Baseline Building Fan System Summary
The baseline building fan system is summarized in this section. See [bookref id="hvac-mapping"] for the HVAC baseline building system mapping.
Total baseline building fan system power for the baseline building fan systems is given in [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007 and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] for ASHRAE Standard 90.1-2001. In these tables, "cfms" is the supply fan air flow at peak design conditions. This is calculated for the baseline building with the sizing procedure described in [bookref id="calculation-process-for-tax-deductions-and-green-building-ratings"] and [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. This brake horsepower includes the supply fan, the return fan, and exhaust fans. Exhaust fans include kitchen hoods, toilets, fume hoods, and other miscellaneous fans that operate at design conditions.
[table title="Baseline Building Fan System – ASHRAE Standard 90.1-2007" id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"]
System Types 1-2 | System Types 3-4 | System Types 5-8 | |
Brake Horsepower (bhp) | Not applicable | 0.00094 x cfms + A | 0.0013 x cfms + A |
Fan Motor Efficiency (hm) | Not applicable | ASHRAE Standard 90.1-2007, Table 10.8 | ASHRAE Standard 90.1-2007, Table 10.8 |
Fan Power (W) | 0.3 x cfms | (bhp x 746)/$\eta$m | (bhp x 746)/$\eta$m |
The term “A” for system types 3-8, is calculated based on equipment in the proposed design using the procedure in Table 6.5.3.1.1B of ASHRAE Standard 90.1-2007. This accounts for various additional fan pressure drops associated with special conditions. |
[table title="Baseline Building Fan System – ASHRAE Standard 90.1-2001" id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"]
Fan Size | System Types 1-4 | System Types 5-8 | |
Nameplate Horsepower (nhp) | < 20,000 cfm | 0.0012 x cfms + Pfilter + Pprocess + Prelief | 0.0017 x cfms + Pfilter + Pprocess + Prelief |
=> 20,000 cfm | 0.0011 x cfms + Pfilter + Pprocess + Prelief | 0.0015 x cfms + Pfilter + Pprocess + Prelief | |
Fan Motor Efficiency (hm) | ASHRAE Standard 90.1-2001, Table 10.2 | ASHRAE Standard 90.1-2001, Table 10.2 | |
Brake Horsepower (bhp) | nhp x $\eta$m | nhp x $\eta$m | |
Fan Power (W) | (bhp x 746)/ $\eta$m | (bhp x 746)/ $\eta$m | |
The terms Pfilter, Pprocess, and Prelief account for additional pressure drop. These are based on features in the proposed design such as special filtration, process fans, and relief or return fans. See Section 6.3.3.1 of ASHRAE Standard 90.1-2001 and the associated User's Manual for details on how to calculate these adders. |
When the proposed design has exhaust fans (toilets or kitchens), return fans, or fume hood exhaust systems, the baseline building has the same systems. The brake horsepower determined from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] is allocated to these baseline building fan systems proportionally to the allocation in the proposed design. The allocation of brake horsepower to the supply fan, the return and any exhaust or fume hood fans is based on the ratios described below.
Supply Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of supply fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Return Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of return fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Exhaust Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of exhaust fan brake horsepower in the proposed design to total fan system brake hp for the proposed design at design conditions. Exhaust fans include toilet exhaust, kitchen hoods and other miscellaneous exhaust. Fume hood exhaust is treated separately. |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors. In the event that a common exhaust system serves thermal blocks that are served by different HVAC systems, the brake horsepower shall be divided in proportion to design cfm. |
Baseline Rules | Same as proposed design |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules | The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. |
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable to variable air volume systems Based on the prescribed system type. Refer to the HVAC System Map in [bookref id="hvac-mapping"]. |
[table title="Baseline Building Fan Control Method" id="baseline -bilding-fan-control-method"]
Baseline building System | Fan Control Method |
System 1 – PTAC | Constant volume |
System 2 – PTHP | Constant volume |
System 3 – PSZ-AC | Constant volume |
System 4 – PSZ-HP | Constant volume |
System 5 – Packaged VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 6 – Packaged VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
System 7 – VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 8 – VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Baseline Rules | See [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007 and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] for ASHRAE Standard 90.1-2001. These tables give the baseline building fan system brake horsepower. The brake horsepower for the supply fan is this value times the Supply Fan Ratio (see above). |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 or Table 10.2 of ASHRAE Standard 90.1-2001 |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Draw through |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
[table title="Fan Curve Default Values" id="fan-curve-default-values"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 with no adjustment for static pressure setpoint reset. |
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
||||
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007 and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] for ASHRAE Standard 90.1-2001. This power is then multiplied by the supply fan ratio. |
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum, otherwise, the return air ducts are assumed to be located in the space. |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be same as proposed design. |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The return fan air Rated Capacity shall be equal to the baseline building supply fan capacity less exhaust air flow. |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The bhp of the return fan shall be the fan system brake horsepower (see [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"]) times the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 or Table 10.2 of ASHRAE Standard 90.1-2001 |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 that have a return/relief fan. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007 and [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] for ASHRAE Standard 90.1-2001. This power is then multiplied by the return fan ratio. |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks. The baseline building has exhaust fans when the proposed design has exhaust fans. The exhaust air flow is the same for the baseline building and the proposed design.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Baseline Rules | The baseline building exhaust fan control shall generally be the same as the proposed design. For laboratories that have exhaust flow of 5,000 cfm or more, the baseline building exhaust flow shall vary in response to scheduled fume hood exhaust and lab zone airflow schedules. Fume hood exhaust flow control shall be the same as design, and general exhaust (relief) shall be VSD. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Baseline Rules | Same as the proposed design |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | The bhp for the baseline building is the total system fan horsepower from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] or [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] times the exhaust fan ratio. |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 or Table 10.2 of ASHRAE Standard 90.1-2001 |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Baseline Rules | The baseline building fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |
Baseline Rules | The fan system power from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] or [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2001"] |
Baseline Building Fan System Summary
The baseline building fan system is summarized in this section. See [bookref id="hvac-mapping"] for the HVAC baseline building system mapping.
