Baseline building systems 3 through 8 and 11 through 13, shall have a return/relief fan when the proposed design has a return/relief fan fan.
|
Plenum Zone |
|
|---|---|
|
Applicability |
Any system with return ducts or return air plenum |
|
Definition |
A reference to the thermal block that serves as return plenum or where the return ducts are located |
|
Units |
Text, unique |
|
Input Restrictions |
As designed |
|
Baseline Rules |
Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum, otherwise, the return air ducts are assumed to be located in the space. |
|
Return Air Path |
|
|---|---|
|
Applicability |
Any system with return ducts or return air plenum |
|
Definition |
Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Rules |
Applicable when the baseline building has a return fan. For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and 11 through 13, when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be same as proposed design. |
|
Return/Relief Air Rated Capacity |
|
|---|---|
|
Applicability |
All systems with a return or relief fan |
|
Definition |
The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
|
Units |
cfm |
|
Input Restrictions |
As designed |
|
Baseline Rules |
Applicable when the baseline building has a return fan. The return fan air Rated Capacity shall be equal to 90% of the baseline building supply fan capacity or the baseline building supply fan capacity less the minimum outdoor air, whichever is larger. The two special cases apply.
|
|
Return/Relief Fan Brake Horsepower |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the brake horsepower method |
|
Definition |
The design shaft brake horsepower of the return/relief fan(s) |
|
Units |
Brake horsepower (bhp) |
|
Input Restrictions |
As designed |
|
Baseline Rules |
Applicable when the baseline building has a return fan. The bhp of the return fan shall be the fan system brake horsepower (see Table 3.7.3-1) times the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
|
Return/Relief Design Static Pressure |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the static pressure method |
|
Definition |
The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
|
Units |
Inches of water column (in. H20) |
|
Input Restrictions |
As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
|
Baseline Rules |
The baseline Return/Relief Design Static Pressure shall be equal to the return/relief fan brake horsepower divided by the constant 6,356 and an assumed fan efficiency of 65%. |
|
Return/Relief Fan Efficiency |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the static pressure method |
|
Definition |
The efficiency of the fan at design conditions |
|
Units |
Unitless |
|
Input Restrictions |
As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
|
Baseline Rules |
65% |
|
Return/Relief Motor Efficiency |
|
|---|---|
|
Applicability |
All return fans, except those specified using the power-per-unit-flow method |
|
Definition |
The full-load efficiency of the motor serving the supply fan |
|
Units |
Unitless |
|
Input Restrictions |
As designed. Not applicable when the power-per-unit-flow method is used. |
|
Baseline Rules |
For baseline systems 1, 2, 9 and 10, motor efficiency shall be 80%. For other systems, the minimum value from Table 3.7.3-3 shall be used. |
|
Motor Position |
|
|---|---|
|
Applicability |
All return fans |
|
Definition |
The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed. |
|
Baseline Rules |
In the air stream |
|
Fan Part-Flow Power Curve |
|
|---|---|
|
Applicability |
All return fans for variable flow fan systems. |
|
Definition |
A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
|
Units |
Unitless ratio |
|
Input Restrictions |
As designed. The default fan curve shall be selected from COMNET Appendix H for the type of fan specified in the proposed design. |
|
Baseline Rules |
Not applicable for baseline building systems 1-, 9, 10, 12 and 13. The default curve for VSD fans shall be used for baseline building systems 5-8 that have a return/relief fan. The default shall be taken from COMNET Appendix H. |
|
Return/Relief Fan Power Index |
|
|---|---|
|
Applicability |
Any system with a return fan |
|
Definition |
The supply fan power per unit of flow |
|
Units |
kW/cfm |
|
Input Restrictions |
As specified in the manufacturers’ literature |
|
Baseline Rules |
Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined from Table 3.7.3-2. This power is then multiplied by the return fan ratio. |
System design supply airflow rates for the baseline building design shall be based on a supply-air-to room-air temperature difference of 20°F or the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is greater. For systems 3, 4, and 11 through 13, if return or relief fans are specified for systems serving the corresponding zones in the proposed design, the baseline building design shall also be modeled with fans serving the same functions. For systems 5 through 8, if return or relief fans are specified in the proposed building, then the baseline systems serving the corresponding zones will be modeled with a return/relief fan.
