Baseline Building Summary. Hot water pumping in the baseline building (systems 1, 5, and 7) shall be modeled as a variable flow primary only system. When the spaces served by the hot water system are greater than or equal to 120,000 ft², the pump shall have a variable speed drive, otherwise, the pump “rides the curve”. Pumping energy shall be assumed to be 19 W/gpm. Two-way valves are assumed at the heating coils with a modulating bypass valve at the end of the loop. The bypass valve shall open as necessary to maintain minimum flow through the boiler when the system is activated. This will establish the minimum flow through the system.
Chilled water pumping in the baseline building (systems 7 and 8) is a primary/secondary system. Each chiller has its own primary and condenser water pumps that operate when the chiller is activated. All primary and secondary pumps shall be assumed to be 22 W/gpm and the condenser water pump is assumed to be 19 W/gpm. For plants less than or equal to 300 tons, the secondary pump “rides the curve” for larger plants, the pump has a variable speed drive.
General Notes. The building descriptors in this section are repeated for each pumping system. See the Pump Service building descriptor for a list of common pump services.
Pump Name | |
Applicability | All pumps |
---|---|
Definition | A unique descriptor for each pump |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | Same as the proposed design. If there is no equivalent in the proposed design, assign a sequential tag to each piece of equipment. The sequential tags should indicate the pump service as part of the descriptor (e.g. CW for condenser water, CHW for chilled water, or HHW for heating hot water). |
Pump Service | |
Applicability | All pumps |
---|---|
Definition | The service for each pump. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | As needed by the baseline building system |
Number of Pumps | |
Applicability | All pumps |
---|---|
Definition | The number of identical pumps in service in a particular loop, e.g. the heating hot water loop, chilled water loop, or condenser water loop |
Units | Numeric: integer |
Input Restrictions | As designed |
Baseline Rules | There will be one heating hot water pump for each boiler, one chilled water pump, and one condenser water pump for each chiller. |
Water Loop Design | |
Applicability | All pumps |
---|---|
Definition | The heating and cooling delivery systems can consist of a simple primary loop system, or more complicated primary/secondary loops or primary/secondary/tertiary loops. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Assume primary loops only for heating hot water. For chilled water loops, a primary-secondary loop design is assumed. |
Pump Motor Modeling Method | |
Applicability | All pumps |
---|---|
Definition | Software commonly models fans in one of two ways: The simple method is for the user to enter the electric power per unit of flow (W/gpm). This method is commonly used for smaller systems. A more detailed method requires a specification of the pumping head, impeller efficiency, motor efficiency, and other inputs. |
Units | List: Power-Per-Unit-Flow or Detailed |
Input Restrictions | Either method may be used, as appropriate. |
Baseline Rules | Power-Per-Unit-Flow |
Pump Motor Power-Per-Unit-Flow | |
Applicability | All baseline building pumps and proposed design pumps that use the Power-Per-Unit-Flow method. |
---|---|
Definition | The electric power of the pump divided by the flow at design conditions. |
Units | W/gpm |
Input Restrictions | As designed |
Baseline Rules | Prescribed to be 19 W/gpm for condenser and heating hot water pumps and 22 W/gpm for primary and secondary chilled water pumps. |
Impeller Efficiency | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The full load efficiency of the impeller |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Motor Efficiency | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The full load efficiency of the pump motor |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Pump Design Head | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The design pressure for the pump |
Units | Feet of water (or feet of head) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Pump Minimum Speed | |
Applicability | All two-speed or variable-speed pumps |
---|---|
Definition | The minimum pump speed for a two-speed for variable-speed pump. For two-speed pumps this is typically 0.67 or 0.5. Note that the pump minimum speed is not necessarily the same as the minimum flow ratio, since the system head may change. |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | The secondary chilled water pumps for baseline building systems 7 and 8 have variable speed drives when the size of the cooling plant is greater than 300 tons. In these cases the Pump Minimum Speed shall be 0.10. |
Pump Design Flow (GPM) | |
Applicability | All pumps |
---|---|
Definition | The flow rate of the pump at design conditions. This is derived from the load, and the design supply and return temperatures. |
Units | gpm or gpm/ton for condenser and primary chilled water pumps |