Total baseline building fan system power for the baseline building fan systems is given in [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"]. In this table, "cfms" is the supply fan air flow at peak design conditions. This is calculated for the baseline building with the sizing procedure described in [bookref id="calculation-process-for-tax-deductions-and-green-building-ratings"] and [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. This brake horsepower includes the supply fan, the return fan, and exhaust fans. Exhaust fans include kitchen hoods, toilets, fume hoods, and other miscellaneous fans that operate at design conditions.
[table title="Baseline Building Fan System – ASHRAE Standard 90.1-2007" id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"]
System Types 1-2 | System Types 3-4 | System Types 5-8 | |
Brake Horsepower (bhp) | Not applicable | 0.00094 x cfms + A | 0.0013 x cfms + A |
Fan Motor Efficiency (hm) | Not applicable | ASHRAE Standard 90.1-2007, Table 10.8 | ASHRAE Standard 90.1-2007, Table 10.8 |
Fan Power (W) | 0.3 x cfms | (bhp x 746)/$\eta$m | (bhp x 746)/$\eta$m |
The term “A” for system types 3-8, is calculated based on equipment in the proposed design using the procedure in Table 6.5.3.1.1B of ASHRAE Standard 90.1-2007. This accounts for various additional fan pressure drops associated with special conditions. |
When the proposed design has exhaust fans (toilets or kitchens), return fans, or fume hood exhaust systems, the baseline building has the same systems. The brake horsepower determined from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] is allocated to these baseline building fan systems proportionally to the allocation in the proposed design. The allocation of brake horsepower to the supply fan, the return and any exhaust or fume hood fans is based on the ratios described below.
Supply Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of supply fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Return Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of return fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Exhaust Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of exhaust fan brake horsepower in the proposed design to total fan system brake hp for the proposed design at design conditions. Exhaust fans include toilet exhaust, kitchen hoods and other miscellaneous exhaust. Fume hood exhaust is treated separately. |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors. In the event that a common exhaust system serves thermal blocks that are served by different HVAC systems, the brake horsepower shall be divided in proportion to design cfm. |
Baseline Rules | Same as proposed design |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules | The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. |
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable to variable air volume systems Based on the prescribed system type. Refer to the HVAC System Map in [bookref id="hvac-mapping"]. |
[table title="Baseline Building Fan Control Method" id="baseline -bilding-fan-control-method"]
Baseline building System | Fan Control Method |
System 1 – PTAC | Constant volume |
System 2 – PTHP | Constant volume |
System 3 – PSZ-AC | Constant volume |
System 4 – PSZ-HP | Constant volume |
System 5 – Packaged VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 6 – Packaged VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
System 7 – VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 8 – VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Baseline Rules | See [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007. These tables give the baseline building fan system brake horsepower. The brake horsepower for the supply fan is this value times the Supply Fan Ratio (see above). |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Draw through |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
[table title="Fan Curve Default Values" id="fan-curve-default-values"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 with no adjustment for static pressure setpoint reset. |
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
||||
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007. This power is then multiplied by the supply fan ratio. |
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum, otherwise, the return air ducts are assumed to be located in the space. |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be same as proposed design. |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The return fan air Rated Capacity shall be equal to the baseline building supply fan capacity less exhaust air flow. |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The bhp of the return fan shall be the fan system brake horsepower (see [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"]) times the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 that have a return/relief fan. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] for ASHRAE Standard 90.1-2007. This power is then multiplied by the return fan ratio. |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks. The baseline building has exhaust fans when the proposed design has exhaust fans. The exhaust air flow is the same for the baseline building and the proposed design.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Baseline Rules | The baseline building exhaust fan control shall generally be the same as the proposed design. For laboratories that have exhaust flow of 5,000 cfm or more, the baseline building exhaust flow shall vary in response to scheduled fume hood exhaust and lab zone airflow schedules. Fume hood exhaust flow control shall be the same as design, and general exhaust (relief) shall be VSD. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Baseline Rules | Same as the proposed design |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | The bhp for the baseline building is the total system fan horsepower from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] times the exhaust fan ratio. |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Baseline Rules | The baseline building fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |
Baseline Rules | The fan system power from [bookref id="baseline-building-fan-system-–-ASHRAE-standard-90.1-2007"] |
Baseline Building Fan System Summary
The baseline building fan system is summarized in this section. See Figure 6.1.2-1 for the HVAC baseline building system mapping.
Total baseline building fan system power for the baseline building fan systems is given in Table 6.7.3-1. In this table, "cfms" is the supply fan air flow at peak design conditions. This is calculated for the baseline building with the sizing procedure described in Figure 2.4-1. This brake horsepower includes the supply fan, the return fan, and exhaust fans. Exhaust fans include kitchen hoods, toilets, fume hoods, and other miscellaneous fans that operate at design conditions.
Table 6.7.3-1: Baseline Building Fan System – ASHRAE Standard 90.1 2010
System Types 1-2 | System Types 3-4 | System Types 5-8 | System Types 9-10 | |
Brake Horsepower (bhp) | Not applicable | 0.00094 x cfms + A | 0.0013 x cfms + A | Not Applicable |
Fan Motor Efficiency (hm) | Not applicable | ASHRAE Standard 90.1-2007, Table 10.8 | ASHRAE Standard 90.1-2007, Table 10.8 | Not Applicable |
Fan Power (W) | 0.3 x cfms | (bhp x 746)/$\eta$m | (bhp x 746)/$\eta$m | 0.3 x cfms OR 0.054 x CFMnmc |
The term “A” for system types 3-8, is calculated based on equipment in the proposed design using the procedure in Table 6.5.3.1.1B of ASHRAE Standard 90.1-2010. This accounts for various additional fan pressure drops associated with special conditions. *CFMnmc is the baseline non-mechanical cooling fan airflow in cfm. This alternate equation is only used if there is a non-mechanical cooling system in place. |
When the proposed design has exhaust fans (toilets or kitchens), return fans, or fume hood exhaust systems, the baseline building has the same systems. The brake horsepower determined from Table 6.7.3-1 is allocated to these baseline building fan systems proportionally to the allocation in the proposed design. The allocation of brake horsepower to the supply fan, the return and any exhaust or fume hood fans is based on the ratios described below.