|
Plenum Zone |
|
|---|---|
|
Applicability |
Any system with return ducts or return air plenum |
|
Definition |
A reference to the thermal zone that serves as return plenum or where the return ducts are located |
|
Units |
Text, unique |
|
Input Restrictions |
As designed |
|
Baseline Building |
Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum; otherwise, the return air ducts are assumed to be located in the space. |
|
Return Air Path |
|
|---|---|
|
Applicability |
Any system with return ducts or return air plenum |
|
Definition |
Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and 11 through 13 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be the same as proposed design. |
|
Return/Relief Air Rated Capacity |
|
|---|---|
|
Applicability |
All systems with a return or relief fan |
|
Definition |
The design airflow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
|
Units |
cfm |
|
Input Restrictions |
As designed |
|
Baseline Building |
Applicable when the baseline building has a return fan. Return or relief fans shall be sized for the baseline system supply fan air quantity less the minimum outdoor air, or 90% of the supply fan air quantity, whichever is larger. |
|
Return/Relief Fan Brake Horsepower |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the brake horsepower method |
|
Definition |
The design shaft brake horsepower of the return/relief fan(s) |
|
Units |
Brake horsepower (bhp) |
|
Input Restrictions |
As designed |
|
Baseline Building |
Applicable when the baseline building has a return fan. The bhp of the return fan shall be the system fan brake horsepower multiplied by the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
|
Return/Relief Design Static Pressure |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the static pressure method |
|
Definition |
The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
|
Units |
Inches of water column (in. H2O gauge) |
|
Input Restrictions |
As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
|
Baseline Building |
Return fan static pressure = (Return fan BHP x 6356 x 0.65)/cfm return |
|
Return/Relief Fan Efficiency |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the static pressure method |
|
Definition |
The efficiency of the fan at design conditions; this is the static efficiency and does not include the efficiency loss of the motor |
|
Units |
Unitless |
|
Input Restrictions |
As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
|
Baseline Building |
65% |
|
Return/Relief Motor Efficiency |
|
|---|---|
|
Applicability |
All return fans, except those specified using the power-per-unit-flow method |
|
Definition |
The full-load efficiency of the motor serving the supply fan |
|
Units |
Unitless |
|
Input Restrictions |
As designed. Not applicable when the power-per-unit-flow method is used. |
|
Baseline Building |
For baseline systems 1, 2, 9, 10, 12, and 13 is 80%. For baseline systems 3 through 8 and 11, fan motor efficiency is determined from Table G3.9.1 of Standard 90.1-2019 for the next motor size greater than the bhp calculated, through the process described above, using a totally enclosed fan motor at 1800 rpm. |
|
Motor Position |
|
|---|---|
|
Applicability |
All return fans |
|
Definition |
The position of the supply fan motor relative to the cooling air stream. The choices are in the air stream or out of the air stream. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
In the air stream |
|
Fan Part-Flow Power Curve |
|
|---|---|
|
Applicability |
All return fans for variable flow fan systems |
|
Definition |
A part-load power curve that represents the percentage full-load power draw of the return fan as a function of the percentage full-load airflow |
|
Units |
Unitless ratio |
|
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (10) and Table 57 for the type of fan specified in the proposed design. |
|
Baseline Building |
Not applicable for baseline building systems 1 through 4. The curve for “Multi zone VAV with static pressure reset curve” shall be used for baseline building systems 5 through 8 and system 11. |
|
Return/Relief Fan Power Index |
|
|---|---|
|
Applicability |
Any system with a return fan |
|
Definition |
The return fan power per unit of flow |
|
Units |
kW/cfm |
|
Input Restrictions |
As specified in the manufacturers’ literature |
|
Baseline Building |
Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 53. This power is then multiplied by the return fan ratio. |
G3.2 New Construction/Major Alterations
System design supply airflow rates for the baseline building design shall be based on a supply-air-to room-air temperature difference of 20°F or the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is greater. For systems 3, 4, and 11 through 13, if return or relief fans are specified for systems serving the corresponding zones in the proposed design, the baseline building design shall also be modeled with fans serving the same functions. For systems 5 through 8, if return or relief fans are specified in the proposed building, then the baseline systems serving the corresponding zones will be modeled with a return/relief fan.
