Maximum Supply T.

1 PTAC

Constant volume

Not required

Direct Expansion

Minimum SEER or EER based on equipment type and output capacity of proposed unit(s).  Adjusted EER is calculated to account for supply fan energy.

20 °F below occupied space cooling setpoint

Hot-water fossil fuel boiler

Minimum AFUE, Thermal Efficiency, COP or HSPF based on equipment type and output capacity of baseline unit(s).

20 °F above occupied space heating setpoint

2 PTHP

Electric heat pump

3 PSZ-AC

Integrated economizer with dry-bulb high limit by climate zone. See 6.7.4 ‘Outside Air Controls and Economizer’ for details and exceptions.

Fossil fuel furnace

4 PSZ-HP

Electric heat pump

5 PVAV

Variable volume

Hot-water fossil fuel boiler

6 PVAV / PFP

Electric resistance

7 VAV

Chilled water

See 6.8 Primary Systems

Hot-water fossil fuel boiler

8 VAV / PFP

Electric resistance

9 HV Furnace

Constant volume

Not required

None

None

Fossil fuel furnace

10 HV Electric

Electric resistance

11 SZ-VAV

Variable volume

Integrated economizer with dry-bulb high limit by climate zone. See 6.7.4 for details.

Chilled water

See 6.8 Primary Systems

See note.

12 SZ-CV-HW

Constant Volume

Hot-water fossil fuel boiler

13 SZ-CV-ER

Electric resistance

Table 3.7-3: Summary of Baseline Building Variable Volume Fan Control and Reheat

Code

Supply Fan Control

PFP Fan

Reheat Terminal Flow

5 PVAV

Variable speed controlled by variable speed drives.

The part load performance of VAV fans is required to be modeled in accordance to section ‘Fan Part Load Curve’ in ‘Fan Systems’.

 

Minimum volume setpoint for reheat is highest of 30% of zone peak flow, minimum outdoor air flow rate or airflow rate required by applicable rating authority. See Section 3.6.5 for details

 

6 PVAV / PFP

PIU fan would be constant volume. AHU fan should cycle on only for cooling. Zone fans should provide unoccupied heating.

Fans for PIU units are sized for 50% of peak design primary air

7 VAV

 

 

8 VAV / PFP

PIU fan would be constant volume. AHU fan should cycle on only for cooling. Zone fans should provide unoccupied heating.

Fans for PIU units are sized for 50% of peak design primary air

 

90.1-2019

This group of building descriptors relate to the secondary HVAC systems. There is not a one-to-one relationship between secondary HVAC system components in the proposed design and the baseline building since the baseline building system is determined from building type, size, and heating source. Depending on the nature of the proposed design, any of the building descriptors could apply.

The HVAC baseline systems are described in the summary tables below for reference. The details of individual building descriptor definitions can be found in Sections 3.8 and 3.9.

Table 41. System 1 and System 2 Descriptions

System Description

Packaged terminal air conditioner (#1) or packaged terminal heat pump (#2)

Supply Fan Power

Fan power integral to unit efficiency. Fan power = 0.3 ´ cfms. Refer to building descriptor Fan Systems. Ventilation is provided through the system.

Supply Fan Control

Constant volume

Min Supply Temp

20°F below occupied space cooling setpoint

Cooling System

DX

Cooling Efficiency

Minimum seasonal energy efficiency ratio (SEER) or EER based on equipment type and output capacity of proposed unit(s). Adjusted EER is calculated to account for supply fan energy.

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

Hot water boiler (#1) or heat pump (#2)

Heating Efficiency

Minimum annual fuel utilization efficiency (AFUE), thermal efficiency, COP, or heating seasonal performance factor (HSPF) based on equipment type and output capacity of baseline unit(s)

Economizer

None

Ducts

N/A (not ducted)

Table 42. System 3 and System 4 Descriptions

System Description

Packaged single zone with gas furnace/electric air conditioning (#3) or heat pump (#4)

Supply Fan Power

See building descriptor Fan Systems, Section 3.7.3 of this document

Supply Fan Control

Constant volume

Min Supply Temp

20°F below occupied space cooling setpoint

Cooling System

DX

Cooling Efficiency

Minimum SEER or EER based on equipment type and output capacity of baseline unit(s). Adjusted EER is calculated to account for supply fan energy.

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

Fossil fuel furnace (#3) or heat pump (#4)

Heating Efficiency

Minimum AFUE, thermal efficiency, COP, or HSPF based on equipment type and output capacity of baseline unit(s)

Economizer

Integrated economizer with dry-bulb high limit by climate zone. Refer to building descriptor Outside Air Controls and Economizer, Section 3.7.4, for details.

