3.7.3.4 Exhaust Fan Systems

90.1-2016 BM

Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks. The baseline building has exhaust fans when the proposed design has exhaust fans. The exhaust air flow is the same for the baseline building and the proposed design.

Exhaust Fan Name

Applicability

All exhaust systems serving multiple thermal blocks

Definition

A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name.

Units

Text, unique

Input Restrictions

Where applicable, this should match the tags that are used on the plans.

Baseline Rules

The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used.

 

Exhaust Fan System Modeling Method

Applicability

All exhaust fan systems

Definition

Software commonly models fans in three ways. See definition for supply system modeling method.

Units

List: power-per-unit-flow, static pressure or brake horsepower

Input Restrictions

As designed

Baseline Rules

If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method.

 

Exhaust Fan Rated Capacity

Applicability

All exhaust systems

Definition

The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block.

Units

cfm

Input Restrictions

As designed

Baseline Rules

Same as the proposed design. 

 

Fan Control Method

Applicability

All exhaust fan systems

Definition

A description of how the exhaust fan(s) are controlled. The options include:

  • Constant volume
  • Two-speed
  • Variable-flow, inlet or discharge dampers
  • Variable-flow, inlet guide vanes
  • Variable-flow, variable speed drive (VSD)
  • Variable-flow, variable pitch blades

Units

List (see above)

Input Restrictions

As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified.

Baseline Rules

The baseline building exhaust fan control shall generally be the same as the proposed design, with the following exceptions.

  • For laboratories that have exhaust flow of 5,000 cfm or more, the baseline building exhaust flow shall vary in response to scheduled fume hood exhaust and lab zone airflow schedules. Fume hood exhaust flow control shall be the same as design, and general exhaust (relief) shall be VSD.
  • If a kitchen zone design exhaust rate is greater than 5,000 cfm, the baseline building system serving the kitchen shall be system type 5 or 7 with a demand ventilation system on 75% of the exhaust air. The system shall reduce exhaust and replacement air system airflow rates by 50% for one half of the kitchen occupied hours.

 

Exhaust Fan Schedule

Applicability

All exhaust fan systems

Definition

A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level.

Units

Data structure: schedule, on/off

Input Restrictions

The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust.

Baseline Rules

Same as the proposed design

 

Exhaust Fan Brake Horsepower

Applicability

All exhaust fan systems

Definition

The design shaft brake horsepower of the exhaust fan(s).

Units

Brake horsepower (bhp)

Input Restrictions

As designed

Baseline Rules

The bhp for the baseline building is the total system fan horsepower from Table 3.7.3-2 times the exhaust fan ratio.

 

Exhaust Fan Design Static Pressure

Applicability

Any system with return or relief fans that uses the static pressure method

Definition

The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations.

Units

Inches of water column (in. H20)

Input Restrictions

As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified.

Baseline Rules

The exhaust fan static pressure for the baseline building would be equal to the total fan system static pressure (specified in section Supply Fan Static Pressure) multiplied by the exhaust fan ratio.

Exhaust Fan Static Pressure = (Exhaust Fan BHP x 6356 x 0.65)/cfm exhaust

 

Exhaust Fan Efficiency

Applicability

Any exhaust fan system that uses the static pressure method

Definition

The efficiency of the exhaust fan at rated capacity

Units

Unitless

Input Restrictions

For kitchen exhaust fans, the fan efficiency is prescribed at 50%. As designed for other exhaust fan systems. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified.

Baseline Rules

The baseline exhaust fan efficiency is 65%.

 

Exhaust Fan Motor Efficiency

Applicability

All exhaust fan systems

Definition

The full-load efficiency of the motor serving the exhaust fan

Units

Unitless

Input Restrictions

As designed

Baseline Rules

From Table 3.7.3-4.

 

Fan Part-Flow Power Curve

Applicability

All variable flow exhaust fan systems

Definition

A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow.

Units

Unitless ratio

Input Restrictions

As designed. The default fan curve shall be selected from COMNET Appendix H for the type of fan specified in the proposed design.

Baseline Rules

The baseline building fan curve shall be selected from COMNET Appendix H for the type of fan specified in the proposed design.

 

Exhaust Fan Power Index

Applicability

All exhaust systems

Definition

The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method.

Units

W/cfm

Input Restrictions

As designed.

Baseline Rules

The baseline building exhaust fan power index shall be the fan system power from Table 3.7.3-2 multiplied times the exhaust fan ratio.

90.1-2019

Exhaust fans include toilet, kitchen and laboratory exhaust. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal zone. An exhaust fan system may serve multiple thermal zones. The baseline building has exhaust fans when the proposed design has exhaust fans. The design exhaust airflow is the same for the baseline building and the proposed building.

