This group of building descriptors relate to the secondary HVAC systems. There is not a one-to-one relationship between secondary HVAC system components in the proposed design and the baseline building since the baseline building system is determined from building type, size and heating source. Appendix A shows the applicability of each building descriptor for the eight baseline building systems. Depending on the nature of the proposed design, any of the building descriptors could apply.
This group of building descriptors relate to the secondary HVAC systems. There is not a one-to-one relationship between secondary HVAC system components in the proposed design and the baseline building since the baseline building system is determined from building type, size and heating source. See Table 3.1-1, 3.1-2 and 3.1-3. Additional detail on the baseline building systems is provided in the tables below. Depending on the nature of the proposed design, any of the building descriptors could apply.
Table 3.7-1: Baseline Building System Type
Baseline Building System |
System Type |
System 1 – PTAC |
Single Zone Heating and Cooling |
System 2 – PTHP |
Single Zone Heating and Cooling |
System 3 – PSZ-AC |
Single Zone Heating and Cooling |
System 4 – PSZ-HP |
Single Zone Heating and Cooling |
System 5 – Packaged VAV with Reheat |
Single Duct VAV |
System 6 – Packaged VAV with PFP boxes |
Single Duct VAV |
System 7 – VAV with Reheat |
Single Duct VAV |
System 8 – VAV with PFP boxes |
Single Duct VAV |
System 9 – Heating and Ventilation |
Constant Volume Heat/Vent (no cooling) |
System 10 – Heating and Ventilation |
Constant Volume Heat/Vent (no cooling) |
System 11. SZ–VAV |
Single-zone VAV |
System 12. SZ-CV-HW |
Single zone with hot water heat |
System 13. SZ-CV-ER |
Single zone with electric resistance heat |
Table 3.7-2: Summary of Baseline Building Secondary HVAC System Properties
System |
Fan Control |
Economizer |
Cooling Type |
Cooling Efficiency. |
Minimum Supply T. |
Heating Type |
Heating Efficiency |
Maximum Supply T. |
1 PTAC |
Constant volume |
Not required |
Direct Expansion |
Minimum SEER or EER based on equipment type and output capacity of proposed unit(s). Adjusted EER is calculated to account for supply fan energy. |
20 °F below occupied space cooling setpoint |
Hot-water fossil fuel boiler |
Minimum AFUE, Thermal Efficiency, COP or HSPF based on equipment type and output capacity of baseline unit(s). |
|
2 PTHP |
Electric heat pump |
|||||||
3 PSZ-AC |
Integrated economizer with dry-bulb high limit by climate zone. See 6.7.4 ‘Outside Air Controls and Economizer’ for details and exceptions. |
Fossil fuel furnace |
||||||
4 PSZ-HP |
Electric heat pump |
|||||||
5 PVAV |
Variable volume |
Hot-water fossil fuel boiler |
||||||
6 PVAV / PFP |
Electric resistance |
|||||||
7 VAV |
Chilled water |
See 6.8 Primary Systems |
Hot-water fossil fuel boiler |
|||||
8 VAV / PFP |
Electric resistance |
|||||||
9 HV Furnace |
Constant volume |
Not required |
None |
None |
Fossil fuel furnace |
|||
10 HV Electric |
Electric resistance |
|||||||
11 SZ-VAV |
Variable volume |
Integrated economizer with dry-bulb high limit by climate zone. See 6.7.4 for details. |
Chilled water |
See 6.8 Primary Systems |
See note. |
|||
12 SZ-CV-HW |
Constant Volume |
Hot-water fossil fuel boiler |
||||||
13 SZ-CV-ER |
Electric resistance |
Table 3.7-3: Summary of Baseline Building Variable Volume Fan Control and Reheat
Code |
Supply Fan Control |
PFP Fan |
Reheat Terminal Flow |
|
5 PVAV |
Variable speed controlled by variable speed drives. The part load performance of VAV fans is required to be modeled in accordance to section ‘Fan Part Load Curve’ in ‘Fan Systems’. |
|
Minimum volume setpoint for reheat is highest of 30% of zone peak flow, minimum outdoor air flow rate or airflow rate required by applicable rating authority. See Section 3.6.5 for details |
|
6 PVAV / PFP |
PIU fan would be constant volume. AHU fan should cycle on only for cooling. Zone fans should provide unoccupied heating. |
Fans for PIU units are sized for 50% of peak design primary air |
||
7 VAV |
|
|
||
8 VAV / PFP |
PIU fan would be constant volume. AHU fan should cycle on only for cooling. Zone fans should provide unoccupied heating. |
Fans for PIU units are sized for 50% of peak design primary air |
This group of building descriptors relate to the secondary HVAC systems. There is not a one-to-one relationship between secondary HVAC system components in the proposed design and the baseline building since the baseline building system is determined from building type, size, and heating source. Depending on the nature of the proposed design, any of the building descriptors could apply. The HVAC baseline systems are described in the summary tables below for reference. The details of individual building descriptor definitions can be found in Sections 3.7 and 3.8.
Table 41. System 1 and System 2 Descriptions
System Description | Packaged terminal air conditioner (#1) or packaged terminal heat pump (#2) |
Supply Fan Control | Constant volume |
Min Supply Temp | 20°F below occupied space cooling setpoint |
Cooling System | DX |
Cooling Efficiency | Minimum seasonal energy efficiency ratio (SEER) or EER based on equipment type and output capacity of proposed unit(s). Adjusted EER is calculated to account for supply fan energy. |
Maximum Supply Temp | 20°F above occupied space heating setpoint |
Heating System | Hot water boiler (#1) or heat pump (#2) |
Heating Efficiency | Minimum annual fuel utilization efficiency (AFUE), thermal efficiency, COP, or heating seasonal performance factor (HSPF) based on equipment type and output capacity of baseline unit(s) |
Economizer | None |
Ducts | N/A (not ducted) |