Table 43. System 5 Description

System Description

Packaged VAV with DX cooling, fossil fuel boiler and hot-water reheat

Supply Fan Power

See building descriptor Fan Systems, Section 3.7.3 of this document

Supply Fan Control

  • Variable speed controlled by variable speed drives
  • The part load performance of VAV fans is required to be modeled in accordance to section Fan Part Load Curve in Fan Systems, Section 3.7.3 of this document

Return Fan Control

Same as supply fan

Minimum Supply Temp

20°F below occupied space cooling setpoint

Supply Temp Control

The air temperature for cooling shall be reset higher by 5°F under minimum cooling load conditions. This strategy is described in Section 3.7.2.2 of this document.

Cooling System

DX

Cooling Efficiency

Minimum efficiency based on average output capacity of equipment unit(s)

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

Hot water boiler, with hot water (HW) reheat

Reheat Terminal Airflow

System 5: Minimum volume setpoint for reheat is highest of 30% of zone peak flow, minimum outdoor airflow rate or airflow rate required by applicable rating authority.

See Section 3.7.5 for details.

Hot Water Pumping System

The pumping system shall be modeled as primary-only with continuous variable flow and a minimum of 25% of the design flow rate. Hot-water systems serving 120,000 ft2 or more shall be modeled with variable-speed drives, and systems serving less than 120,000 ft2 shall be modeled as riding the pump curve. See Section 3.8.5 of this document for details.

Heating Efficiency

Minimum efficiency based on average output capacity of baseline equipment unit(s)

Economizer

Integrated economizer with dry-bulb high limit by climate zone. Refer to building descriptor Outside Air Controls and Economizer, Section 3.7.4, for details.

Table 44. System 6 Description

System Description

Packaged VAV, with DX cooling, electric heating and parallel fan-powered boxes with electric heat

Supply Fan Power

See building descriptor Fan Systems, Section 3.7.3 of this document

Supply Fan Control

  • Variable speed controlled by variable speed drives
  • The part load performance of VAV fans is required to be modeled in accordance to section Fan Part Load Curve in Fan Systems
  • Power induction unit (PIU) fan would be constant volume

Return Fan Control

Same as supply fan

Minimum Supply Temp:

20°F below occupied space cooling setpoint

Supply Temp Control

The air temperature for cooling shall be reset higher by 5°F under minimum cooling load conditions. This strategy is described in Section 3.7.2.2 of this document.

Cooling System

DX cooling

Cooling Efficiency

Minimum efficiency based on average output capacity of equipment unit(s)

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

Electric resistance, electric reheat terminals

Heating Efficiency

NA

Reheat Terminal Airflow

Fans for PIU units are sized for 50% of peak design primary air.

Minimum volume setpoint for reheat is highest of 30% of peak design primary airflow rate, minimum outdoor airflow rate or airflow rate required by applicable rating authority. See Section 3.7.5 for details.

Economizer

Integrated economizer with dry-bulb high limit by climate zone. Refer to building descriptor Outside Air Controls and Economizer, Section 3.7.4, for details.

Table 45. System 7 Description

System Description

VAV system with HW boiler, HW reheat and chilled water (CHW) cooling

Supply Fan Power

See building descriptor Fan Systems, Section 3.7.3 of this document.

Supply Fan Control

Variable speed controlled by variable speed drives.

The part load performance of VAV fans is required to be modeled in accordance with Fan Part Load Curve in Fan Systems.

Minimum Supply Temp

20°F below occupied space cooling setpoint

Supply Temp Control

The air temperature for cooling shall be reset higher by 5°F under minimum cooling load conditions. This strategy is described in Section 3.7.2.2 of this document.

Cooling System

Chiller

Cooling Efficiency

Minimum efficiency based on the output capacity of specific equipment unit(s)

Chilled Water Pumping System

The baseline building design pump power shall be 22 W/gpm. Chilled-water systems with a cooling capacity of 300 tons or more shall be modeled as primary/secondary systems with variable-speed drives on the secondary pumping loop and a minimum flow of 25% of the design flow rate. Chilled-water pumps in systems serving less than 300 tons cooling capacity shall be modeled as a primary/ secondary system with secondary pump riding the pump curve. See Section 3.8.5 of this document for details.

Chiller Type and Number

Electric chillers shall be used in the baseline building design. The baseline building design’s chiller plant shall be modeled with chillers having the number and type as indicated in Standard 90.1-2019, Table G3.1.3.7, as a function of building peak cooling load.

Maximum Supply Temp

20°F above occupied space heating setpoint

Reheat Terminal Flow

System 5: Minimum volume setpoint for reheat is highest of 30% of zone peak flow, minimum outdoor airflow rate or airflow rate required by applicable rating authority.

See Section 3.7.5 for details.

