General
Heating Source | |
Applicability | All systems that provide heating |
---|---|
Definition | The source of heating for the heating and preheat coils. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Based on the prescribed system type. Refer to the HVAC System Map in [bookref id="hvac-mapping"]. |
[table title="Heating Source for Baseline Building" id="heating-source-for-baseline-building"]
Baseline Building System | Heating Source |
System 1 – PTAC | Gas Furnace |
System 2 – PTHP | Heat pump |
System 3 – PSZ-AC | Gas or Oil Furnace |
System 4 – PSZ-HP | Heat pump |
System 5 – Packaged VAV with Reheat | Hot water |
System 6 – Packaged VAV with PFP boxes | Electric Resistance |
System 7 – VAV with Reheat | Hot water |
System 8 – VAV with PFP boxes | Electric Resistance |
Preheat Coil
Preheat Coil Capacity | |
Applicability | Systems with a preheat coil located in the outside air stream |
---|---|
Definition | The heating capacity of a preheating coil at design conditions. |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | If the proposed design has a preheat coil and it can be modeled in the baseline building system, then the baseline building also has a preheat coil sized to meet the preheat coil temperature specified for the proposed design. Autosize to maintain the preheat coil temperature of the proposed design. |
Heating Coils
Systems with boilers have heating coils, including baseline building systems 1, 5 and 7.
Heating Coil Capacity | |
Applicability | All systems with a heating coil |
---|---|
Definition | The heating capacity of a heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Baseline Rules | Autosize with a heating oversizing factor of 25%. If the number of unmet load hours for the proposed design exceeds the number of unmet load hours for the baseline building by more than 50, reduce the heating coil capacity as indicated in [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. |
Furnace
Furnace Capacity | |
Applicability | Systems with a furnace |
---|---|
Definition | The full load heating capacity of the unit |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Baseline Rules | Autosize with an oversizing factor of 25% (let the software determine heating capacity based on the building loads). If the number of unmet load hours for the proposed design exceeds the number of unmet load hours for the baseline building by more than 50, reduce the furnace capacity as indicated in [bookref id="calculation-process-for-tax-deductions-and-green-building-ratings"] and [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. |
Furnace Fuel Heating Efficiency | |||||
Applicability | Systems with a furnace | ||||
---|---|---|---|---|---|
Definition | The full load thermal efficiency of either a gas or oil furnace at design conditions. The software must accommodate input in either Thermal Efficiency (Et) or Annual Fuel Utilization Efficiency (AFUE). Where AFUE is provided, Et shall be calculated as follows:
(6.7.6-1) $ 1) All\ Single\ Package\ Equipment$ where
|
||||
Units | Fraction | ||||
Input Restrictions | As designed | ||||
Baseline Rules | Look up the requirement from the equipment efficiency tables in Table 6.8.1E of Standard 90.1-2007 Table 6.2.1E of Standard 90.1-2001. Use the heating input of the proposed design system to determine the size category. |
Furnace Fuel Heating Part Load Efficiency Curve | |||||||||||||||||||
Applicability | Systems with furnaces | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | An adjustment factor that represents the percentage of full load fuel consumption as a function of the percentage full load capacity. This curve shall take the form of a quadratic equation as follows:
(6.7.6-2) $$ Fuel_{partload} = Fuel_{rated} \times F\!HeatP\!LC$$ (6.7.6-3) $$ F\!HeatP\!LC = \left ( a + b \times \frac{Q_{partload}}{Q_{rated}} + c \times \left( \frac{Q_{partload}}{Q_{rated}} \right )^2 \right )$$ where
[table title="Furnace Efficiency Curve Coefficients" id="furnace-efficiency-curve-coefficients"]
|
||||||||||||||||||
Units | Data structure | ||||||||||||||||||
Input Restrictions | As designed when data is available, otherwise use the default values are provided above. | ||||||||||||||||||
Baseline Rules | Use defaults |
Furnace Fuel Heating Pilot | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fuel input for a pilot light on a furnace |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Zero (pilotless ignition) |
Furnace Fuel Heating Fan/Auxiliary | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fan energy in forced draft furnaces and the auxiliary (pumps and outdoor fan) energy in fuel-fired heat pumps |
Units | Kilowatts (kW) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Electric Heat Pump