Input Restrictions | Not a user input |
Baseline Rules | The temperature change on the evaporator side of the chillers is 12 F (56 F less 44 F) and this equates to a flow of 2 gpm/ton. The temperature change on the condenser side of the chillers is 10 F, which equates to a flow of 2.5 gpm/ton. The flow for secondary chilled water pumps varies with cooling demand, since there are two-way valves at the coils. The flow for primary only heating varies with demand down to the minimum required for flow through the boiler. A VSD is required for heating pumps when the service area is greater than or equal to 120,000 ft². |
Pump Control Type | |
Applicability | All pumps |
---|---|
Definition | The type of control for the pump. Choices are:
|
Units | None |
Input Restrictions | As designed. The default is “Fixed Speed, Variable Flow” which models the action of a constant speed pump riding the curve against 2-way control valves. |
Baseline Rules | The hot water and condenser water loops shall be primary loops only. When the hot water system serves less than 120,000 ft², the hot water pump shall be modeled as a fixed speed, variable flow pump (riding the pump curve). When the hot water system serves more than 120,000 ft², the hot water pump shall be modeled as a variable speed pump on a primary loop. The chilled water pumping for systems 7 and 8 is primary/secondary with variable flow. When the chilled water system has a capacity of less than 300 tons, the secondary system pumps shall ride the pump curve. When the chilled water system has a capacity of more than 300 tons, the secondary chilled water pumps shall be variable speed. Chilled water pumps used in the primary loop shall be fixed speed, fixed flow. Condenser water pumps shall be modeled as fixed speed, fixed flow. |
Pump Operation | |
Applicability | All pumps |
---|---|
Definition | The type of pump operation can be either On-Demand, Standby or Scheduled. On-Demand operation means the pumps are only pumping when their associated equipment is cycling, so chiller and condenser pumps are on when the chiller is on and the heating hot water pump operates when its associated boiler is cycling. Standby operation allows hot or chilled water to circulate through the primary loop of a primary/secondary loop system or through a reduced portion of a primary-only system, assuming the system has appropriate 3-way valves. Scheduled operation means that the pumps and their associated equipment are turned completely off according to occupancy schedules, time of year, or outside conditions. Under scheduled operation, when the systems are on they are assumed to be in On-Demand mode. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | The baseline system pumps are assumed to operate in On-Demand mode. The chilled water and condenser pumps are tied to the chiller operation, cycling on and off with the chiller, and the heating hot water pumps are tied to the boiler operation. |
Pump Part Load Curve | |||||||||||||||||
Applicability | All pumps | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A part-load power curve for the pump (6.8.5-1) $$ C\!I\!RC - PU\!M\!P - F\!P\!LR = a + b \times PLR + c \times PLR^2 + d \times PLR^3$$ (6.8.5-2) $$ P_{pump} = P_{design} \times C\!I\!RC - PU\!M\!P - F\!P\!L\!R $$where
[table title="Default Part-Load CIRC-PUMP-FPLR Coefficients – VSD on Circulation Pump" id="default-part-load-CIRC-PUMP-FPLR-Coefficients-–-VSD-on-Circulation-Pump"]
|
||||||||||||||||
Units | Data structure | ||||||||||||||||
Input Restrictions | As designed. Default is curve above. | ||||||||||||||||
Baseline Rules | Use the defaults described above. |
Baseline Building Summary
Hot Water Pumping
Hot water pumping in the baseline building (systems 1, 5, 7, and 12) shall be modeled as a variable flow primary only system. When the spaces served by the hot water system are greater than or equal to 120,000 ft², the pump shall have a variable speed drive, otherwise, the pump “rides the curve”. Pumping energy shall be assumed to be 19 W/gpm. Two-way valves are assumed at the heating coils with a modulating bypass valve at the end of the loop. The bypass valve shall open as necessary to maintain minimum flow through the boiler when the system is activated. This will establish the minimum flow through the system.
Chilled-water systems shall be modeled as primary/secondary systems with constant flow primary loop and variable flow secondary loop.
- For systems with cooling capacity of 300 tons or more, the secondary pump shall be modeled with variable speed drives and a minimum flow of 25% of the design flow rate.
- For systems with less than 300 tons cooling capacity, the secondary pump shall be modeled as riding the pump curve.
Chilled Water Pumping
Chilled-water systems shall be modeled as primary/secondary systems with constant flow primary loop and variable flow secondary loop.
- For systems with cooling capacity of 300 tons or more, the secondary pump shall be modeled with variable speed drives and a minimum flow of 25% of the design flow rate.
- For systems with less than 300 tons cooling capacity, the secondary pump shall be modeled as riding the pump curve.
