Baseline Building Summary. None of the baseline building systems use a water-side economizer.
Water-Side Economizer Name | |
Applicability | All water-side economizers |
---|---|
Definition | The name of a water-side economizer for a cooling system |
Units | Text, unique |
Input Restrictions | Descriptive reference to the construction documents. The default is no water-side economizer. |
Baseline Rules | No water economizer |
Water Economizer Type | |
Applicability | All water-side economizers |
---|---|
Definition | The type of water-side economizer. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | No water economizer |
Water-Side Economizer HX Effectiveness | |||||||||
Applicability | Water-side economizers with an open cooling tower | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The effectiveness of a water-side heat exchanger at design conditions. This is defined as: (6.8.4-1) $$ W\!SE_{eff} = \frac{t_{ea}-t_{la}}{t_{ea}-t_{ew}}$$where
|
||||||||
Units | Ratio | ||||||||
Input Restrictions | As designed. The default is 60 %. | ||||||||
Baseline Rules | No water economizer |
Water-Side Economizer Maximum Tdb | |
Applicability | All water-side economizers |
---|---|
Definition | The control temperature (outside air dry-bulb temperature) above which the water-side economizer is disabled. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 65°F. |
Baseline Rules | No water economizer |
Water-Side Economizer Maximum CWS | |
Applicability | All water-side economizers |
---|---|
Definition | The control temperature (condenser water supply temperature) above which the water-side economizer is disabled. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 50°F. |
Baseline Rules | No water economizer |
Water-Side Economizer CWS Setpoint | |
Applicability | All water-side economizers |
---|---|
Definition | The design condenser water supply temperature for the cooling tower in economizer mode. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 45°F or 40°F for “Thermo Cycle.” |
Baseline Rules | No water economizer |
Water-Side Economizer Availability Schedule | |
Applicability | All water-side economizers |
---|---|
Definition | A schedule which represents the availability of the water-side economizer |
Units | Data structure: schedule, on/off |
Input Restrictions | As designed |
Baseline Rules | No water economizer |
Water-Side Economizer Auxiliary kW | |
Applicability | Water-side economizers with an open tower |
---|---|
Definition | The electrical input (pumps and auxiliaries) for a dedicated pump for the chilled water side of the heat exchanger. This power is in excess of the condenser water pumps and cooling tower fans for the system during water-side economizer operation. |
Units | KW or kW/ton |
Input Restrictions | As designed |
Baseline Rules | No water economizer |
Baseline Building Summary. None of the baseline building systems use a water-side economizer. Additional inputs to those below may be required to simulate actual control sequences.
Water-Side Economizer Name |
|
---|---|
Applicability |
All water-side economizers |
Definition |
The name of a water-side economizer for a cooling system |
Units |
Text, unique |
Input Restrictions |
Descriptive reference to the construction documents. The default is no water-side economizer. |
Baseline Rules |
No water economizer |
Water Economizer Type |
|
---|---|
Applicability |
All water-side economizers |
Definition |
The type of water-side economizer. Choices include:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
No water economizer |
Water-Side Economizer HX Effectiveness |
|||||||||
---|---|---|---|---|---|---|---|---|---|
Applicability |
Water-side economizers with an open cooling tower |
||||||||
Definition |
The effectiveness of a water-side heat exchanger at design conditions. This is defined as: (Equation 3.8.4-1) $$WSE_{eff} = \frac{t_{ea} - t_{la}} {t_{ea}-t_{ew}} $$ Where
|
||||||||
Units |
Ratio |
||||||||
Input Restrictions |
As designed. The default is 60 %. |
||||||||
Baseline Rules |
No water economizer |
Water-Side Economizer Maximum Tdb |
|
---|---|
Applicability |
All water-side economizers |
Definition |
The control temperature (outside air dry-bulb temperature) above which the water-side economizer is disabled. |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed. Defaults to 65 °F. |
Baseline Rules |
No water economizer |
Water-Side Economizer Maximum CWS |
|
---|---|
Applicability |
All water-side economizers |
Definition |
The control temperature (condenser water supply temperature) above which the water-side economizer is disabled. |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed. Defaults to 50 °F. |
Baseline Rules |
No water economizer |
Water-Side Economizer CWS Setpoint |
|
---|---|
Applicability |
All water-side economizers |
Definition |
The design condenser water supply temperature for the cooling tower in economizer mode. |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed. Defaults to 45°F or 40°F for “Thermo Cycle.” If a strainer cycle is specified, changeover temperature from economizer to mechanical cooling shall be set at 50°F. |
Baseline Rules |
No water economizer |
Water-Side Economizer Availability Schedule |
|
---|---|
Applicability |
All water-side economizers |
Definition |
A schedule which represents the availability of the water-side economizer |
Units |
Data structure: schedule, on/off |
Input Restrictions |
As designed |
Baseline Rules |
No water economizer |
Water-Side Economizer Auxiliary kW |
|
---|---|
Applicability |
Water-side economizers with an open tower |
Definition |
The electrical input (pumps and auxiliaries) for a dedicated pump for the chilled water side of the heat exchanger. This power is in excess of the condenser water pumps and cooling tower fans for the system during water-side economizer operation. |
Units |
KW or kW/ton |
Input Restrictions |
As designed |
Baseline Rules |
No water economizer |
Baseline Building Summary:
Baseline building system 11 would include an integrated fluid economizer, meeting the requirements as specified in this section, also in Section 6.5.1.2 of Standard 90.1-2019. Additional inputs to those below may be required to simulate actual control sequences.