Electric Heat Pump Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The full load heating capacity of the unit, excluding supplemental heating capacity at ARI rated conditions |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Autosize and use an oversizing factor of 25% (let the software determine heating capacity based on the building loads). The autosized equipment may need to be downsized to achieve a maximum difference in unmet load hours between the proposed design and the baseline building of 50. |
Electric Heat Pump Supplemental Heating Source | |
Applicability | All heat pumps |
---|---|
Definition | The auxiliary heating source for a heat pump heating system. The common control sequence is to lock out the heat pump compressor when the supplemental heat is activated. Other building descriptors may be needed if this is not the case. Choices for supplemental heat include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Electric resistance |
Electric Heat Pump Heating Efficiency | |||||||||
Applicability | All heat pumps | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The heating efficiency of a heat pump at ARI rated conditions as a dimensionless ratio of output over input. The software must accommodate user input in terms of either the Coefficient of Performance (COP) or the Heating Season Performance Factor (HSPF). Where HSPF is provided, COP shall be calculated as follows: (6.7.6-4) $ 1) All\ Single\ Package\ Equipment$ For all unitary and applied equipment where the fan energy is part of the equipment efficiency rating, the COP shall be adjusted as follows to remove the fan energy: (6.7.6-5) $$ C\!O\!P_{adj} = \frac{\frac{H\!C\!A\!P_{rated}}{3.413} - B\!H\!P_{supply} \times 0.7457}{\frac{H\!C\!A\!P_{rated}}{C\!O\!P \times 3.413} - B\!H\!P_{supply} \times 0.7457}$$ where
Refer to building descriptor Supply Fan BHP. |
||||||||
Units | Unitless | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules | For the purpose of green building ratings, look up the requirement from the equipment efficiency Table 6.8.1B and Table 6.8.1D in ASHRAE Standard 90.1-2007. For the purpose of tax deduction calculations, find the equipment efficiency from Table 6.2.1B and 6.2.1D in ASHRAE Standard 90.1-2001. Use the heating capacity of the proposed design to determine the size category. |
Electric Heat Pump Heating Capacity Adjustment Curve(s) | ||||||||||||||||||||||||||
Applicability | All heat pumps | |||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that represent the available heat-pump heating capacity as a function of evaporator and condenser conditions. The default curves are given as follows: (6.7.6-6) $$ Q_{available} = C\!A\!P\_FT \times Q_{rated}$$For air-cooled heat pumps: (6.7.6-7) $$ C\!A\!P\_FT = a + b \times t_{odb} + c \times \left. t_{odb}\right. ^2 + d \times \left. t_{odb}\right. ^3 $$ For water-cooled heat pumps: (6.7.6-8) $$ C\!A\!P\_FT = a + b \times t_{db} + d \times t_{wt}$$ where
[table title="Heat Pump Capacity Adjustment Curves (CAP-FT)" id="heat-pump-capacity-adjustment-curves-(CAP-FT)"]
|
|||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation shall be provided. | |||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Electric Heat Pump Heating Efficiency Adjustment Curve(s) | |||||||||||||||||||||||||||||||||||||||||
Applicability | All heat pumps | ||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the heat-pump heating efficiency as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.7.6-9) $$ P\!LR = \frac{Q_{operating}}{Q_{available}\left ( t_{db},t_{odb/wt}\right )}$$ (6.7.6-10) $$ E\!I\!R\_F\!P\!LR = a + b \times P\!LR + c \times P\!LR^2 + d \times P\!LR^3 $$ Air Source Heat Pumps: (6.7.6-11) $$ E\!I\!R\_FT = a + b \times \left ( \frac{t_{odb}}{t_{db}} \right ) + c \times \left ( \frac{t_{odb}}{t_{db}} \right ) ^2 + d \times \left ( \frac{t_{odb}}{t_{db}} \right )^3$$Water Source Heat Pumps: (6.7.6-12) $$ E\!I\!R\_FT = a + b \times t_{wt} + d \times t_{db}$$ (6.7.6-13) $$ P_{operating} = P_{rated} \times E\!I\!R\_F\!P\!LR \times E\!I\!R\_FT \times C\!AP\_FT $$ where
[table title="Heat Pump Heating Efficiency Adjustment (Curves)" id="heat-pump-heating-efficiency-adjustment-curves"]
|
||||||||||||||||||||||||||||||||||||||||
Units | None | ||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, documentation shall be provided. | ||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves |
Electric Heat Pump Supplemental Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The design heating capacity of a heat pump supplemental heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Autosize |
Electric Supplemental Heating Control Temp | |
Applicability | All heat pumps |
---|---|
Definition | The outside dry-bulb temperature below which the heat pump supplemental heating is allowed to operate |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Default to 40°F |