The baseline building constant-volume primary pump power shall be modeled as 9 W/gpm, and the variable-flow secondary pump power shall be modeled as 13 W/gpm at design conditions. For computer room systems using System 11 with an integrated water-side economizer, the baseline building design primary chilled-water pump power shall be increased by 3 W/gpm for flow associated with the water-side economizer. For systems using purchased chilled water, the building distribution pump shall be modeled with variable-speed drive, a minimum flow of 25% of the design flow rate, and a pump power of 16 W/gpm.
General Notes. The building descriptors in this section are repeated for each pumping system. See the Pump Service building descriptor for a list of common pump services.
Pump Name |
|
---|---|
Applicability |
All pumps |
Definition |
A unique descriptor for each pump |
Units |
Text, unique |
Input Restrictions |
User entry. Where applicable, this should match the tags that are used on the plans. |
Baseline Rules |
Same as the proposed design. If there is no equivalent in the proposed design, assign a sequential tag to each piece of equipment. The sequential tags should indicate the pump service as part of the descriptor (e.g. CW for condenser water, CHW for chilled water, or HHW for heating hot water). |
Pump Service |
|
---|---|
Applicability |
All pumps |
Definition |
The service for each pump. Choices include:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
As needed by the baseline building system |
Number of Pumps |
|
---|---|
Applicability |
All pumps |
Definition |
The number of identical pumps in service in a particular loop, e.g. the heating hot water loop, chilled water loop, or condenser water loop |
Units |
Numeric: integer |
Input Restrictions |
As designed |
Baseline Rules |
The number of pumps will be defined as specified below:
|
Water Loop Design |
|
---|---|
Applicability |
All pumps |
Definition |
The heating and cooling delivery systems can consist of a simple primary loop system, or more complicated primary/secondary loops or primary/secondary/tertiary loops. |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
Heating water systems shall be modeled with primary loops only. Chilled water systems shall be modeled with primary/secondary loops. |
Pump Motor Modeling Method |
|
---|---|
Applicability |
All pumps |
Definition |
Software commonly models pumps in one of two ways: The simple method is for the user to enter the electric power per unit of flow (W/gpm). This method is commonly used for smaller systems. A more detailed method requires a specification of the pumping head, impeller efficiency, motor efficiency, and other inputs. |
Units |
List: Power-Per-Unit-Flow or Detailed |
Input Restrictions |
Either method may be used, as appropriate. |
Baseline Rules |
Detailed |
Pump Motor Power-Per-Unit-Flow |
|
---|---|
Applicability |
All baseline building pumps and proposed design pumps that use the Power-Per-Unit-Flow method. |
Definition |
The electric power of the pump divided by the flow at design conditions. |
Units |
W/gpm |
Input Restrictions |
As designed |
Baseline Rules |
Not applicable |
Pump Motor Horspower |
|
---|---|
Applicability |
All pumps that use the detailed modeling method |
Definition |
The nameplate motor horspower |
Units |
Horsepower |
Input Restrictions |
Constrained to be a value from the following list of standard motor sizes: A standard motor size table (hp) is defined as: 1/12, 1/8, ¼, ½, ¾, 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200 |
Baseline Rules |
Not applicable |
Pump Design Head |
|
---|---|
Applicability |
All baseline building pumps and proposed design pumps that use the detailed modeling method |
Definition |
The head of the pump at design flow conditions |
Units |
ft or wg |
Input Restrictions |
As designed |
Baseline Rules |
For the baseline building:
|
Impeller Efficiency |
|
---|---|
Applicability |
All pumps in baseline building and proposed design that use the detailed modeling method |
Definition |
The full load efficiency of the impeller |
Units |
Ratio between 0 and 1.0 |
Input Restrictions |
As designed |
Baseline Rules |
For the baseline building:
|
Motor Efficiency |
|
---|---|
Applicability |
All pumps in baseline building and proposed design that use the detailed modeling method |
Definition |
The full load efficiency of the pump motor |
Units |
Ratio between 0 and 1.0 |
Input Restrictions |
As designed |
Baseline Rules |
For the baseline building
|
Pump Minimum Speed |
|
---|---|
Applicability |
All two-speed or variable-speed pumps |
Definition |
The minimum pump speed for a two-speed for variable-speed pump. For two-speed pumps this is typically 0.67 or 0.5. Note that the pump minimum speed is not necessarily the same as the minimum flow ratio, since the system head may change. (Equation 3.8.5-1) $$Pump \ Speed_{Min} = Pump \ Speed_{Design} \times \sqrt{\frac{Head_{Min}}{Head_{Design}}}$$ |
Units |