Fluid Economizer Name | |
---|---|
Applicability | All fluid economizers |
Definition | The name of a fluid economizer for a cooling system |
Units | Text, unique |
Input Restrictions | As designed |
Baseline Building | A water side fluid economizer will be modeled for baseline system 11, for computer rooms |
Water Economizer Type | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All fluid economizers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Definition |
The type of fluid economizer. Choices include: · None · Heat exchanger in parallel with chillers: This would be used with an open cooling tower combined with a heat exchanger or evaporative cooler (closed circuit cooling tower) and is a non-integrated economizer, because the chillers are locked out when the plant is in economizer mode. · Heat exchanger in series with chillers: This would be used with an open cooling tower and heat exchanger or evaporative cooler (closed circuit cooling tower) and is integrated because the piping is arranged so the chilled water return is precooled and chillers can operate simultaneously with water economizer operation. Depending on the proportion of water economizer capacity compared to chiller capacity, the water economizer heat exchanger may see the full chilled water flow, or be in a “sidecar” arrangement where only a portion of the chilled water flow goes through the heat exchanger. · Direct water economizer: In this system, the condenser and chilled-water systems are connected. When the outdoor wet bulb temperature is low enough, cold water from the cooling tower is routed directly into the chilled-water loop. This would be used with filtration of the condenser water. In this case, a heat exchanger is not needed. This type can work as either an integrated or a non-integrated economizer, depending on piping arrangement. Although the strainer cycle is the most efficient water economizer option, it greatly increases the risk of fouling in the chilled-water system and cooling coils with the same type of contamination that is common in open cooling-tower systems. A strainer or filter can be used to minimize this contamination, but the potential for fouling prevents widespread use of the strainer-cycle system (Trane, 2016). |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | List (see above) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Building |
The baseline water side economizer should be a ‘heat exchanger in series with chillers’. It shall be modeled for HVAC system 11 that serve computer rooms. The baseline system will be modeled with a heat exchanger in series with the chiller that pre-cools the chilled water return. The flow through the heat exchanger shall match the required water economizer capacity. The fluid economizer shall be capable of providing up to 100% of the expected system cooling load at outdoor air temperatures listed in Table 93. Table 93. Fluid Economizer Sizing Dry-Bulb and Wet-Bulb Requirements for Computer Rooms
|
Fluid Economizer Approach | |
---|---|
Applicability | All fluid economizers |
Definition | The design temperature difference between the chilled water temperature leaving the heat exchanger and the condenser water (tower leaving) inlet to the heat exchanger. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 2°F. |
Baseline Building | This will be specified as 2°F for the baseline building. |
Fluid Economizer Activation Temp. Difference | |
---|---|
Applicability | All fluid economizers |
Definition | The minimum temperature difference between the tower leaving temperature and the chilled water return below which the fluid economizer is disabled. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 3.5°F below the chilled water return temperature. |
Baseline Building | This will be specified as 3.5°F below the chilled water return temperature for the baseline building. |
Fluid Economizer Tower Leaving Temp. Setpoint | |
---|---|
Applicability | All fluid economizers |
Definition | The temperature setpoint for the water side economizer heat exchanger entering temperature (tower leaving temperature). |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. |
Baseline Building | This will be the 2°F below the chilled water supply temperature for the baseline building. |
Fluid Economizer Availability Schedule | |
---|---|
Applicability | All fluid economizers |
Definition | A schedule that represents the availability of the fluid economizer |
Units | Data structure: schedule, on/off |
Input Restrictions | As designed. |
Baseline Building | The waterside economizer will be simulated to be ‘Always On’ for the baseline building. |
Fluid Economizer Hydronic Pressure Drop | |
---|---|
Applicability | All fluid economizers |
Definition | Pressure drop of the pre-cooling coils of the fluid to water heat exchanger. |
Units | ft of water |
Input Restrictions | As designed |
Baseline Building | Refer to Section 3.7.5 for baseline system hydronic pressure drop requirements. |
Baseline Building Summary. None of the baseline building systems use a water-side economizer.