Baseline Rules | 40°F |
Coil Defrost | |
Applicability | Air-cooled electric heat pump |
---|---|
Definition | The defrost control mechanism for an air-cooled heat pump. The choices are:
|
Units | List (see above) |
Input Restrictions | Default to use hot-gas defrost, timed 3.5 minute cycle. User may select any of the above. |
Baseline Rules | The baseline building uses the default. |
Coil Defrost kW | |
Applicability | Heat pumps with electric resistance defrost |
---|---|
Definition | The capacity of the electric resistance defrost heater |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Baseline Rules | Not applicable. Baseline building systems 2 and 4 use hot-gas, timed 3.5 minute cycle. |
Crank Case Heater kW | |
Applicability | All heat pumps |
---|---|
Definition | The capacity of the electric resistance heater in the crank case of a direct expansion (DX) compressor. The crank case heater operates only when the compressor is off. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Baseline Rules | Zero (0) |
Crank Case Heater Shutoff Temperature | |
Applicability | All heat pumps |
---|---|
Definition | The outdoor air dry-bulb temperature above which the crank case heater is not permitted to operate. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. This descriptor defaults to 50°F. |
Baseline Rules | 50°F |
Heat Recovery
Exhaust to Outside Heat Recovery Effectiveness | |||||||||
Applicability | Any system with outside air heat recovery | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The effectiveness of an air-to-air heat exchanger between the building exhaust and entering outside air streams. Effectiveness is defined as follows: (6.7.6-14) $$ H\!R\!E\!F\!F = \frac{\left ( E\!E\!A_{db} - E\!L\!A_{db}\right )}{\left ( E\!E\!A_{db} - O\!S\!A_{db}\right )}$$where
|
||||||||
Units | Ratio | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules | Required for fan systems with a design supply air flow rate of 5,000 cfm or greater if the minimum outside air quantity is 70% of the design air flow rate. If required, the energy recovery system should have at least 50% effectiveness. Energy recovery is not required for heating systems in climate zones 1 through 3 or for cooling systems in climate zones 3c, 4c, 5b, 5c, 6b, 7 and 8. |
Condenser Heat Recovery Effectiveness | |
Applicability | Systems that use recover heat from a condenser |
---|---|
Definition | The percentage of heat rejection at design conditions from a DX or heat pump unit in cooling mode that is available for space or water heating. |
Units | Percent (%) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
Baseline Rules | Not applicable for most conditions. Condenser heat recovery is required for 24-hour facilities when the heat rejection exceeds 6,000,000 Btu/h and the design service water heating load exceeds 1,000,000 Btu/h. When required, the effectiveness will be 60%. |
Heat Recovery Use | |
Applicability | Systems that use heat recovery |
---|---|
Definition | The end use of the heat recovered from a DX or heat pump unit. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
Baseline Rules | Not applicable for most conditions. The end use will be water heating if required for 24-hour facility operation. |
/3765-electric-heat-pumpGeneral
Heating Source | |
Applicability | All systems that provide heating |
---|---|
Definition | The source of heating for the heating and preheat coils. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Based on the prescribed system type. Refer to the HVAC System Map in [bookref id="hvac-mapping"]. |
[table title="Heating Source for Baseline Building" id="heating-source-for-baseline-building"]
Baseline Building System | Heating Source |
System 1 – PTAC | Gas Furnace |
System 2 – PTHP | Heat pump |
System 3 – PSZ-AC | Gas or Oil Furnace |
System 4 – PSZ-HP | Heat pump |
System 5 – Packaged VAV with Reheat | Hot water |
System 6 – Packaged VAV with PFP boxes | Electric Resistance |
System 7 – VAV with Reheat | Hot water |
System 8 – VAV with PFP boxes | Electric Resistance |
Preheat Coil
Preheat Coil Capacity | |
Applicability | Systems with a preheat coil located in the outside air stream |
---|---|
Definition | The heating capacity of a preheating coil at design conditions. |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | If the proposed design has a preheat coil and it can be modeled in the baseline building system, then the baseline building also has a preheat coil sized to meet the preheat coil temperature specified for the proposed design. Autosize to maintain the preheat coil temperature of the proposed design. |
Heating Coils
Systems with boilers have heating coils, including baseline building systems 1, 5 and 7.