Ratio between 0 and 1.0 |
Input Restrictions |
As designed |
Baseline Rules |
When the baseline pumps are required to have variable speed drives in accordance with descriptor Pump Control Type, the pump minimum speed shall be 0.10. |
Pump Design Flow (GPM) |
|
---|---|
Applicability |
All pumps |
Definition |
The flow rate of the pump at design conditions. For the baseline, this is derived from the heating and cooling loads, the appropriate oversizing factors, and the design supply and return temperatures. |
Units |
gpm or gpm/ton for condenser and primary chilled water pumps |
Input Restrictions |
Not a user input |
Baseline Rules |
The temperature change on the evaporator side of the chillers is 12°F (56°F less 44°F) and this equates to a flow of 2 gpm/ton. The temperature change on the condenser side of the chillers is 10 °F, which equates to a flow of 2.4 gpm/ton. The flow for secondary chilled water pumps varies with cooling demand, since there are two-way valves at the coils. The flow for primary only heating varies with demand down to the minimum required for flow through the boiler. A VSD is required for heating pumps when the service area is greater than or equal to 120,000 ft². For hot water pumps servicing boilers, the flow rate in gpm shall be the boiler capacity in Btu/h / 25,000, which corresponds to a loop temperature drop of 50°F. |
Pump Control Type |
|
---|---|
Applicability |
All pumps |
Definition |
The type of control for the pump. Choices are:
|
Units |
None |
Input Restrictions |
As designed. The default is “Fixed Speed, Variable Flow” which models the action of a constant speed pump riding the curve against two-way control valves. |
Baseline Rules |
The following rules shall apply:
|
Pump Operation |
|
---|---|
Applicability |
All pumps |
Definition |
The type of pump operation can be either On-Demand, Standby or Scheduled. On-Demand operation means the pumps are only pumping when their associated equipment is cycling, so chiller and condenser pumps are on when the chiller is on and the heating hot water pump operates when its associated boiler is cycling. Standby operation allows hot or chilled water to circulate through the primary loop of a primary/secondary loop system or through a reduced portion of a primary-only system, assuming the system has appropriate 3-way valves. Scheduled operation means that the pumps and their associated equipment are turned completely off according to occupancy schedules, time of year, or outside conditions. Under scheduled operation, when the systems are on they are assumed to be in On-Demand mode. |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
The baseline system pumps are assumed to operate in on-demand mode. The chilled water and condenser pumps are tied to the chiller operation, cycling on and off with the chiller, and the heating hot water pumps are tied to the boiler operation. |
Hot water pumping in the baseline building (systems 1, 5, 7, 11, and 12) shall be modeled as a primary only system with continuous variable flow, and a minimum of 25% of design flow rate of the baseline building. When the spaces served by the hot water system are greater than or equal to 120,000 ft², the pump shall have a variable speed drive; otherwise, the pump “rides the curve.” Pumping energy shall be assumed to be 19 W/gpm. Two-way valves are assumed at the heating coils with a modulating bypass valve at the end of the loop. The bypass valve shall open as necessary to maintain minimum flow through the boiler when the system is activated. This will establish the minimum flow through the system.
District hot water systems shall follow the same rules as hot water pumps, except for pump energy, which shall be equal to 14 W/gpm.
Chilled water pumping in the baseline building (systems 7, 8, 11, 12, and 13) is a primary/secondary system with constant flow primary loop and variable flow secondary loop. The minimum flow of the secondary loop is 25% of the design flow rate. Each chiller has its own primary and condenser water pumps that operate when the chiller is activated. All primary pumps shall be 9 W/gpm and secondary pump shall be 13 W/gpm, and the condenser water pump is assumed to be 19 W/gpm. For plants less than or equal to 300 tons, the secondary pump “rides the curve,” for larger plants, the pump has a variable speed drive. The primary chilled water pump is constant speed and the condenser water pump is fixed speed. District chilled water system pumps shall follow the same rules as secondary chilled water pumps and pump energy shall be assumed to be 16 W/gpm. For computer room systems using system 11 with an integrated fluid economizer, the baseline building design both primary chilled water pump and condenser water pump power shall be increased by 3 W/gpm for flow associated with the fluid economizer.
The building descriptors in this section are repeated for each pumping system. See the Pump Service building descriptor for a list of common pump services.