Water-Side Economizer Name | |
Applicability | All water-side economizers |
---|---|
Definition | The name of a water-side economizer for a cooling system |
Units | Text, unique |
Input Restrictions | Descriptive reference to the construction documents. The default is no water-side economizer. |
Baseline Rules | No water economizer |
Water Economizer Type | |
Applicability | All water-side economizers |
---|---|
Definition | The type of water-side economizer. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Water-Side Economizer HX Effectiveness | |||||||||
Applicability | Water-side economizers with an open cooling tower | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The effectiveness of a water-side heat exchanger at design conditions. This is defined as: (6.8.4-1) $$ W\!SE_{eff} = \frac{t_{ea}-t_{la}}{t_{ea}-t_{ew}}$$where
|
||||||||
Units | Ratio | ||||||||
Input Restrictions | As designed. The default is 60 %. |
Water-Side Economizer Maximum Tdb | |
Applicability | All water-side economizers |
---|---|
Definition | The control temperature (outside air dry-bulb temperature) above which the water-side economizer is disabled. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 65°F. |
Water-Side Economizer Maximum CWS | |
Applicability | All water-side economizers |
---|---|
Definition | The control temperature (condenser water supply temperature) above which the water-side economizer is disabled. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 50°F. |
Water-Side Economizer CWS Setpoint | |
Applicability | All water-side economizers |
---|---|
Definition | The design condenser water supply temperature for the cooling tower in economizer mode. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 45°F or 40°F for “Thermo Cycle.” |
Water-Side Economizer Availability Schedule | |
Applicability | All water-side economizers |
---|---|
Definition | A schedule which represents the availability of the water-side economizer |
Units | Data structure: schedule, on/off |
Input Restrictions | As designed |
Water-Side Economizer Auxiliary kW | |
Applicability | Water-side economizers with an open tower |
---|---|
Definition | The electrical input (pumps and auxiliaries) for a dedicated pump for the chilled water side of the heat exchanger. This power is in excess of the condenser water pumps and cooling tower fans for the system during water-side economizer operation. |
Units | KW or kW/ton |
Input Restrictions | As designed |
Baseline Building Summary. None of the baseline building systems use a water-side economizer.
Water-Side Economizer Name | |
Applicability | All water-side economizers |
---|---|
Definition | The name of a water-side economizer for a cooling system |
Units | Text, unique |
Input Restrictions | Descriptive reference to the construction documents. The default is no water-side economizer. |
Baseline Rules | No water economizer |
Water Economizer Type | |
Applicability | All water-side economizers |
---|---|
Definition | The type of water-side economizer. Choices include:
|
Units | List (see above) |
Input Restrictions | As designed |
Water-Side Economizer HX Effectiveness | |||||||||
Applicability | Water-side economizers with an open cooling tower | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The effectiveness of a water-side heat exchanger at design conditions. This is defined as: (6.8.4-1) $$ W\!SE_{eff} = \frac{t_{ea}-t_{la}}{t_{ea}-t_{ew}}$$where
|
||||||||
Units | Ratio | ||||||||
Input Restrictions | As designed. The default is 60 %. |
Water-Side Economizer Maximum Tdb | |
Applicability | All water-side economizers |
---|---|
Definition | The control temperature (outside air dry-bulb temperature) above which the water-side economizer is disabled. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 65°F. |
Water-Side Economizer Maximum CWS | |
Applicability | All water-side economizers |
---|---|
Definition | The control temperature (condenser water supply temperature) above which the water-side economizer is disabled. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 50°F. |
Water-Side Economizer CWS Setpoint | |
Applicability | All water-side economizers |
---|---|
Definition | The design condenser water supply temperature for the cooling tower in economizer mode. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Defaults to 45°F or 40°F for “Thermo Cycle.” |
Water-Side Economizer Availability Schedule | |
Applicability | All water-side economizers |
---|---|
Definition | A schedule which represents the availability of the water-side economizer |
Units | Data structure: schedule, on/off |
Input Restrictions | As designed |
Water-Side Economizer Auxiliary kW | |
Applicability | Water-side economizers with an open tower |
---|---|
Definition | The electrical input (pumps and auxiliaries) for a dedicated pump for the chilled water side of the heat exchanger. This power is in excess of the condenser water pumps and cooling tower fans for the system during water-side economizer operation. |
Units | KW or kW/ton |
Input Restrictions | As designed |