 

Exhaust Fan Name

Applicability

All exhaust systems serving multiple thermal zones

Definition

A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal zone level refer to this name.

Units

Text, unique

Input Restrictions

Where applicable, this should match the tags that are used on the plans

Baseline Building

The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used.

 

Exhaust Fan System Modeling Method

Applicability

All exhaust fan systems

Definition

Software commonly models fans in three ways. See definition for supply system modeling method.

Units

List: Power-Per-Unit-Flow, Static Pressure, or Brake Horsepower

Input Restrictions

As designed

Baseline Building

If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the static pressure method

 

Exhaust Fan Rated Capacity

Applicability

All exhaust systems

Definition

The rated design airflow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual airflow is the sum of the flow specified for each thermal zone, as modified by the schedule for each thermal zone.

Units

cfm

Input Restrictions

As designed

Baseline Building

Same as the proposed design except that baseline building kitchen exhaust rate may not exceed the maximum levels defined by Section 3.6.5.3 of this document

 

Fan Control Method

Applicability

All exhaust fan systems

Definition

A description of how the exhaust fan(s) are controlled. The options include:

  • Constant volume
  • Two-speed
  • Variable-flow, inlet or discharge dampers
  • Variable-flow, inlet guide vanes
  • Variable-flow, VSD
  • Variable-flow, variable pitch blades

Units

List (see above)

Input Restrictions

As designed, however, when exhaust fan flow at the thermal zone level is varied through a schedule, one of the variable-flow options shall be specified

Baseline Building

The baseline building exhaust fan control shall generally be the same as the proposed design. Exceptions: Exhaust fans s serving laboratory spaces shall reduce the exhaust air volume during unoccupied periods to the largest of 50% of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards as described in Section 3.6.5.3 under descriptor Laboratory: Exhaust Minimum Airflow Rate.

 

Exhaust Fan Schedule

Applicability

All exhaust fan systems

Definition

A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal zone level.

Units

Data structure: schedule, on/off

Input Restrictions

As designed

Baseline Building

Same as the proposed design for exhaust fans not serving kitchen or laboratory spaces

For kitchen and laboratory zone exhaust, refer to Section 3.6.5.3 of this document

 

Exhaust Fan Brake Horsepower

Applicability

All exhaust fan systems

Definition

The design shaft brake horsepower of the exhaust fan(s)

Units

Brake horsepower (bhp)

Input Restrictions

As designed

Baseline Building

The bhp for the baseline building is the total system fan horsepower from Table 53 of this document multiplied by the exhaust fan ratio

 

Exhaust Fan Design Static Pressure

Applicability

Any system with return or relief fans that uses the static pressure method

Definition

The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations.

Units

Inches of water column (in. H2O)

Input Restrictions

As designed for exhaust fans not serving kitchens. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan bhp is specified.

Baseline Building

The exhaust fan static pressure for the baseline building would be equal to the total fan system static pressure (specified in section Supply Fan Static Pressure) multiplied by the exhaust fan ratio

Exhaust Fan Static Pressure = (Exhaust Fan BHP x 6356 x 0.65)/cfm exhaust

 

Exhaust Fan Efficiency

Applicability

Any exhaust fan system that uses the static pressure method

Definition

The efficiency of the exhaust fan at rated capacity; this is the static efficiency and does not include losses through the motor

Units

Unitless

Input Restrictions

As designed. The exhaust fan efficiency does not need to be specified if the return fan bhp is specified.

Baseline Building

For baseline system, fan efficiency is 65%

 

Exhaust Fan Motor Efficiency

Applicability

All exhaust fan systems

Definition

The full-load efficiency of the motor serving the exhaust fan

Units

Unitless

Input Restrictions

As designed

Baseline Building

From Table G3.9.1 of Standard 90.1-2019 for the next motor size greater than the bhp calculated, through the process described above, using a totally enclosed fan motor at 1800 rpm

 

Fan Part-Flow Power Curve

Applicability

All variable flow exhaust fan systems

Definition

A part-load power curve that represents the power draw of the exhaust fan as a function of the airflow

Units

Unitless ratio

Input Restrictions

As designed. The default fan curve shall be selected from Equation (10) and Table 57 for the type of fan specified in the proposed design.

Baseline Building

Same as proposed

 

Exhaust Fan Power Index

Applicability

All exhaust systems

Definition

The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method.

Units

kW/cfm

Input Restrictions

As designed

Baseline Building

The fan system power from Table 53 multiplied by the exhaust fan ratio