Pump Name | |
---|---|
Applicability | All pumps |
Definition | A unique descriptor for each pump |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Baseline Building | Same as the proposed design. If there is no equivalent in the proposed design, assign a sequential tag to each piece of equipment. The sequential tags should indicate the pump service as part of the descriptor (e.g., CW for condenser water, CHW for chilled water, or HHW for heating hot water). |
Pump Service | |
---|---|
Applicability | All pumps |
Definition |
The service for each pump. Choices include: · Chilled water · Chilled water (primary) · Chilled water (secondary) · Heating water · Heating water (primary) · Heating water (secondary) · Service hot water · Condenser water · Loop water (for hydronic heat pumps) |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Building | As needed by the baseline building system |
Number of Pumps | |
---|---|
Applicability | All pumps |
Definition |
The number of identical pumps in service in a particular loop, e.g., the heating hot water loop, chilled water loop, or condenser water loop |
Units | Numeric: integer |
Input Restrictions | As designed |
Baseline Building |
The number of pumps will be defined as specified below: One heating hot water pump for each boiler · One primary chilled water pump for each chiller and one secondary chilled water pump for the chilled water loop · One condenser water pump for each chiller · One district hot water pump for each building served by a district hot water system · One district chilled water pump for each building served by a district chilled water system |
Water Loop Design | |
---|---|
Applicability | All pumps |
Definition |
The heating and cooling delivery systems can consist of a simple primary loop system, or more complicated primary/secondary loops or primary/secondary/tertiary loops |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Building |
Heating water systems shall be modeled with primary loops only. Chilled water systems shall be modeled with primary/secondary loops. |
Pump Motor Modeling Method | |
---|---|
Applicability | All pumps |
Definition |
Software commonly models pumps in one of two ways: The simple method is for the user to enter the electric power per unit of flow (W/gpm). This method is commonly used for smaller systems. A more detailed method requires a specification of the pump head, design flow, impeller, and motor efficiency. |
Units | List: Power-Per-Unit-Flow or Detailed |
Input Restrictions | Either method may be used, as appropriate |
Baseline Building |
Detailed modeling method will be used for the baseline building. |
Pump Motor Power-Per-Unit-Flow | |
---|---|
Applicability | All proposed design pumps that use the power-per-unit-flow method |
Definition |
The electric power of the pump divided by the flow at design conditions |
Units | W/gpm |
Input Restrictions | As designed |
Baseline Building |
Detailed modeling method will be used for the baseline building. |
Pump Motor Horsepower | |
---|---|
Applicability | All pumps |
Definition |
The nameplate motor horsepower |
Units | horsepower |
Input Restrictions |
Constrained to be a value from the following list of standard motor sizes: A standard motor size table (hp) is defined as: 1/12, 1/8, 1/4, 1/2, 3/4, 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200 |
Baseline Building |
Not applicable |
Pump Design Head | |
---|---|
Applicability | All baseline building pumps and proposed design pumps that use the detailed modeling method |
Definition |
The head of the pump at design flow conditions |
Units | ft or wg |
Input Restrictions |
As designed |
Baseline Building |
For the baseline building: · District chilled water Pressure drop is 55 ft head · District hot water Pressure drop is 44 ft head · Chilled water system Pressure drop is 31 ft of head for the primary loop and 45 ft of head for the secondary loop For pumps serving baseline system 11, pressure drop is 41 ft of head for the primary loop and 45 feet of head for the secondary loop. · Condenser water system Pressure drop is 60 ft of head For pumps serving baseline system 11, pressure drop is 70 ft of head. · Hot water system Pressure drop is 60 ft of head |
Impeller Efficiency | |
---|---|
Applicability | All pumps in proposed design that use the detailed modeling method |
Definition |
The full load efficiency of the impeller |
Units | Ratio (between 0 and 1) |
Input Restrictions | As designed |
Baseline Building |
For the baseline building: · District chilled water system Impeller efficiency = 72% (assuming motor efficiency of 90% and a total pump efficiency of 65%) · District hot water system Impeller efficiency = 66.67% (assuming motor efficiency of 90% and a total pump efficiency of 60%) · Chilled water system Impeller efficiency = 72% (assuming motor efficiency of 90% and total pump efficiency of 65%) · Condenser water system Impeller efficiency = 66.67% (assuming motor efficiency of 90% and total pump efficiency of 60%) · Hot water system Impeller efficiency = 66.67% (assuming motor efficiency of 90% and total pump efficiency of 60%) |
Motor Efficiency | |
---|---|
Applicability | All pumps in proposed design that use the detailed modeling method |
Definition |
The full load efficiency of the pump motor |
Units | Ratio (between 0 and 1) |
Input Restrictions | As designed |
Baseline Building |