Heating Coil Capacity | |
Applicability | All systems with a heating coil |
---|---|
Definition | The heating capacity of a heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Baseline Rules | Autosize with a heating oversizing factor of 25%. If the number of unmet load hours for the proposed design exceeds the number of unmet load hours for the baseline building by more than 50, reduce the heating coil capacity as indicated in [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. |
Furnace
Furnace Capacity | |
Applicability | Systems with a furnace |
---|---|
Definition | The full load heating capacity of the unit |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Baseline Rules | Autosize with an oversizing factor of 25% (let the software determine heating capacity based on the building loads). If the number of unmet load hours for the proposed design exceeds the number of unmet load hours for the baseline building by more than 50, reduce the furnace capacity as indicated in [bookref id="calculation-process-for-tax-deductions-and-green-building-ratings"] and [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. |
Furnace Fuel Heating Efficiency | |||||
Applicability | Systems with a furnace | ||||
---|---|---|---|---|---|
Definition | The full load thermal efficiency of either a gas or oil furnace at design conditions. The software must accommodate input in either Thermal Efficiency (Et) or Annual Fuel Utilization Efficiency (AFUE). Where AFUE is provided, Et shall be calculated as follows:
(6.7.6-1) $ 1) All\ Single\ Package\ Equipment$ where
|
||||
Units | Fraction | ||||
Input Restrictions | As designed | ||||
Baseline Rules | Look up the requirement from the equipment efficiency tables in Table 6.8.1E of Standard 90.1-2007. Use the heating input of the proposed design system to determine the size category. |
Furnace Fuel Heating Part Load Efficiency Curve | |||||||||||||||||||
Applicability | Systems with furnaces | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | An adjustment factor that represents the percentage of full load fuel consumption as a function of the percentage full load capacity. This curve shall take the form of a quadratic equation as follows:
(6.7.6-2) $$ Fuel_{partload} = Fuel_{rated} \times F\!HeatP\!LC$$ (6.7.6-3) $$ F\!HeatP\!LC = \left ( a + b \times \frac{Q_{partload}}{Q_{rated}} + c \times \left( \frac{Q_{partload}}{Q_{rated}} \right )^2 \right )$$ where
[table title="Furnace Efficiency Curve Coefficients" id="furnace-efficiency-curve-coefficients"]
|
||||||||||||||||||
Units | Data structure | ||||||||||||||||||
Input Restrictions | As designed when data is available, otherwise use the default values are provided above. | ||||||||||||||||||
Baseline Rules | Use defaults |
Furnace Fuel Heating Pilot | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fuel input for a pilot light on a furnace |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Zero (pilotless ignition) |
Furnace Fuel Heating Fan/Auxiliary | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fan energy in forced draft furnaces and the auxiliary (pumps and outdoor fan) energy in fuel-fired heat pumps |
Units | Kilowatts (kW) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Electric Heat Pump
Electric Heat Pump Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The full load heating capacity of the unit, excluding supplemental heating capacity at ARI rated conditions |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Autosize and use an oversizing factor of 25% (let the software determine heating capacity based on the building loads). The autosized equipment may need to be downsized to achieve a maximum difference in unmet load hours between the proposed design and the baseline building of 50. |
Electric Heat Pump Supplemental Heating Source | |
Applicability | All heat pumps |
---|---|
Definition | The auxiliary heating source for a heat pump heating system. The common control sequence is to lock out the heat pump compressor when the supplemental heat is activated. Other building descriptors may be needed if this is not the case. Choices for supplemental heat include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Electric resistance |
Electric Heat Pump Heating Efficiency | |||||||||
Applicability | All heat pumps | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The heating efficiency of a heat pump at ARI rated conditions as a dimensionless ratio of output over input. The software must accommodate user input in terms of either the Coefficient of Performance (COP) or the Heating Season Performance Factor (HSPF). Where HSPF is provided, COP shall be calculated as follows: (6.7.6-4) $ 1) All\ Single\ Package\ Equipment$ For all unitary and applied equipment where the fan energy is part of the equipment efficiency rating, the COP shall be adjusted as follows to remove the fan energy: (6.7.6-5) $$ C\!O\!P_{adj} = \frac{\frac{H\!C\!A\!P_{rated}}{3.413} - B\!H\!P_{supply} \times 0.7457}{\frac{H\!C\!A\!P_{rated}}{C\!O\!P \times 3.413} - B\!H\!P_{supply} \times 0.7457}$$ where
Refer to building descriptor Supply Fan BHP. |
||||||||
Units | Unitless | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules | For the purpose of green building ratings, look up the requirement from the equipment efficiency Table 6.8.1B and Table 6.8.1D in ASHRAE Standard 90.1-2007. Use the heating capacity of the proposed design to determine the size category. |
Electric Heat Pump Heating Capacity Adjustment Curve(s) | ||||||||||||||||||||||||||
Applicability | All heat pumps | |||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that represent the available heat-pump heating capacity as a function of evaporator and condenser conditions. The default curves are given as follows: (6.7.6-6) $$ Q_{available} = C\!A\!P\_FT \times Q_{rated}$$For air-cooled heat pumps: (6.7.6-7) $$ C\!A\!P\_FT = a + b \times t_{odb} + c \times \left. t_{odb}\right. ^2 + d \times \left. t_{odb}\right. ^3 $$ For water-cooled heat pumps: (6.7.6-8) $$ C\!A\!P\_FT = a + b \times t_{db} + d \times t_{wt}$$ where
[table title="Heat Pump Capacity Adjustment Curves (CAP-FT)" id="heat-pump-capacity-adjustment-curves-(CAP-FT)"]
|
|||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation shall be provided. | |||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Electric Heat Pump Heating Efficiency Adjustment Curve(s) | |||||||||||||||||||||||||||||||||||||||||