Supply Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of supply fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Return Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of return fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors |
Baseline Rules | Same as proposed design |
Exhaust Fan Ratio | |
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust or return fans |
---|---|
Definition | The ratio of exhaust fan brake horsepower in the proposed design to total fan system brake hp for the proposed design at design conditions. Exhaust fans include toilet exhaust, kitchen hoods and other miscellaneous exhaust. Fume hood exhaust is treated separately. |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors. In the event that a common exhaust system serves thermal blocks that are served by different HVAC systems, the brake horsepower shall be divided in proportion to design cfm. |
Baseline Rules | Same as proposed design |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules |
The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system.
|
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable to variable air volume systems Based on the prescribed system type. Refer to the HVAC System Map in Figure 6.1.2-1. |
Table 6.7.3-2: Baseline Building Fan Control Method
Baseline building System | Fan Control Method |
System 1 – PTAC | Constant volume |
System 2 – PTHP | Constant volume |
System 3 – PSZ-AC | Constant volume |
System 4 – PSZ-HP | Constant volume |
System 5 – Packaged VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 6 – Packaged VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
System 7 – VAV with Reheat | Variable-flow, variable speed drive (VSD) |
System 8 – VAV with PFP boxes | Variable-flow, variable speed drive (VSD) |
System 9 – Heating and Ventilation | Constant Volume |
System 10 – Heating and Ventilation | Constant Volume |
*Effective 1/1/2012, all air-conditioning equipment and air-handling units with dx cooling and a cooling capacity greater than or equal to 110,000 Btu/h that serve single zones shall have supply fans controlled by two-speed motors or variable speed drives. At cooling demands less than or equal to 50% , the supply fan controls shall reduce the airflow to no greater than the larger of the following: 1)1/2 of the full fan speed or 2)the minimum outdoor air. |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Baseline Rules | See Table 6.7.2-1 for ASHRAE Standard 90.1-2007. These tables give the baseline building fan system brake horsepower. The brake horsepower for the supply fan is this value times the Supply Fan Ratio (see above). |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Draw through |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and Table 6.7.3-3 for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
Table 6.7.3-3:Fan Curve Default Values
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 with no adjustment for static pressure setpoint reset. |
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
||||
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 6.7.3-1 for ASHRAE Standard 90.1-2007. This power is then multiplied by the supply fan ratio. |
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum, otherwise, the return air ducts are assumed to be located in the space. |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be same as proposed design. |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The return fan air Rated Capacity shall be equal to the baseline building supply fan capacity less exhaust air flow. |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | Applicable when the baseline building has a return fan. The bhp of the return fan shall be the fan system brake horsepower (see Table 6.7.3-1) times the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When Static Pressure and Fan Efficiency are entered for the proposed design, the baseline building shall use Brake Horsepower. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | In the air stream |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and Table 6.7.3-3 for the type of fan specified in the proposed design. |
Baseline Rules | Not applicable for baseline building systems 1-4. The curve for VSD fans shall be used for baseline building systems 5-8 that have a return/relief fan. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Baseline Rules | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 6.7.3-1 for ASHRAE Standard 90.1-2007. This power is then multiplied by the return fan ratio. |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks. The baseline building has exhaust fans when the proposed design has exhaust fans. The exhaust air flow is the same for the baseline building and the proposed design.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules |
Same as the proposed design except that baseline building kitchen exhaust rate may not exceed the maximum levels defined by ASHRAE 90.1-2010, Table 6.5.7.1.3.
|
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Baseline Rules |
The baseline building exhaust fan control shall generally be the same as the proposed design. For laboratories that have exhaust flow of 5,000 cfm or more, the baseline building exhaust flow shall vary in response to scheduled fume hood exhaust and lab zone airflow schedules. Fume hood exhaust flow control shall be the same as design, and general exhaust (relief) shall be VSD.
If a kitchen zone design exhaust rate is greater than 5,000 cfm, the baseline building system serving the kitchen shall be system type 5 or 7 with a demand ventilation system on 75% of the exhaust air. The system shall reduce exhaust and replacement air system airflow rates by 50% for one half of the kitchen occupied hours. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Baseline Rules | Same as the proposed design |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Rules | The bhp for the baseline building is the total system fan horsepower from Table 6.7.3-1 times the exhaust fan ratio. |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules | Not applicable. When static pressure and fan efficiency are entered for the proposed design, the baseline building shall use brake horsepower. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Baseline Rules | From Table 10.8 of ASHRAE Standard 90.1-2007 |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and Table 6.7.3-3 for the type of fan specified in the proposed design. |
Baseline Rules | The baseline building fan curve shall be selected from Equation (6.7.3-1) and Table 6.7.3-3 for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |
Baseline Rules | The fan system power from Table 6.7.3-1. |
This section addresses:
Baseline Building Fan System Summary
The baseline building fan system is summarized in this section. See Table 3 for the HVAC baseline building system mapping.
Total baseline building fan system power for the baseline building fan systems is given in the following sections as well as Table 53 and Table 54. Table 52 summarizes all descriptors for fan systems and their applicability to supply, return/relief, and exhaust fans.
Table 4 summarizes inputs for each of the three approaches for imputing system fan power (fan power method, brake horsepower method, and design pressure drop method).
· In these tables, CFMs is the baseline fan supply fan airflow at peak design conditions.
· The fan system power includes the supply fan, the return fan, and exhaust fans.
· Exhaust fans include kitchen hoods, toilets, fume hoods, and other miscellaneous fans that operate at design conditions.
When the proposed design has return fans, exhaust fans (toilets or kitchens), or fume hood exhaust systems, the baseline building has the same systems. Fan power will be allocated to the baseline supply, return, and exhaust fans based on the Fan System Power described below and the ratio of each fans power in the proposed design to the proposed design fan system power.