G3.3 Minor Alterations
System design supply airflow rates for the baseline building design shall be based on the design sizing supply-air-to room-air temperature difference (or 20°F if this is unknown) or the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is greater.
HVAC system type is modeled the same in the baseline and proposed with the exception that if the proposed design includes variable refrigerant flow heat pumps or single-zone systems with electric resistance heat, then air source heat pumps shall be used in the baseline design. This means that all fans specified in the proposed design (return, relief, exhaust, supply fans) should also be modeled in the baseline design. This exception is intended for single zone systems with electric resistance coils and not single zone systems served by central hot water systems.
|
Plenum Zone |
|
|---|---|
|
Applicability |
Any system with return ducts or return air plenum |
|
Definition |
A reference to the thermal zone that serves as return plenum or where the return ducts are located |
|
Units |
Text, unique |
|
Input Restrictions |
As designed |
|
Baseline Building |
Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum; otherwise, the return air ducts are assumed to be located in the space. |
|
Return Air Path |
|
|---|---|
|
Applicability |
Any system with return ducts or return air plenum |
|
Definition |
Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and 11 through 13 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be the same as proposed design. G3.3 Minor Alterations Same as the proposed design. |
|
Return/Relief Air Rated Capacity |
|
|---|---|
|
Applicability |
All systems with a return or relief fan |
|
Definition |
The design airflow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
|
Units |
cfm |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations Applicable when the baseline building has a return fan. Return or relief fans shall be sized for the baseline system supply fan air quantity less the minimum outdoor air, or 90% of the supply fan air quantity, whichever is larger. G3.3 Minor Alterations The return/relief air capacities for the baseline design shall be sized proportionally to the capacities in the proposed design based on sizing runs—i.e., the ratio between the capacities used in the annual simulations and the capacities determined by the sizing runs shall be the same for both the proposed design and baseline building design. |
|
Return/Relief Fan Brake Horsepower |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the brake horsepower method |
|
Definition |
The design shaft brake horsepower of the return/relief fan(s) |
|
Units |
Brake horsepower (bhp) |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations Applicable when the baseline building has a return fan. The bhp of the return fan shall be the system fan brake horsepower multiplied by the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. G3.3 Minor Alterations 90.1 G3.3.2.8 (d) requires that for fan systems included in the scope of the retrofit using the BHP method of modeling proposed fan power, BHP should be the same as the proposed design up to the limit prescribed in Section 6.5.3.1, whichever is smaller. Exception to 90.1 G3.3.2.8 (d): When a proposed design includes energy recovery, and all the following conditions are met,
then the fan power of the baseline system shall be equal to either the proposed design system or the fan power limit in Section 6.5.3.1 calculated without fan power credit for energy recovery, whichever is less.