For the baseline building · District chilled water system Motor efficiency = 90% · District hot water system Motor efficiency = 90% · Chilled water system Motor efficiency = 90% · Condenser water system Motor efficiency = 90% · Hot water system Motor efficiency = 90% |
Pump Minimum Speed | |
---|---|
Applicability | All two-speed or variable-speed pumps |
Definition |
The minimum pump speed for a two-speed or variable-speed pump. A fraction of the pump design head. For two-speed pumps this is typically 0.67 or 0.5. Note that the pump minimum speed is not necessarily the same as the minimum flow ratio, since the system head may change. Pump Speed min = Pump Speed design * √(Head min / Head design) |
Units | Ratio (between 0 and 1) |
Input Restrictions | As designed |
Baseline Building | When the baseline pumps are required to have variable speed drives in accordance with descriptor Pump Control Type, the pump minimum speed shall be 0.10 |
Pump Design Flow (gpm) | |
---|---|
Applicability | All pumps |
Definition |
The flow rate of the pump at design conditions. For the baseline, this is derived from the heating and cooling loads, the appropriate oversizing factors, and the design supply and return temperatures. |
Units | gpm or gpm/ton for condenser and primary chilled water pumps |
Input Restrictions | Not a user input |
Baseline Building |
The temperature change on the evaporator side of the chillers is 12°F (56°F less 44°F) and this equates to a flow of 2 gpm/ton. The temperature change on the condenser side of the chillers is 10°F, which equates to a flow of 2.4 gpm/ cooling ton. The flow for secondary chilled water varies with cooling demand, since there are two-way valves at the coils. The flow for primary only heating varies with demand down to the minimum required for flow through the boiler. For hot water pumps servicing boilers, the flow rate in gpm shall be the boiler capacity in Btu/h / 25,000, which corresponds to a loop temperature drop of 50°F. |
Pump Control Type | |
---|---|
Applicability | All pumps |
Definition |
The type of control for the pump. Choices are: · Fixed speed, fixed flow · Fixed speed, variable flow (the default, with flow control via a valve) · Two-speed · Variable speed, variable flow |
Units | None |
Input Restrictions | As designed. The default is “Fixed Speed, Variable Flow,” which models the action of a constant speed pump riding the curve against two-way control valves. |
Baseline Building |
Hot water loops are primary loops only. · For systems serving less than 120,000 ft2, the HW pump is modeled as variable flow with a constant speed pump riding the pump curve. For systems serving more than 120,000 ft2, the HW pump is modeled as a variable flow with a variable speed pump controlled with a variable speed drive. Condenser water pumps: · Condenser water loops are primary only. CW pumps are required to be modeled as fixed speed and fixed flow. Chilled water pumps: · The CHW pumping for systems 7, 8, 11, 12, and 13 are primary/secondary with variable flow. The chilled water pumps used for the primary loop are fixed speed and fixed flow. For systems with a capacity of less than 300 tons, the secondary system pumps shall ride the pump curve. For systems with a capacity greater than 300 tons, the secondary pumps will be modeled as variable speed. District chilled water pump shall follow the same rules for secondary chilled water pumps.
|
Pump Operation | |
---|---|
Applicability | All pumps |
Definition |
The type of pump operation can be either on-demand, standby, or scheduled. On-demand operation means the pumps are only pumping when their associated equipment is cycling, so chiller and condenser pumps are on when the chiller is on and the heating hot water pump operates when its associated boiler is cycling. Standby operation allows hot or chilled water to circulate through the primary loop of a primary/secondary loop system or through a reduced portion of a primary-only system, assuming the system has appropriate three-way valves. Scheduled operation means that the pumps and their associated equipment are turned completely off according to occupancy schedules, time of year, or outside conditions. Under scheduled operation, when the systems are on they are assumed to be in On-Demand mode. |
Units | List: On Demand, Standby, Scheduled |
Input Restrictions | As designed |
Baseline Building |
The baseline system pumps are assumed to operate in on-demand mode. The chilled water and condenser pumps are tied to the chiller operation, cycling on and off with the chiller, and the heating hot water pumps are tied to the boiler operation. |
Pump Part Load Curve | |||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All pumps | ||||||||||||||||||||||||
Definition |
A part-load power curve for the pump: Where: PLR= Part load ratio (the ratio of operating flow rate in gpm to design flow rate in gpm) P pump= Pump power draw at part-load conditions (W) P design= Pump power draw at design conditions (W) Table 94. Default Part-Load CIRC-PUMP-FPLR Coefficients
|
||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||
Input Restrictions | As designed. Default is curve above. | ||||||||||||||||||||||||
Baseline Building |
Use the defaults described above based on pump type. The curve with differential pressure reset isn’t used for the baseline building. |
General Notes. The building descriptors in this section are repeated for each pumping system. See the Pump Service building descriptor for a list of common pump services.