Table 52. Building Descriptor Applicability for Fan Systems
Inputs | Supply Fan | Return/ Relief Fan | Exhaust Fans (Hoods) |
---|---|---|---|
Modeling Method | yes | Same as supply | yes |
Air Rated Capacity | yes | yes | yes |
Plenum Zone | no | yes | no |
Return Air Path | no | yes | no |
Fan Control Method | no | Same as supply | yes |
Brake Horsepower | yes | yes | yes |
Static Pressure | yes | yes | yes |
Fan Efficiency | yes | yes | yes |
Motor Efficiency | yes | yes | yes |
Fan Position | yes | no | no |
Motor Position | yes | yes | no |
Part-Load Power Curve | yes | yes | yes |
Fan KW | yes | yes | yes |
Table 53. Baseline Fan System Details for Fan System Power
System | Fan Power Method (W/cfm) | Brake Horsepower Method (bhp/cfm) | Design Pressure Drop (DPD) Method | Fan Motor Efficiency ŋm | Fan Mech Efficiency | DPD (If no additional pressure drop credits) (a) |
1 & 2 | 0.3 | W/cfm x ŋm x 0.00134 | bhp/cfm x fan mech efficiency x 6356 | 80% | 65% | 1.33 in. w.g |
3, 4, 12. & 13 |
(bhp x 746)/ŋm | 0.00094 x CFMs + A | bhp/cfm x fan mech efficiency x 6356 | Standard 90.1-2019, Table G3.9.1(a) | 65% | 3.88 in. w.g. |
5 through 8 |
(bhp x 746)/ŋm | 0.0013 x CFMs + A | bhp/cfm x fan mech efficiency x 6356 | Standard 90.1-2019, Table G3.9.1(a) | 65% | 5.37 in. w.g. |
9 & 10 supply fan |
0.3 | W/cfm x ŋm x 0.00134 | bhp/cfm x fan mech efficiency x 6356 | Standard 90.1-2019, Table G3.9.1(a) | 65% | 1.33 in. w.g. |
9 & 10 non- mechanical cooling fan(b) |
0.054 | W/cfm x ŋm x 0.00134 | bhp/cfm x fan mech efficiency x 6356 | 80% | 65% | 0.24 in. w.g. |
11 | (bhp x 746)/ŋm | 0.00062 x CFMs + A | bhp/cfm x fan mech efficiency x 6356 | Standard 90.1-2019, Table G3.9.1(a) | 65% | 2.56 in. w.g. |
The term “A” for system types 3 through 8 is calculated based on equipment included in the proposed design
using the procedure in Table 6.5.3.1.1 of ASHRAE Standard 90.1-2019 and the airflows from the baseline
design. This accounts for various additional fan pressure drops associated with special conditions.
(a) Fan motor efficiency is the efficiency from Table G3.9.1 of Standard 90.1-2019 for the next motor size
greater than the bhp.
(b) This alternate equation is only used if there is a non-mechanical cooling fan in place in the proposed design.
(c) If system qualified for additional pressure drop credits DPD should be calculated based on adjusted bhp.
Pressure Drop Adjustment | |
---|---|
Applicability | Any system serving zones served by systems in the proposed design which qualify for pressure drop adjustments in Table 54 |
Definition | Adjustments to fan power limitations related to application-specific requirements as allowed by Standard 90.1-2019 Table 6.5.3.1-1 |
Units | List |
Input Restrictions | As designed |
Baseline Building | Calculated from Section 6.5.3.1-1 of Standard 90.1-2019 for baseline system fans. Pressure drop adjustment is based on the device from Table 54 being present in the proposed design. |
Table 54. Baseline Building: Fan Power Limitation Pressure Drop Adjustment
Device | Adjustment |
Credits | |
Return or exhaust systems required by code or accreditation standards to be fully ducted, or systems required to maintain air pressure differentials between adjacent rooms. |
0.5 in. w.c. (2.15 in. w.c. for laboratory and vivarium systems) |
Return and/or exhaust airflow control devices | 0.5 in. w.c. |
Exhaust filters, scrubbers, or other exhaust treatment | The pressure drop of device calculated at fan system design condition |
Particulate filtration credit: MERV 9 through 12 | 0.5 in. w.c. |
Particulate filtration credit: MERV 13 through 15 | 0.9 in. w.c. |
Particulate filtration credit: MERV 16 and greater and electronically enhanced filters |
Pressure drop calculated at 2x clean filter pressure drop at fan system design condition |
Carbon and other gas-phase air cleaners | Clean filter pressure drop at fan system design condition |
Biosafety cabinet | Pressure drop of device at fan system design condition |
Energy recovery device and other coil runaround loop | (2.2 × Energy Recovery Effectiveness)—0.5 in w.c. for each airstream |
Coil runaround loop | 0.6 in. w.c. for each airstream |
Evaporative humidifier/cooler in series with another cooling coil |
Pressure drop of device at fan system design condition |
Sound attenuation section | 0.15 in. w.c. |
Exhaust systems serving fume hoods | 0.35 in. w.c. |
Laboratory and vivarium exhaust systems in high-rise buildings |
0.25 in. w.c./100 ft of vertical duct exceeding 75 ft. |
Deductions | |
Systems without central cooling device | –0.6 in. w.c. |
Systems without central heating device | –0.3 in. w.c. |
Systems with central electric resistance heat | –0.2 in. w.c. |
Fan Power Adjustment | |
---|---|
Applicability | All fan systems qualifying for pressure drop adjustments as described above. |
Definition | Standard 90.1-2019 specifies a “pressure drop adjustment” for fan systems with requirements for filtration or other process requirements. |
Units | List |
Input Restrictions | Derived from other building descriptors |
Baseline Building |
Pressure drop adjustment is calculated separately for each applicable device. Credit for each device is specified in the section above. A = sum of zones (PD_sum ´ CFMd_baseline/4131) Where: PD = Each applicable pressure drop adjustment from the proposed design CFMd = The design airflow through each applicable device in cfm from the baseline building Note: In scenarios where the proposed and baseline building have varying zone to system assignment, the pressure drop credit ‘A’ shall be calculated for each thermal zone in the proposed building, using the design flow rates in the proposed building design. For multi-zone systems in the proposed building, the pressure drop adjustment will be split for each zone based on the zone to system airflow ratio. The pressure drop adjustment for the baseline building will then be calculated by adjusting the calculated PDA by the ratio of baseline building design airflow rate to proposed building design air flow rate for each zone. The baseline system pressure drop adjustment will be a sum of the individual pressure drop adjustments of the applicable zones. |
Supply Fan Ratio | |
---|---|
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust, or return fans |
Definition | The ratio of supply fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions. |
Units | Unitless fraction (0 to 1) |
Input Restrictions | As designed |
Baseline Building | Same as proposed |
Return Fan Ratio | |
---|---|
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust, or return fans |
Definition | The ratio of return fan brake horsepower in the proposed design to total fan system brake horsepower for the proposed design at design conditions |
Units | Unitless fraction (0 to 1) |
Input Restrictions | Derived from other building descriptors |
Baseline Building | Same as proposed |
Exhaust Fan Ratio | |
---|---|
Applicability | Systems that serve thermal blocks that have exhaust, fume hoods, kitchen exhaust, or return fans |
Definition |
The ratio of exhaust fan brake horsepower in the proposed design to total fan system brake hp for the proposed design at design conditions. Exhaust fans include toilet exhaust, kitchen hoods, and other miscellaneous exhaust. For fan systems with multiple exhaust fans, the exhaust fan ratios shall be calculated separately for each exhaust fan. |
Units | Unitless ratio |