Fans not included in the scope of the alteration should be modeled the same in the baseline and proposed. |
|
Return/Relief Design Static Pressure |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the static pressure method |
|
Definition |
The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
|
Units |
Inches of water column (in. H2O gauge) |
|
Input Restrictions |
As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
|
Baseline Building |
G3.2 New Construction/Major Alterations Return fan static pressure = (Return fan BHP x 6356 x 0.65)/cfm return G3.3 Minor Alterations 90.1 G3.3.2.8 (d) requires that for fan systems included in the scope of the retrofit using the using the pressure drop method of modeling proposed fan power, the pressure drop should be the same as the proposed design up to the limit that corresponds to fan power allowances prescribed in Section 6.5.3.1, whichever is smaller. Exception to 90.1 G3.3.2.8 (d): When a proposed design includes energy recovery, and all the following conditions are met,
then the fan power of the baseline system shall be equal to either the proposed design system or the fan power limit in Section 6.5.3.1 calculated without fan power credit for energy recovery, whichever is less. Fans not included in the scope of the alteration should be modeled the same in the baseline and proposed. |
|
Return/Relief Fan Efficiency |
|
|---|---|
|
Applicability |
Any system with return or relief fans that uses the static pressure method |
|
Definition |
The efficiency of the fan at design conditions; this is the static efficiency and does not include the efficiency loss of the motor |
|
Units |
Unitless |
|
Input Restrictions |
As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
|
Baseline Building |
G3.2 New Construction/Major Alterations 65% G3.3 Minor Alterations If using the pressure drop method of modeling proposed fan power, same as the proposed design. If unknown, a default of 65% can be used. |
|
Return/Relief Motor Efficiency |
|
|---|---|
|
Applicability |
All return fans, except those specified using the power-per-unit-flow method |
|
Definition |
The full-load efficiency of the motor serving the supply fan |
|
Units |
Unitless |
|
Input Restrictions |
As designed. Not applicable when the power-per-unit-flow method is used. |
|
Baseline Building |
G3.2 New Construction/Major Alterations For baseline systems 1, 2, 9, 10, 12, and 13 is 80%. For baseline systems 3 through 8 and 11, fan motor efficiency is determined from Table G3.9.1 of Standard 90.1-2022 for the next motor size greater than the bhp calculated, through the process described above, using a totally enclosed fan motor at 1800 rpm. G3.3 Minor Alterations For fan systems included in the scope of the retrofit, motor efficiency should be modeled with the minimum efficiency requirement of Standard 90.1-2022 Section 10.4.1 as applicable. Fractional horsepower fan motors (motors 1/12 hp or greater and less than 1 hp) shall be modeled with a motor efficiency of 70%. If any of the exceptions apply, then it shall be modeled the same in the baseline and proposed. Fans not included in the scope of the alteration should be modeled the same in the baseline and proposed. |
|
Motor Position |
|
|---|---|
|
Applicability |
All return fans |
|
Definition |
The position of the supply fan motor relative to the cooling air stream. The choices are in the air stream or out of the air stream. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations In the air stream G3.3 Minor Alterations Same as the proposed design. |
|
Fan Part-Flow Power Curve |
|
|---|---|
|
Applicability |
All return fans for variable flow fan systems |
|
Definition |
A part-load power curve that represents the percentage full-load power draw of the return fan as a function of the percentage full-load airflow |
|
Units |
Unitless ratio |
|
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (11) and Table 61 for the type of fan specified in the proposed design. |
|
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable for baseline building systems 1 through 4. The curve for “Multi zone VAV with fixed static pressure setpoint” shall be used for baseline building systems 5 through 8. System 11 shall use the “Single zone VAV fan” curve. G3.3 Minor Alterations The baseline shall be modeled using the “Multi zone VAV with static pressure reset(c)” curve. Exception: the fan part load curve should be modeled the same in the baseline and proposed if, based on the requirements of 90.1-2022 Section 6.1.4 and the scope of the alteration, 90.1-2022 Section 6.5.3.2.3 requirements are inapplicable. |
|
Return/Relief Fan Power Index |
|
|---|---|
|
Applicability |
Any system with a return fan |
|
Definition |
The return fan power per unit of flow |
|
Units |
kW/cfm |
|
Input Restrictions |
As specified in the manufacturers’ literature |
|
Baseline Building |
G3.2 New Construction/Major Alterations Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 57. This power is then multiplied by the return fan ratio. G3.3 Minor Alterations 90.1 G3.3.2.8 (d) requires that for fan systems included in the scope of the retrofit using the power-per-unit-flow method of modeling proposed fan power, the kW/CFM should be the same as the proposed design up to the limit that corresponds to fan power allowances prescribed in Section 6.5.3.1, whichever is smaller. Exception to 90.1 G3.3.2.8 (d): When a proposed design includes energy recovery, and all the following conditions are met,
then the fan power of the baseline system shall be equal to either the proposed design system or the fan power limit in Section 6.5.3.1 calculated without fan power credit for energy recovery, whichever is less.
Fans not included in the scope of the alteration should be modeled the same in the baseline and proposed. |