Applicability | All heat pumps | ||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the heat-pump heating efficiency as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.7.6-9) $$ P\!LR = \frac{Q_{operating}}{Q_{available}\left ( t_{db},t_{odb/wt}\right )}$$ (6.7.6-10) $$ E\!I\!R\_F\!P\!LR = a + b \times P\!LR + c \times P\!LR^2 + d \times P\!LR^3 $$ Air Source Heat Pumps: (6.7.6-11) $$ E\!I\!R\_FT = a + b \times \left ( \frac{t_{odb}}{t_{db}} \right ) + c \times \left ( \frac{t_{odb}}{t_{db}} \right ) ^2 + d \times \left ( \frac{t_{odb}}{t_{db}} \right )^3$$Water Source Heat Pumps: (6.7.6-12) $$ E\!I\!R\_FT = a + b \times t_{wt} + d \times t_{db}$$ (6.7.6-13) $$ P_{operating} = P_{rated} \times E\!I\!R\_F\!P\!LR \times E\!I\!R\_FT \times C\!AP\_FT $$ where
[table title="Heat Pump Heating Efficiency Adjustment (Curves)" id="heat-pump-heating-efficiency-adjustment-curves"]
|
||||||||||||||||||||||||||||||||||||||||
Units | None | ||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, documentation shall be provided. | ||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves |
Electric Heat Pump Supplemental Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The design heating capacity of a heat pump supplemental heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Autosize |
Electric Supplemental Heating Control Temp | |
Applicability | All heat pumps |
---|---|
Definition | The outside dry-bulb temperature below which the heat pump supplemental heating is allowed to operate |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Default to 40°F |
Baseline Rules | 40°F |
Coil Defrost | |
Applicability | Air-cooled electric heat pump |
---|---|
Definition | The defrost control mechanism for an air-cooled heat pump. The choices are:
|
Units | List (see above) |
Input Restrictions | Default to use hot-gas defrost, timed 3.5 minute cycle. User may select any of the above. |
Baseline Rules | The baseline building uses the default. |
Coil Defrost kW | |
Applicability | Heat pumps with electric resistance defrost |
---|---|
Definition | The capacity of the electric resistance defrost heater |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Baseline Rules | Not applicable. Baseline building systems 2 and 4 use hot-gas, timed 3.5 minute cycle. |
Crank Case Heater kW | |
Applicability | All heat pumps |
---|---|
Definition | The capacity of the electric resistance heater in the crank case of a direct expansion (DX) compressor. The crank case heater operates only when the compressor is off. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Baseline Rules | Zero (0) |
Crank Case Heater Shutoff Temperature | |
Applicability | All heat pumps |
---|---|
Definition | The outdoor air dry-bulb temperature above which the crank case heater is not permitted to operate. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. This descriptor defaults to 50°F. |
Baseline Rules | 50°F |
Heat Recovery
Exhaust to Outside Heat Recovery Effectiveness | |||||||||
Applicability | Any system with outside air heat recovery | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The effectiveness of an air-to-air heat exchanger between the building exhaust and entering outside air streams. Effectiveness is defined as follows: (6.7.6-14) $$ H\!R\!E\!F\!F = \frac{\left ( E\!E\!A_{db} - E\!L\!A_{db}\right )}{\left ( E\!E\!A_{db} - O\!S\!A_{db}\right )}$$where
|
||||||||
Units | Ratio | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules | Required for fan systems with a design supply air flow rate of 5,000 cfm or greater if the minimum outside air quantity is 70% of the design air flow rate. If required, the energy recovery system should have at least 50% effectiveness. Energy recovery is not required for heating systems in climate zones 1 through 3 or for cooling systems in climate zones 3c, 4c, 5b, 5c, 6b, 7 and 8. |
Condenser Heat Recovery Effectiveness | |
Applicability | Systems that use recover heat from a condenser |
---|---|
Definition | The percentage of heat rejection at design conditions from a DX or heat pump unit in cooling mode that is available for space or water heating. |
Units | Percent (%) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
Baseline Rules | Not applicable for most conditions. Condenser heat recovery is required for 24-hour facilities when the heat rejection exceeds 6,000,000 Btu/h and the design service water heating load exceeds 1,000,000 Btu/h. When required, the effectiveness will be 60%. |
Heat Recovery Use | |
Applicability | Systems that use heat recovery |
---|---|
Definition | The end use of the heat recovered from a DX or heat pump unit. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
Baseline Rules | Not applicable for most conditions. The end use will be water heating if required for 24-hour facility operation. |
General
Heating Source | |
Applicability | All systems that provide heating |
---|---|
Definition | The source of heating for the heating and preheat coils. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Based on the prescribed system type. Refer to the HVAC System Map in Figure 6.1.2-1. |
Table 6.7.6-1: Heating Source for Baseline Building
Baseline Building System | Heating Source |
System 1 – PTAC | Gas Furnace |
System 2 – PTHP | Heat pump |
System 3 – PSZ-AC | Gas or Oil Furnace |
System 4 – PSZ-HP | Heat pump |
System 5 – Packaged VAV with Reheat | Hot water |
System 6 – Packaged VAV with PFP boxes | Electric Resistance |
System 7 – VAV with Reheat | Hot water |
System 8 – VAV with PFP boxes | Electric Resistance |
System 9 – Heating and Ventilation | Electric Resistance |
System 10 – Heating and Ventilation | Gas Furnace |
Preheat Coil
Preheat Coil Capacity | |
Applicability | Systems with a preheat coil located in the outside air stream |
---|---|
Definition | The heating capacity of a preheating coil at design conditions. |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | If the proposed design has a preheat coil and it can be modeled in the baseline building system, then the baseline building also has a preheat coil sized to meet the preheat coil temperature specified for the proposed design. Autosize to maintain the preheat coil temperature of the proposed design. |
Heating Coils
Systems with boilers have heating coils, including baseline building systems 1, 5 and 7.