Input Restrictions | Derived from other building descriptors. In the event that a common exhaust system serves thermal blocks that are served by different HVAC systems, the brake horsepower shall be divided in proportion to design cfm. |
Baseline Building | Same as proposed |
Supply Fans
Fan System Modeling Method | |
---|---|
Applicability | All fan systems |
Definition | Software commonly models fans in three ways. The simple method is for the user to enter the electric power per unit of flow (W/cfm). This method is commonly used for unitary equipment and other small fan systems. A more detailed method is to model the fan as a system whereby the static pressure, fan efficiency, and motor efficiency are specified at design conditions. A third method is to specify brake horsepower at design conditions instead of fan efficiency and static pressure. This is a variation of the second method whereby brake horsepower is specified in lieu of static pressure and fan efficiency. |
Units | List: Power-Per-Unit-Flow, Design Pressure Drop, or Brake Horsepower |
Input Restrictions | As designed |
Baseline Building | Systems 1, 2, 9, and 10 should use power per unit flow if allowed by the software. If not allowed used one of the other methods as described in Table 54. All other baseline system shall use the brake horsepower method. If that method is not available, static pressure method should be used. |
Supply Fan Design Air Rated Capacity | |
---|---|
Applicability | All fan systems |
Definition | The design airflow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed |
Baseline Building |
The software shall automatically size the system airflow to meet the baseline building loads based on · a supply-air-to-room-air temperature difference of 20°F, · or the minimum outdoor airflow rate, · or the airflow rate required to comply with the applicable codes or accreditation standards, whichever is greater. The baseline system airflow is determined by the load to be met by the airflow and the 20°F (11°C) temperature difference. The loads to be used would be the design load as determined by the sizing runs specified in Section G3.1.2.2, not the cooling or heating capacity of the system as determined using the sizing factors, also specified in G3.1.2.2. Using the system cooling and heating capacity will result in oversized baseline system airflows and energy cost because of the oversizing factors used in G3.1.2.2. See additional discussion in Section 3.5.5.1 for VAV systems. spaces with special process requirements.) The supply fan design airflow rate shall be the sum of the calculated design airflow for the thermal zones served by the fan system. For laboratory spaces, the design airflow rate calculation shall be based on a 17°F temperature differential rather than 20°F. For baseline systems 9 and 10, the design supply airflow rates shall be based on the temperature difference between a SAT setpoint of 105°F and the design space heating temperature setpoint, the minimum outdoor airflow rate or the airflow rate required to comply with applicable codes, whichever is greater. If the proposed design HVAC system airflow rate based on latent loads greater than the same based on sensible loads, then the same supply-air-to-room humidity ratio difference (gr/lb) used to calculate the proposed design airflow should be used to calculate the design airflow rates for the baseline building. |
Fan Control Method | |
---|---|
Applicability | All fan systems |
Definition |
A description of how the supply (and return/relief) fan(s) is controlled. The options include: · Constant volume · Variable-flow, inlet or discharge dampers · Variable-flow, inlet guide vanes · Variable-flow, variable speed drive (VSD) · Variable-flow, variable pitch blades · Variable-flow, other · Two-speed · Constant volume, cycling (fan cycles with heating and cooling) |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Building | Based on the baseline system type, summarized in Table 55 |
Table 55. Baseline Building Fan Control Method
System No. | System Type | Fan Control |
System 1 | Package terminal air conditioner | Constant volume |
System 2 | Packaged terminal heat pump | Constant volume |
System 3 | Packaged roof top air conditioner | Constant volume |
System 4 | Packaged roof top heat pump | Constant volume |
System 5 | Packaged rooftop VAV with reheat | Variable volume, variable speed drive (VSD) |
System 6 | Packaged rooftop VAV with PFP boxes and reheat | Variable volume, VSD |
System 7 | Packaged rooftop VAV with reheat | Variable volume, VS |
System 8 | VAV with parallel fan-powered boxes and reheat | Variable volume, VSD |
System 9 | Warm air furnace, gas fired | Constant volume |
System 10 | Warm air furnace, electric | Constant volume |
System 11 | Single zone VAV | Variable volume, VSD |
System 12 | Single zone system (CHW and HW boiler) | Constant volume |
System 13 | Single zone system (CHW and electric resistance) | Constant volume |
Supply Fan Brake Horsepower | |
---|---|
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the supply fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the static pressure and fan efficiency are not required. |
Baseline Building |
Fans for parallel fan-powered boxes are not included in fan power calculations. Table 53 of this document gives the baseline building fan system brake horsepower. The brake horsepower for the supply fan is this value times the supply fan ratio (see above). |
Supply Fan Static Pressure | |
---|---|
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H2O) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Building | The baseline building is defined by Table 53. This approach only works if the system has only a supply fan. If return/exhaust fans are also present in the system, then the supply fan bhp needs to be calculated and divided amongst the supply, return, and exhaust fans. |
Supply Fan Efficiency | |
---|---|
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
Definition | The efficiency of the fan at design conditions; this is the static efficiency and does not include motor losses |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Baseline Building | The baseline supply fan efficiency shall be 65%. |
Supply Motor Efficiency | |
---|---|
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Building | For systems 1, 2, 9, and 10, motor efficiency is assumed to be 80%. The motor efficiency for systems 3 through 8 is determined from Table G3.9.1 of ASHRAE Standard 90.1-2019 (Table 56 below). |
Table 56. Minimum Nominal Efficiency for Electric Motors (%)
Shaft Input Power | Full-Load Motor Efficiency, % |
1 |
82.5 |
1.5 | 84 |
2 | 84 |
3 | 87.5 |
5 | 87.5 |
7.5 | 89.5 |
10 | 89.5 |
15 | 91 |
20 | 91 |
25 | 92.4 |
30 | 92.4 |
40 | 93 |
50 | 93 |
60 | 93.6 |
75 | 94.1 |
100 | 94.5 |
125 | 94.5 |
150 | 95 |
200 | 95 |
Fan Position | |
---|---|
Applicability | All supply fans |
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Building | Draw through |
Motor Position | |
---|---|
Applicability | All supply fans |
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Building | In the air stream |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
Definition | A part-load power curve that represents the percentage full-load power draw of the supply fan as a function of the percentage full-load airflow. The curve is typically represented as a cubic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