Heating System

Hot water boiler (system 8), hot water reheat

Hot Water Pumping System

The pumping system shall be modeled as primary-only with continuous variable flow and a minimum flow of 25% of the design flow rate. Hot-water systems serving 120,000 ft2 or more shall be modeled with variable-speed drives, and systems serving less than 120,000 ft2 shall be modeled as riding the pump curve.

Heating Efficiency

Minimum efficiency based on the output capacity of specific baseline equipment unit(s)

Economizer

Integrated economizer with dry-bulb high limit by climate zone. Refer to building descriptor ‘Outside Air Controls and Economizer’, Section 3.7.4, for details.

Table 46. System 8 Description

System Description

VAV with CHW cooling, electric resistance heating, and PFP boxes with electric heat

Supply Fan Power

See building descriptor Fan Systems, Section 3.7.3 of this document

Supply Fan Control

Variable speed controlled by variable speed drives. The part load performance of VAV fans is required to be modeled in accordance with section Fan Part Load Curve in Fan Systems.

Minimum Supply Temp

20°F below occupied space cooling setpoint

Supply Temp Control

The air temperature for cooling shall be reset higher by 5°F under minimum cooling load conditions. This strategy is described in Section 3.7.2.2 of this document.

Cooling System

Chiller

Cooling Efficiency

Minimum efficiency based on the proposed output capacity of specific equipment unit(s)

Chilled Water Pumping System

The baseline building design pump power shall be 22 W/gpm. Chilled-water systems with a cooling capacity of 300 tons or more shall be modeled as primary/secondary systems with variable-speed drives on the secondary pumping loop and a minimum flow of 25% of the design flow rate. Chilled-water pumps in systems serving less than 300 tons cooling capacity shall be modeled as a primary/secondary system with secondary pump riding the pump curve. See Section 3.8.5 of this document for details.

Chiller Type and Number

Electric chillers shall be used in the baseline building design. The baseline building design’s chiller plant shall be modeled with chillers having the number and type as indicated in Standard 90.1-2019, Table G3.1.3.7, as a function of building peak cooling load.

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

Electric resistance, electric resistance reheat

Reheat Terminal Airflow

Fans for PIU units are sized for 50% of peak design primary air. Minimum volume setpoint for reheat is highest of 30% of peak design primary airflow rate, minimum outdoor airflow rate or airflow rate required by applicable rating authority. See Section 3.7.5 for details.

Hot Water Pumping System

N/A

Heating Efficiency

N/A

Economizer

Integrated dry bulb economizer with dry-bulb high limit based on climate zone. Refer to building descriptor Outside Air Controls and Economizer, Section 3.7.4, for details.

Table 47. System 9 and System 10 Description

System 9 Description

Heating and ventilation only system

Supply Fan Power

See building descriptor Fan Systems, Section 3.7.3 of this document

Supply Fan Control

Constant volume

Minimum

Supply Temp

N/A

Cooling System

None

Cooling Efficiency

N/A

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

Gas furnace

Hot Water Pumping System

N/A

Heating Efficiency

Minimum efficiency based on the baseline output capacity of specific equipment unit(s)

Economizer

Not required for system 9

System 10 Description

Heating and ventilation only system

Supply Fan Power

See building descriptor ‘Fan Systems’

Supply Fan Control

Constant volume

Minimum Supply Temp:

N/A

Cooling System

None

Cooling Efficiency

N/A

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

Electric resistance

Hot Water Pumping System

N/A

Heating Efficiency

N/A

Economizer

Not required for system 10

Table 48. System 11 Description

System 11 Description

Single zone variable air volume system

Supply Fan Power

See building descriptor Fan Systems, Section 3.7.3 of this document

Supply Fan Control

Variable speed controlled by variable speed drives. The part load performance of VAV fans is required to be modeled in accordance with section Fan Part Load Curve in Fan Systems

Minimum

Supply Temp

20°F below occupied space cooling setpoint

Cooling System

Chiller

Cooling Efficiency

Minimum efficiency based on the proposed output capacity of specific equipment unit(s)

Chilled Water Pumping System

The baseline building design pump power shall be 22 W/gpm. Chilled-water systems with a cooling capacity of 300 tons or more shall be modeled as primary/secondary systems with variable-speed drives on the secondary pumping loop and a minimum flow of 25% of the design flow rate. Chilled-water pumps in systems serving less than 300 tons cooling capacity shall be modeled as a primary/secondary system with secondary pump riding the pump curve. See Section 3.8.5 of this document for details.

Chiller Type and Number

Electric chillers shall be used in the baseline building design. The baseline building design’s chiller plant shall be modeled with chillers having the number and type as indicated in Standard 90.1-2019, Table G3.1.3.7, as a function of building peak cooling load.