Heating Coil Capacity | |
Applicability | All systems with a heating coil |
---|---|
Definition | The heating capacity of a heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Baseline Rules | Autosize with a heating oversizing factor of 25%. |
Furnace
Furnace Capacity | |
Applicability | Systems with a furnace |
---|---|
Definition | The full load heating capacity of the unit |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Baseline Rules | Autosize with an oversizing factor of 25% (let the software determine heating capacity based on the building loads). |
Furnace Fuel Heating Efficiency | |||||
Applicability | Systems with a furnace | ||||
---|---|---|---|---|---|
Definition | The full load thermal efficiency of either a gas or oil furnace at design conditions. The software must accommodate input in either Thermal Efficiency (Et) or Annual Fuel Utilization Efficiency (AFUE). Where AFUE is provided, Et shall be calculated as follows:
(6.7.6-1) $ 1) All\ Single\ Package\ Equipment$ where
|
||||
Units | Fraction | ||||
Input Restrictions | As designed | ||||
Baseline Rules | Look up the requirement from the equipment efficiency tables in Table 6.8.1E of Standard 90.1-2007. Use the heating input of the proposed design system to determine the size category. |
Furnace Fuel Heating Part Load Efficiency Curve | |||||||||||||||||||
Applicability | Systems with furnaces | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | An adjustment factor that represents the percentage of full load fuel consumption as a function of the percentage full load capacity. This curve shall take the form of a quadratic equation as follows:
(6.7.6-2) $$ Fuel_{partload} = Fuel_{rated} \times F\!HeatP\!LC$$ (6.7.6-3) $$ F\!HeatP\!LC = \left ( a + b \times \frac{Q_{partload}}{Q_{rated}} + c \times \left( \frac{Q_{partload}}{Q_{rated}} \right )^2 \right )$$ where
Table 6.7.6-2: Furnace Efficiency Curve Coefficients
|
||||||||||||||||||
Units | Data structure | ||||||||||||||||||
Input Restrictions | As designed when data is available, otherwise use the default values are provided above. | ||||||||||||||||||
Baseline Rules | Use defaults |
Furnace Fuel Heating Pilot | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fuel input for a pilot light on a furnace |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Zero (pilotless ignition) |
Furnace Fuel Heating Fan/Auxiliary | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fan energy in forced draft furnaces and the auxiliary (pumps and outdoor fan) energy in fuel-fired heat pumps |
Units | Kilowatts (kW) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Electric Heat Pump
Electric Heat Pump Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The full load heating capacity of the unit, excluding supplemental heating capacity at ARI rated conditions |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Autosize and use an oversizing factor of 25% (let the software determine heating capacity based on the building loads). The autosized equipment may need to be downsized to achieve a maximum difference in unmet load hours between the proposed design and the baseline building of 50. |
Electric Heat Pump Supplemental Heating Source | |
Applicability | All heat pumps |
---|---|
Definition | The auxiliary heating source for a heat pump heating system. The common control sequence is to lock out the heat pump compressor when the supplemental heat is activated. Other building descriptors may be needed if this is not the case. Choices for supplemental heat include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Electric resistance |
Electric Heat Pump Heating Efficiency | |||||||||
Applicability | All heat pumps | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The heating efficiency of a heat pump at ARI rated conditions as a dimensionless ratio of output over input. The software must accommodate user input in terms of either the Coefficient of Performance (COP) or the Heating Season Performance Factor (HSPF). Where HSPF is provided, COP shall be calculated as follows: (6.7.6-4) $ 1) All\ Single\ Package\ Equipment$ For all unitary and applied equipment where the fan energy is part of the equipment efficiency rating, the COP shall be adjusted as follows to remove the fan energy: (6.7.6-5) $$ C\!O\!P_{adj} = \frac{\frac{H\!C\!A\!P_{rated}}{3.413} - B\!H\!P_{supply} \times 0.7457}{\frac{H\!C\!A\!P_{rated}}{C\!O\!P \times 3.413} - B\!H\!P_{supply} \times 0.7457}$$ where
Refer to building descriptor Supply Fan BHP. |
||||||||
Units | Unitless | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules | For the purpose of green building ratings, look up the requirement from the equipment efficiency Table 6.8.1B and Table 6.8.1D in ASHRAE Standard 90.1-2007. Use the heating capacity of the proposed design to determine the size category. |
Electric Heat Pump Heating Capacity Adjustment Curve(s) | ||||||||||||||||||||||||||