The fan curve shall be selected from Equation (11) and Table 57 for the type of fan specified in the proposed design. ??????? ?? ???=?+?⋅????????+?⋅????????2+?⋅????????3 ???=???????? Where: PLR = Ratio of fan power at part load conditions to full load fan power PowerMin = Minimum fan power ratio FanRatio = Ratio of cfm at part-load to full-load cfm a, b, c and d = Constants from Table 57
Table 57. Fan Curve Default Values
Data Sources: (a) ECB Compliance Supplement, public review draft, Version 1.2, March 1996, but adjusted to be relatively consistent with the curve specified in the PRM. (b) The fan curve for VSD is specified in Table G3.1.3.15. (c) This is the good SP reset VSD fan curve from the advanced VAV design guide used for MZVAV systems. (d) This is the perfect SP reset VSD fan curve from the advanced VAV design guide used for SZVAV systems. http://www.energy.ca.gov/2003publications/CEC-500-2003-082/CEC-500-2003-082-A-11.PDF
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Building | Not applicable for baseline building systems 1 through 4. Baseline systems 5 through 8 will use the curve for “Multi zone VAV with fixed static pressure setpoint” curve. System 11 shall use the “Single zone VAV fan” curve. Constant volume fans are used for systems 9, 10, 12, and 13 and hence the descriptor is not applicable. |
Supply Fan Power Index (kW/cfm) | |
---|---|
Applicability | Fan systems that use the power-per-unit-flow method |
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As designed or specified in the manufacturers’ literature |
Baseline Building | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 53 of this document. This power is then multiplied by the supply fan ratio. |
Static Pressure Reset Controls | |
---|---|
Applicability | All VAV fan systems. Baseline systems 5 through 8. |
Definition | Static pressure reset controls, reset the fan static pressure for VAV systems-based zone damper position. For systems with DDC of individual zone boxes reporting to the central control panel, static pressure setpoint shall be reset based on the zone requiring the most pressure. |
Units | Unitless |
Input Restrictions | As designed. If static pressure reset is implemented in the proposed system, the curve for “Multi zone VAV with static pressure reset curve” shall be used. |
Baseline Building | Not applicable for baseline building systems 1 through 4 or 9, 10, 11, 12, and 13. The curve for “Multi Zone VAV with VSD and fixed SP setpoint”’ shall be used for baseline building systems 5 through 8. |
Return/ Relief Fans
System design supply airflow rates for the baseline building design shall be based on a supply-air-to room-air temperature difference of 20°F or the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is greater. For systems 3, 4, and 11 through 13, if return or relief fans are specified for systems serving the corresponding zones in the proposed design, the baseline building design shall also be modeled with fans serving the same functions. For systems 5 through 8, if return or relief fans are specified in the proposed building, then the baseline systems serving the corresponding zones will be modeled with a return/relief fan.
Plenum Zone | |
---|---|
Applicability | Any system with return ducts or return air plenum |
Definition | A reference to the thermal zone that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Baseline Building | Applicable when the baseline building has a return fan. Same as the proposed design when the proposed design has a plenum; otherwise, the return air ducts are assumed to be located in the space. |
Return Air Path | |
---|---|
Applicability | Any system with return ducts or return air plenum |
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Building | For baseline building systems 1 and 2, the return air path shall be direct-to-unit. For baseline building systems 3 through 8 and 11 through 13 and when the proposed design is direct-to-unit, the baseline building shall be ducted return, otherwise the baseline building return air path shall be the same as proposed design. |
Return/ Relief Air Rated Capacity | |
---|---|
Applicability | All systems with a return or relief fan |
Definition | The design airflow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Baseline Building | Applicable when the baseline building has a return fan. Return or relief fans shall be sized for the baseline system supply fan air quantity less the minimum outdoor air, or 90% of the supply fan air quantity, whichever is larger. |
Return/ Relief Fan Brake Horsepower | |
---|---|
Applicability | Any system with return or relief fans that uses the brake horsepower method |
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Building | Applicable when the baseline building has a return fan. The bhp of the return fan shall be the system fan brake horsepower multiplied by the return fan ratio. In other words, brake horsepower is allocated in proportion to the proposed design. |
Return/ Relief Design Static Pressure | |
---|---|
Applicability | Any system with return or relief fans that uses the static pressure method |
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H2O gauge) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Building | Return fan static pressure = (Return fan BHP ´ 6356 ´ 0.65)/cfm return |
Return/ Relief Fan Efficiency | |
---|---|
Applicability | Any system with return or relief fans that uses the static pressure method |
Definition | The efficiency of the fan at design conditions; this is the static efficiency and does not include the efficiency loss of the motor |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Building | 65% |
Return/ Relief Motor Efficiency | |
---|---|
Applicability | All return fans, except those specified using the power-per-unit-flow method |
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Baseline Building | For baseline systems 1, 2, 9, 10, 12, and 13 is 80%. For baseline systems 3 through 8 and 11, fan motor efficiency is determined from Table G3.9.1 of Standard 90.1-2019 for the next motor size greater than the bhp calculated, through the process described above, using a totally enclosed fan motor at 1800 rpm. |
Motor Position | |
---|---|
Applicability | All return fans |
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed |
Baseline Building | In the air stream |
Fan Part-Flow Power Curve | |
---|---|
Applicability | All return fans for variable flow fan systems |
Definition | A part-load power curve that represents the percentage full-load power draw of the return fan as a function of the percentage full-load airflow |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (11) and Table 57 for the type of fan specified in the proposed design. |
Baseline Building | Not applicable for baseline building systems 1 through 4. The curve for “Multi zone VAV with static pressure reset curve” shall be used for baseline building systems 5 through 8 and system 11. |
Return/ Relief Fan Power Index | |
---|---|
Applicability | Any system with a return fan |
Definition | The return fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Baseline Building | Applicable when the baseline building uses the power-per-unit-flow method. Fan power is determined using Table 53. This power is then multiplied by the return fan ratio. |
Exhaust Fan Systems
Exhaust fans include toilet, kitchen and laboratory exhaust. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal zone. An exhaust fan system may serve multiple thermal zones. The baseline building has exhaust fans when the proposed design has exhaust fans. The design exhaust airflow is the same for the baseline building and the proposed building.