Pump Name | |
Applicability | All pumps |
---|---|
Definition | A unique descriptor for each pump |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Pump Service | |
Applicability | All pumps |
---|---|
Definition | The service for each pump. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Number of Pumps | |
Applicability | All pumps |
---|---|
Definition | The number of identical pumps in service in a particular loop, e.g. the heating hot water loop, chilled water loop, or condenser water loop |
Units | Numeric: integer |
Input Restrictions | As designed |
Water Loop Design | |
Applicability | All pumps |
---|---|
Definition | The heating and cooling delivery systems can consist of a simple primary loop system, or more complicated primary/secondary loops or primary/secondary/tertiary loops. |
Units | List (see above) |
Input Restrictions | As designed |
Pump Motor Modeling Method | |
Applicability | All pumps |
---|---|
Definition | Software commonly models fans in one of two ways: The simple method is for the user to enter the electric power per unit of flow (W/gpm). This method is commonly used for smaller systems. A more detailed method requires a specification of the |
Units | List: Power-Per-Unit-Flow or Detailed |
Input Restrictions | Either method may be used, as appropriate. |
Pump Motor Power-Per-Unit-Flow | |
Applicability | All baseline building pumps and proposed design pumps that use the Power-Per-Unit-Flow method. |
---|---|
Definition | The electric power of the pump divided by the flow at design conditions. |
Units | W/gpm |
Input Restrictions | As designed |
Impeller Efficiency | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The full load efficiency of the impeller |
Units | Ratio |
Input Restrictions | As designed |
Motor Efficiency | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The full load efficiency of the pump motor |
Units | Ratio |
Input Restrictions | As designed |
Pump Design Head | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The design pressure for the pump |
Units | Feet of water (or feet of head) |
Input Restrictions | As designed |
Pump Minimum Speed | |
Applicability | All two-speed or variable-speed pumps |
---|---|
Definition | The minimum pump speed for a two-speed for variable-speed pump. For two-speed pumps this is typically 0.67 or 0.5. Note that the pump minimum speed is not necessarily the same as the minimum flow ratio, since the system head may change. |
Units | Ratio |
Input Restrictions | As designed |
Pump Design Flow (GPM) | |
Applicability | All pumps |
---|---|
Definition | The flow rate of the pump at design conditions. This is derived from the load, and the design supply and return temperatures. |
Units | gpm or gpm/ton for condenser and primary chilled water pumps |
Input Restrictions | Not a user input |
Pump Control Type | |
Applicability | All pumps |
---|---|
Definition | The type of control for the pump. Choices are:
|
Units | None |
Input Restrictions | As designed. The default is “Fixed Speed, Variable Flow” which models the action of a constant speed pump riding the curve against 2-way control valves. |
Pump Operation | |
Applicability | All pumps |
---|---|
Definition | The type of pump operation can be either On-Demand, Standby or Scheduled. On-Demand operation means the pumps are only pumping when their associated equipment is cycling, so chiller and condenser pumps are on when the chiller is on and the heating hot water pump operates when its associated boiler is cycling. Standby operation allows hot or chilled water to circulate through the primary loop of a primary/secondary loop system or through a reduced portion of a primary-only system, assuming the system has appropriate 3-way valves. Scheduled operation means that the pumps and their associated equipment are turned completely off according to occupancy schedules, time of year, or outside conditions. Under scheduled operation, when the systems are on they are assumed to be in On-Demand mode. |
Units | List (see above) |
Input Restrictions | As designed |
Pump Part Load Curve | |||||||||||||||||
Applicability | All pumps | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A part-load power curve for the pump (6.8.5-1) $$ C\!I\!RC - PU\!M\!P - F\!P\!LR = a + b \times PLR + c \times PLR^2 + d \times PLR^3$$ (6.8.5-2) $$ P_{pump} = P_{design} \times C\!I\!RC - PU\!M\!P - F\!P\!L\!R $$where
[table title="Default Part-Load CIRC-PUMP-FPLR Coefficients – VSD on Circulation Pump" id="default-part-load-CIRC-PUMP-FPLR-Coefficients-–-VSD-on-Circulation-Pump"]
|
||||||||||||||||
Units | Data structure | ||||||||||||||||
Input Restrictions | As designed. Default is curve above. |
General Notes. The building descriptors in this section are repeated for each pumping system. See the Pump Service building descriptor for a list of common pump services.
