Economizer Control Type |
|
---|---|
Applicability |
All systems with an air-side economizer |
Definition |
An air-side economizer increases outside air ventilation during periods when cooling loads can be reduced from increased outside airflow. The control types include:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
Outdoor air economizers shall not be included in baseline HVAC systems 1, 2, 9, and 10. Outside air economizers shall be included in baseline HVAC systems 3 through 8, 11, 12, and 13, in climate zones 2B, 3B, 3C, 4C, 5B, 5C, 6B, 7, and 8. Economizers are not required in other climate zones. Economizer control shall be fixed dry bulb with a temperature setpoint as indicated under Economizer High-Temperature Lockout below. Exceptions: Economizers shall not be included for systems meeting one or more of the exceptions listed below. a. Systems that include gas-phase air cleaning to meet the requirements of Section 6.1.2 in Standard 62.1. In the scenario, where there isn’t a one-to-one mapping between the systems in the proposed and baseline building, all systems serving the zones that qualify for the exception in the proposed building will not have economizers. b. Where the use of outdoor air for cooling will affect supermarket open refrigerated casework systems. This exception shall only be used if the system in the proposed design does not use an economizer. c. Systems serving computer rooms which are baseline systems 3-4 shall not have an economizer. Systems that server computer rooms that are baseline system 11 shall include an integrated fluid economizer meeting the requirements of Standard 90.1-2019 Section 6.5.1.2, also summarized below and in Section 3.8.4 of this manual. Fluid Economizers Fluid economizer systems shall be capable of providing up to 100% of the expected system cooling load at outdoor air temperatures of 50°F dry bulb/45°F wet bulb and below. Exceptions:
|
Economizer Integration |
|
---|---|
Applicability |
Airside economizers |
Definition |
This input specifies whether or not the economizer is integrated with mechanical cooling. It is up to the modeling software to translate this into software-specific inputs to model this feature. The input could take the following values:
|
Units |
List: Non-integrated, Integrated |
Input Restrictions |
As designed |
Baseline Building |
Integrated |
Economizer High-Temperature Lockout |
|
---|---|
Applicability |
Systems with fixed dry-bulb economizer |
Definition |
The outside air setpoint temperature above which the economizer will return to minimum position |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Building |
Economizer control shall be fixed dry bulb with a temperature setpoint of 70°F in climate zones 5A and 6A and 75°F in all other climate zones where economizers are required |
Economizer Low-Temperature Lockout |
|
---|---|
Applicability |
Systems with air-side economizers |
Definition |
A feature that permits the lockout of economizer operation (return to minimum outside air position) when the outside air temperature is below the lockout setpoint |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Building |
None |
Economizer High Enthalpy Lockout |
|
---|---|
Applicability |
Systems with fixed enthalpy or differential enthalpy economizers |
Definition |
The outside air enthalpy above which the economizer will return to minimum position |
Units |
Btu/lb |
Input Restrictions |
As designed. The default is 28 Btu/lb. (High altitude locations may require different setpoints.) The software shall apply a fixed offset and add 2 Btu/lb to the user-entered value. |
Baseline Building |
Not applicable since no baseline building system has an enthalpy economizer |