Exhaust Fan Name | |
---|---|
Applicability | All exhaust systems serving multiple thermal zones |
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal zone level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans |
Baseline Building | The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Guide | |
---|---|
Applicability | All exhaust fan systems |
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: Power-Per-Unit-Flow, Static Pressure, or Brake Horsepower |
Input Restrictions | As designed |
Baseline Building | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the static pressure method |
Exhaust Fan Rated Capacity | |
---|---|
Applicability | All exhaust systems |
Definition | The rated design airflow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual airflow is the sum of the flow specified for each thermal zone, as modified by the schedule for each thermal zone. |
Units | cfm |
Input Restrictions | As designed |
Baseline Building | Same as the proposed design except that baseline building kitchen exhaust rate may not exceed the maximum levels defined by Section 3.5.5.3 of this document |
Fan Control Method | |
---|---|
Applicability | All exhaust fan systems |
Definition |
A description of how the exhaust fan(s) are controlled. The options include: · Constant volume · Two-speed · Variable-flow, inlet or discharge dampers · Variable-flow, inlet guide vanes · Variable-flow, VSD · Variable-flow, variable pitch blades |
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal zone level is varied through a schedule, one of the variable-flow options shall be specified |
Baseline Building | The baseline building exhaust fan control shall generally be the same as the proposed design. Exceptions: Exhaust fans s serving laboratory spaces shall reduce the exhaust air volume during unoccupied periods to the largest of 50% of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards as described in Section 3.5.5.3 under descriptor Laboratory: Exhaust Minimum Airflow Rate. |
Exhaust Fan Schedule | |
---|---|
Applicability | All exhaust fan systems |
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal zone level. |
Units | Data structure: schedule, on/off |
Input Restrictions | As designed |
Baseline Building | Same as the proposed design for exhaust fans not serving kitchen or laboratory spaces For kitchen and laboratory zone exhaust, refer to Section 3.5.5.3 of this document |
Exhaust Fan Brake Horsepower | |
---|---|
Applicability | All exhaust fan systems |
Definition | The design shaft brake horsepower of the exhaust fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Baseline Building | The bhp for the baseline building is the total system fan horsepower from Table 53 of this document multiplied by the exhaust fan ratio |
Exhaust Fan Design Static Pressure | |
---|---|
Applicability | Any system with return or relief fans that uses the static pressure method |
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H2O) |
Input Restrictions | As designed for exhaust fans not serving kitchens. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan bhp is specified. |
Baseline Building |
The exhaust fan static pressure for the baseline building would be equal to the total fan system static pressure (specified in section Supply Fan Static Pressure) multiplied by the exhaust fan ratio Exhaust Fan Static Pressure = (Exhaust Fan BHP ´ 6356 ´ 0.65)/cfm exhaust |
Exhaust Fan Efficiency | |
---|---|
Applicability | Any exhaust fan system that uses the static pressure method |
Definition | The efficiency of the exhaust fan at rated capacity; this is the static efficiency and does not include losses through the motor |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan bhp is specified. |
Baseline Building |
For baseline system, fan efficiency is 65% |
Exhaust Fan Motor Efficiency | |
---|---|
Applicability | All exhaust fan systems |
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Baseline Building |
From Table G3.9.1 of Standard 90.1-2019 for the next motor size greater than the bhp calculated, through the process described above, using a totally enclosed fan motor at 1800 rpm |
Fan Part-Flow Power Curve | |
---|---|
Applicability | All variable flow exhaust fan systems |
Definition | A part-load power curve that represents the power draw of the exhaust fan as a function of the airflow |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (11) and Table 57 for the type of fan specified in the proposed design. |
Baseline Building |
Same as proposed |
Exhaust Fan Power Index | |
---|---|
Applicability | All exhaust systems |
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | kW/cfm |
Input Restrictions | As designed |
Baseline Building |
The fan system power from Table 53 multiplied by the exhaust fan ratio |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules | The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. |
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
[table title="Fan Curve Default Values" id="fan-curve-default-values"]
|
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |
Supply Fans
Fan System Modeling Method | |
Applicability | All fan systems |
---|---|
Definition |
Software commonly models fans in three ways.