Pump Name | |
Applicability | All pumps |
---|---|
Definition | A unique descriptor for each pump |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Pump Service | |
Applicability | All pumps |
---|---|
Definition | The service for each pump. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Number of Pumps | |
Applicability | All pumps |
---|---|
Definition | The number of identical pumps in service in a particular loop, e.g. the heating hot water loop, chilled water loop, or condenser water loop |
Units | Numeric: integer |
Input Restrictions | As designed |
Water Loop Design | |
Applicability | All pumps |
---|---|
Definition | The heating and cooling delivery systems can consist of a simple primary loop system, or more complicated primary/secondary loops or primary/secondary/tertiary loops. |
Units | List (see above) |
Input Restrictions | As designed |
Pump Motor Modeling Method | |
Applicability | All pumps |
---|---|
Definition | Software commonly models fans in one of two ways: The simple method is for the user to enter the electric power per unit of flow (W/gpm). This method is commonly used for smaller systems. A more detailed method requires a specification of the |
Units | List: Power-Per-Unit-Flow or Detailed |
Input Restrictions | Either method may be used, as appropriate. |
Pump Motor Power-Per-Unit-Flow | |
Applicability | All baseline building pumps and proposed design pumps that use the Power-Per-Unit-Flow method. |
---|---|
Definition | The electric power of the pump divided by the flow at design conditions. |
Units | W/gpm |
Input Restrictions | As designed |
Impeller Efficiency | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The full load efficiency of the impeller |
Units | Ratio |
Input Restrictions | As designed |
Motor Efficiency | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The full load efficiency of the pump motor |
Units | Ratio |
Input Restrictions | As designed |
Pump Design Head | |
Applicability | All pumps in proposed design that use the detailed modeling method |
---|---|
Definition | The design pressure for the pump |
Units | Feet of water (or feet of head) |
Input Restrictions | As designed |
Pump Minimum Speed | |
Applicability | All two-speed or variable-speed pumps |
---|---|
Definition | The minimum pump speed for a two-speed for variable-speed pump. For two-speed pumps this is typically 0.67 or 0.5. Note that the pump minimum speed is not necessarily the same as the minimum flow ratio, since the system head may change. |
Units | Ratio |
Input Restrictions | As designed |
Pump Design Flow (GPM) | |
Applicability | All pumps |
---|---|
Definition | The flow rate of the pump at design conditions. This is derived from the load, and the design supply and return temperatures. |
Units | gpm or gpm/ton for condenser and primary chilled water pumps |
Input Restrictions | Not a user input |
Pump Control Type | |
Applicability | All pumps |
---|---|
Definition | The type of control for the pump. Choices are:
|
Units | None |
Input Restrictions | As designed. The default is “Fixed Speed, Variable Flow” which models the action of a constant speed pump riding the curve against 2-way control valves. |
Pump Operation | |
Applicability | All pumps |
---|---|
Definition | The type of pump operation can be either On-Demand, Standby or Scheduled. On-Demand operation means the pumps are only pumping when their associated equipment is cycling, so chiller and condenser pumps are on when the chiller is on and the heating hot water pump operates when its associated boiler is cycling. Standby operation allows hot or chilled water to circulate through the primary loop of a primary/secondary loop system or through a reduced portion of a primary-only system, assuming the system has appropriate 3-way valves. Scheduled operation means that the pumps and their associated equipment are turned completely off according to occupancy schedules, time of year, or outside conditions. Under scheduled operation, when the systems are on they are assumed to be in On-Demand mode. |
Units | List (see above) |
Input Restrictions | As designed |
Pump Part Load Curve | |||||||||||||||||
Applicability | All pumps | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A part-load power curve for the pump (6.8.5-1) $$ C\!I\!RC - PU\!M\!P - F\!P\!LR = a + b \times PLR + c \times PLR^2 + d \times PLR^3$$ (6.8.5-2) $$ P_{pump} = P_{design} \times C\!I\!RC - PU\!M\!P - F\!P\!L\!R $$where
[table title="Default Part-Load CIRC-PUMP-FPLR Coefficients – VSD on Circulation Pump" id="default-part-load-CIRC-PUMP-FPLR-Coefficients-–-VSD-on-Circulation-Pump"]
|
||||||||||||||||
Units | Data structure | ||||||||||||||||
Input Restrictions | As designed. Default is curve above. |