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

For climate zones 0 to 3A, the baseline system shall be modeled with electric resistance heating. For all other climate zones, the heating system shall be hot-water fossil-fuel boiler.

Hot Water Pumping System

When boilers are required, the pumping system shall be modeled as primary-only with continuous variable flow and a minimum flow of 25% of the design flow rate. Hot-water systems serving 120,000 ft2 or more shall be modeled with variable-speed drives, and systems serving less than 120,000 ft2 shall be modeled as riding the pump curve.

Heating Efficiency

NA for electric resistance heating. For hot-water boilers, the minimum efficiency based on the output capacity of specific baseline equipment unit(s)

Reheat Terminal Flow

N/A

Economizer

Integrated dry bulb economizer with dry-bulb high limit based on climate zone. Refer to building descriptor Outside Air Controls and Economizer, Section 3.7.4, for details.

Table 49. System 12 and 13 Description

System 12, 13 Description

Single-zone system

Supply Fan Power

See building descriptor Fan Systems, Section 3.7.3 of this document

Supply Fan Control

Constant volume

Minimum

Supply Temp

N/A

Cooling System

Chilled Water

Cooling Efficiency

Minimum efficiency based on the proposed output capacity of specific equipment unit(s)

Chilled Water Pumping System

The baseline building design pump power shall be 22 W/gpm. Chilled-water systems with a cooling capacity of 300 tons or more shall be modeled as primary/secondary systems with variable-speed drives on the secondary pumping loop and a minimum flow of 25% of the design flow rate. Chilled-water pumps in systems serving less than 300 tons cooling capacity shall be modeled as a primary/secondary system with secondary pump riding the pump curve. See Section 3.8.5 of this document for details.

Chiller Type and Number

Electric chillers shall be used in the baseline building design. The baseline building design’s chiller plant shall be modeled with chillers having the number and type as indicated in Standard 90.1-2019, Table G3.1.3.7, as a function of building peak cooling load.

Maximum Supply Temp

20°F above occupied space heating setpoint

Heating System

Hot-water fossil fuel boiler for system 12 and electric resistance heating for system 13.

Hot Water Pumping System

When boilers are required, the pumping system shall be modeled as primary-only with continuous variable flow and a minimum flow of 25% of the design flow rate. Hot-water systems serving 120,000 ft2 or more shall be modeled with variable-speed drives, and systems serving less than 120,000 ft2 shall be modeled as riding the pump curve.

Heating Efficiency

NA for electric resistance heating. For hot-water boilers, the minimum efficiency based on the output capacity of specific baseline equipment unit(s)

Reheat Terminal Flow

N/A

Economizer

Integrated dry bulb economizer with dry-bulb high limit based on climate zone. Refer to building descriptor ‘Outside Air Controls and Economizer’, Section 3.7.4, for details.

Table 50. Summary of Baseline Building Secondary HVAC System Properties

System

Fan Control

Economizer

Cooling Type

Cooling Efficiency

Minimum Supply T.

Heating Type

Heating Efficiency

Maximum Supply T.

System 1-PTAC

Constant volume

Not required

Direct Expansion

Minimum SEER EER, COP or kW/ton based on equipment type and output capacity of proposed unit(s). Adjusted EER is calculated to account for supply fan energy.

20 °F below occupied space cooling setpoint

Hot-water fossil fuel boiler

Minimum AFUE, Thermal Efficiency, COP or HSPF based on equipment type and output capacity of baseline unit(s).

20 °F above space temperature setpoint for systems 1-4 and 11-13.

 

Same as maximum reset cooling supply air temperature for systems 5-8 and 105 °F for systems 9 and 10

System 2-PTHP

Electric heat pump

System 3-PSZ-AC

Integrated economizer with dry-bulb high limit by climate zone.

Fossil fuel furnace

System 4-PSZ-HP

Electric heat pump

System 5-PVAV

Variable volume

Hot-water fossil fuel boiler

System 6-PVAV / PFP

Electric resistance

System 7-VAV

Chilled water

Hot-water fossil fuel boiler

System 8-VAV / PFP

Electric resistance

System 9/10-HV Furnace

Constant volume

Not required

None

None

Fossil fuel furnace

HV Electric

Electric resistance

System 11-SZ-VAV

Variable volume

Integrated economizer with dry-bulb high limit by climate zone.

Chilled water

See 6.8 Primary Systems

See note.

System 12-SZ-CV-HW

Constant Volume

Hot-water fossil fuel boiler

System 13-SZ-CV-ER

Electric resistance

Building EQ

This group of building descriptors relate to the secondary HVAC systems.

Energy Star

This group of building descriptors relate to the secondary HVAC systems.