Applicability | All heat pumps | |||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that represent the available heat-pump heating capacity as a function of evaporator and condenser conditions. The default curves are given as follows: (6.7.6-6) $$ Q_{available} = C\!A\!P\_FT \times Q_{rated}$$For air-cooled heat pumps: (6.7.6-7) $$ C\!A\!P\_FT = a + b \times t_{odb} + c \times \left. t_{odb}\right. ^2 + d \times \left. t_{odb}\right. ^3 $$ For water-cooled heat pumps: (6.7.6-8) $$ C\!A\!P\_FT = a + b \times t_{db} + d \times t_{wt}$$ where
Table 6.7.6-3: Heat Pump Capacity Adjustment Curves (CAP-FT)
|
|||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation shall be provided. | |||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Electric Heat Pump Heating Efficiency Adjustment Curve(s) | |||||||||||||||||||||||||||||||||||||||||
Applicability | All heat pumps | ||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the heat-pump heating efficiency as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.7.6-9) $$ P\!LR = \frac{Q_{operating}}{Q_{available}\left ( t_{db},t_{odb/wt}\right )}$$ (6.7.6-10) $$ E\!I\!R\_F\!P\!LR = a + b \times P\!LR + c \times P\!LR^2 + d \times P\!LR^3 $$ Air Source Heat Pumps: (6.7.6-11) $$ E\!I\!R\_FT = a + b \times \left ( \frac{t_{odb}}{t_{db}} \right ) + c \times \left ( \frac{t_{odb}}{t_{db}} \right ) ^2 + d \times \left ( \frac{t_{odb}}{t_{db}} \right )^3$$Water Source Heat Pumps: (6.7.6-12) $$ E\!I\!R\_FT = a + b \times t_{wt} + d \times t_{db}$$ (6.7.6-13) $$ P_{operating} = P_{rated} \times E\!I\!R\_F\!P\!LR \times E\!I\!R\_FT \times C\!AP\_FT $$ where
Table 6.7.6-4: Heat Pump Heating Efficiency Adjustment (Curves)
|
||||||||||||||||||||||||||||||||||||||||
Units | None | ||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, documentation shall be provided. | ||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves |
Electric Heat Pump Supplemental Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The design heating capacity of a heat pump supplemental heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed |
Baseline Rules | Autosize |
Electric Supplemental Heating Control Temp | |
Applicability | All heat pumps |
---|---|
Definition | The outside dry-bulb temperature below which the heat pump supplemental heating is allowed to operate |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Default to 40°F |
Baseline Rules | 40°F |
Coil Defrost | |
Applicability | Air-cooled electric heat pump |
---|---|
Definition | The defrost control mechanism for an air-cooled heat pump. The choices are:
|
Units | List (see above) |
Input Restrictions | Default to use hot-gas defrost, timed 3.5 minute cycle. User may select any of the above. |
Baseline Rules | The baseline building uses the default. |
Coil Defrost kW | |
Applicability | Heat pumps with electric resistance defrost |
---|---|
Definition | The capacity of the electric resistance defrost heater |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Baseline Rules | Not applicable. Baseline building systems 2 and 4 use hot-gas, timed 3.5 minute cycle. |
Crank Case Heater kW | |
Applicability | All heat pumps |
---|---|
Definition | The capacity of the electric resistance heater in the crank case of a direct expansion (DX) compressor. The crank case heater operates only when the compressor is off. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Baseline Rules | Zero (0) |
Crank Case Heater Shutoff Temperature | |
Applicability | All heat pumps |
---|---|
Definition | The outdoor air dry-bulb temperature above which the crank case heater is not permitted to operate. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. This descriptor defaults to 50°F. |
Baseline Rules | 50°F |
Heat Recovery
Exhaust to Outside Heat Recovery Effectiveness | |||||||||
Applicability | Any system with outside air heat recovery | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The effectiveness of an air-to-air heat exchanger between the building exhaust and entering outside air streams. Effectiveness is defined as follows: (6.7.6-14) $$ H\!R\!E\!F\!F = \frac{\left ( E\!E\!A_{db} - E\!L\!A_{db}\right )}{\left ( E\!E\!A_{db} - O\!S\!A_{db}\right )}$$where
|
||||||||
Units | Ratio | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules | Required for fan systems with a design supply air flow rate of 5,000 cfm or greater if the minimum outside air quantity is 70% of the design air flow rate. If required, the energy recovery system should have at least 50% effectiveness. Energy recovery is not required for heating systems in climate zones 1 through 3 or for cooling systems in climate zones 3c, 4c, 5b, 5c, 6b, 7 and 8. |
Condenser Heat Recovery Effectiveness | |
Applicability | Systems that use recover heat from a condenser |
---|---|
Definition | The percentage of heat rejection at design conditions from a DX or heat pump unit in cooling mode that is available for space or water heating. |
Units | Percent (%) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