|
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed. The power-per-unit-flow method shall be used when no fan performance data is available for the proposed design cooling system, e.g. only EER or SEER are available. |
Baseline Rules | If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the brake horsepower method. |
Supply Fan Design Air Rated Capacity | |
Applicability | All fan systems |
---|---|
Definition | The design air flow rate of the supply fan(s) at design conditions. This building descriptor sets the 100% point for the fan part-load curve. |
Units | cfm |
Input Restrictions | As designed. This input should be at least as great as the sum of the design air flow specified for each of the thermal blocks that are served by the fan system. For multiple deck systems, a separate entry should be made for each deck. |
Baseline Rules | The program shall automatically size the air flow at each thermal block to meet the loads. The design air flow rate calculation shall be based on a 20 degree temperature differential between supply air and the room air. The supply fan design air flow rate shall be the sum of the calculated design air flow for the thermal blocks served by the fan system. |
Fan Control Method | |
Applicability | All fan systems |
---|---|
Definition | A description of how the supply (and return/relief) fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Supply Fan Brake Horsepower | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design shaft brake horsepower of the supply fan(s). This input does not need to be supplied if the Supply Fan kW is supplied. |
Units | Horsepower (hp) |
Input Restrictions | As designed. If this building descriptor is specified for the proposed design, then the Static Pressure and Fan Efficiency are not. |
Supply Fan Static Pressure | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The design static pressure for the supply fan. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the supply fan does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Supply Fan Efficiency | |
Applicability | All fan systems, except those specified using the power-per-unit-flow method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The supply fan efficiency does not need to be specified if the supply fan brake horsepower (bhp) is specified. |
Supply Motor Efficiency | |
Applicability | All supply fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Fan Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan relative to the cooling coil. The configuration is either draw through (fan is downstream of the coil) or blow through (fan is upstream of the coil). |
Units | List (see above) |
Input Restrictions | As designed. |
Motor Position | |
Applicability | All supply fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Fan Part-Flow Power Curve | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All variable flow fan systems | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. The curve is typically represented as a quadratic equation with an absolute minimum power draw specified. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Unitless ratio | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. (6.7.3-1) $Greater \;of$ $PLR = a + b \cdot FanRatio + c \cdot FanRatio^2 + d \cdot FanRatio^3$ $PLR = PowerMin $ where
[table title="Fan Curve Default Values" id="fan-curve-default-values"]
|
Supply Fan kW | |||||
Applicability | Fan systems that use the power-per-unit-flow method | ||||
---|---|---|---|---|---|
Definition | The supply fan power per unit of flow. | ||||
Units | kW/cfm | ||||
Input Restrictions |
As designed or specified in the manufacturers’ literature. For units with rated total cooling capacities less than 120,000 Btu/h, the user may default to a value calculated as follows: (6.7.3-2) $$ Fan_{kw} = 0.365 \times \frac{Q_{rated}}{30,000} $$ where
|
Relief Fans
The baseline building has a return fan when the baseline building system is type 3 through 8 and the proposed design has a return fan.
Plenum Zone | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | A reference to the thermal block that serves as return plenum or where the return ducts are located |
Units | Text, unique |
Input Restrictions | As designed |
Return Air Path | |
Applicability | Any system with return ducts or return air plenum |
---|---|
Definition | Describes the return path for air. This can be one of the following: ducted return; plenum return; or direct-to-unit. |
Units | List (see above) |
Input Restrictions | As designed |
Return/Relief Air Rated Capacity | |
Applicability | All systems with a return or relief fan |
---|---|
Definition | The design air flow fan capacity of the return or relief fan(s). This sets the 100% fan flow point for the part-load curve (see below). |
Units | cfm |
Input Restrictions | As designed |
Return/Relief Fan Brake Horsepower | |
Applicability | Any system with return or relief fans that uses the brake horsepower method |
---|---|
Definition | The design shaft brake horsepower of the return/relief fan(s) |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Return/Relief Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for return fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the return fan does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Return/Relief Fan Efficiency | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The efficiency of the fan at design conditions |
Units | Unitless |
Input Restrictions | As designed. The return/relief fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Return/Relief Motor Efficiency | |
Applicability | All return fans, except those specified using the power-per-unit-flow method |
---|---|
Definition | The full-load efficiency of the motor serving the supply fan |
Units | Unitless |
Input Restrictions | As designed. Not applicable when the power-per-unit-flow method is used. |
Motor Position | |
Applicability | All return fans |
---|---|
Definition | The position of the supply fan motor relative to the cooling air stream. The choices are: in the air stream or out of the air stream. |
Units | List (see above) |
Input Restrictions | As designed. |
Fan Part-Flow Power Curve | |
Applicability | All return fans for variable flow fan systems. |
---|---|
Definition | A part-load power curve which represents the percentage full-load power draw of the supply fan as a function of the percentage full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Return/Relief Fan kW | |
Applicability | Any system with a return fan |
---|---|
Definition | The supply fan power per unit of flow |
Units | kW/cfm |
Input Restrictions | As specified in the manufacturers’ literature |
Exhaust Fan Systems
Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks.
Exhaust Fan Name | |
Applicability | All exhaust systems serving multiple thermal blocks |
---|---|
Definition | A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units | Text, unique |
Input Restrictions | Where applicable, this should match the tags that are used on the plans. |
Exhaust Fan System Modeling Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | Software commonly models fans in three ways. See definition for supply system modeling method. |
Units | List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions | As designed |
Exhaust Fan Rated Capacity | |
Applicability | All exhaust systems |
---|---|
Definition | The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units | cfm |
Input Restrictions | As designed |
Fan Control Method | |
Applicability | All exhaust fan systems |
---|---|
Definition | A description of how the exhaust fan(s) are controlled. The options include:
|
Units | List (see above) |
Input Restrictions | As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Exhaust Fan Schedule | |
Applicability | All exhaust fan systems |
---|---|
Definition | A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units | Data structure: schedule, on/off |
Input Restrictions | The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Exhaust Fan Brake Horsepower | |
Applicability | All exhaust fan systems |
---|---|
Definition | The design shaft brake horsepower of the exhaust fan(s). |
Units | Brake horsepower (bhp) |
Input Restrictions | As designed |
Exhaust Fan Design Static Pressure | |
Applicability | Any system with return or relief fans that uses the static pressure method |
---|---|
Definition | The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units | Inches of water column (in. H20) |
Input Restrictions | As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Exhaust Fan Efficiency | |
Applicability | Any exhaust fan system that uses the static pressure method |
---|---|
Definition | The efficiency of the exhaust fan at rated capacity |
Units | Unitless |
Input Restrictions | As designed. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Exhaust Fan Motor Efficiency | |
Applicability | All exhaust fan systems |
---|---|
Definition | The full-load efficiency of the motor serving the exhaust fan |
Units | Unitless |
Input Restrictions | As designed |
Fan Part-Flow Power Curve | |
Applicability | All variable flow exhaust fan systems |
---|---|
Definition | A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units | Unitless ratio |
Input Restrictions | As designed. The default fan curve shall be selected from Equation (6.7.3-1) and [bookref id="fan-curve-default-values"] for the type of fan specified in the proposed design. |
Exhaust Fan KW | |
Applicability | All exhaust systems |
---|---|
Definition | The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units | W/cfm |
Input Restrictions | As designed. |