Baseline Rules | Not applicable for most conditions. Condenser heat recovery is required for 24-hour facilities when the heat rejection exceeds 6,000,000 Btu/h and the design service water heating load exceeds 1,000,000 Btu/h. When required, the effectiveness will be 60%. |
Heat Recovery Use | |
Applicability | Systems that use heat recovery |
---|---|
Definition | The end use of the heat recovered from a DX or heat pump unit. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
Baseline Rules | Not applicable for most conditions. The end use will be water heating if required for 24-hour facility operation. |
This section addresses:
- 3.7.6.1 General
- 3.7.6.2 Preheat Coil
- 3.7.6.3 Hydronic/Steam Heating Coils
- 3.7.6.4 Furnace
- 3.7.6.5 Electric Heat Pump
- 3.7.6.6 Heat Recovery
General
Heating Source | |
Applicability | All systems that provide heating |
---|---|
Definition | The source of heating for the heating and preheat coils. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Preheat Coil
Preheat Coil Capacity | |
Applicability | Systems with a preheat coil located in the outside air stream |
---|---|
Definition | The heating capacity of a preheating coil at design conditions. |
Units | Btu/h |
Input Restrictions | As designed |
Heating Coils
Heating Coil Capacity | |
Applicability | All systems with a heating coil |
---|---|
Definition | The heating capacity of a heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Furnace
Furnace Capacity | |
Applicability | Systems with a furnace |
---|---|
Definition | The full load heating capacity of the unit |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Furnace Fuel Heating Efficiency | |||||
Applicability | Systems with a furnace | ||||
---|---|---|---|---|---|
Definition | The full load thermal efficiency of either a gas or oil furnace at design conditions. The software must accommodate input in either Thermal Efficiency (Et) or Annual Fuel Utilization Efficiency (AFUE). Where AFUE is provided, Et shall be calculated as follows:
(6.7.6-1) $ 1) All\ Single\ Package\ Equipment$ where
|
||||
Units | Fraction | ||||
Input Restrictions | As designed |
Furnace Fuel Heating Part Load Efficiency Curve | |||||||||||||||||||
Applicability | Systems with furnaces | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | An adjustment factor that represents the percentage of full load fuel consumption as a function of the percentage full load capacity. This curve shall take the form of a quadratic equation as follows:
(6.7.6-2) $$ Fuel_{partload} = Fuel_{rated} \times F\!HeatP\!LC$$ (6.7.6-3) $$ F\!HeatP\!LC = \left ( a + b \times \frac{Q_{partload}}{Q_{rated}} + c \times \left( \frac{Q_{partload}}{Q_{rated}} \right )^2 \right )$$ where
[table title="Furnace Efficiency Curve Coefficients" id="furnace-efficiency-curve-coefficients"]
|
||||||||||||||||||
Units | Data structure | ||||||||||||||||||
Input Restrictions | As designed when data is available, otherwise use the default values are provided above. |
Furnace Fuel Heating Pilot | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fuel input for a pilot light on a furnace |
Units | Btu/h |
Input Restrictions | As designed |
Furnace Fuel Heating Fan/Auxiliary | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fan energy in forced draft furnaces and the auxiliary (pumps and outdoor fan) energy in fuel-fired heat pumps |
Units | Kilowatts (kW) |
Input Restrictions | As designed |
Electric Heat Pump
Electric Heat Pump Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The full load heating capacity of the unit, excluding supplemental heating capacity at ARI rated conditions |
Units | Btu/h |
Input Restrictions | As designed |
Electric Heat Pump Supplemental Heating Source | |
Applicability | All heat pumps |
---|---|
Definition | The auxiliary heating source for a heat pump heating system. The common control sequence is to lock out the heat pump compressor when the supplemental heat is activated. Other building descriptors may be needed if this is not the case. Choices for supplemental heat include:
|
Units | List (see above) |
Input Restrictions | As designed |
Electric Heat Pump Heating Efficiency | |||||||||
Applicability | All heat pumps | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The heating efficiency of a heat pump at ARI rated conditions as a dimensionless ratio of output over input. The software must accommodate user input in terms of either the Coefficient of Performance (COP) or the Heating Season Performance Factor (HSPF). Where HSPF is provided, COP shall be calculated as follows: (6.7.6-4) $ 1) All\ Single\ Package\ Equipment$ For all unitary and applied equipment where the fan energy is part of the equipment efficiency rating, the COP shall be adjusted as follows to remove the fan energy: (6.7.6-5) $$ C\!O\!P_{adj} = \frac{\frac{H\!C\!A\!P_{rated}}{3.413} - B\!H\!P_{supply} \times 0.7457}{\frac{H\!C\!A\!P_{rated}}{C\!O\!P \times 3.413} - B\!H\!P_{supply} \times 0.7457}$$ where
Refer to building descriptor Supply Fan BHP. |
||||||||
Units | Unitless | ||||||||
Input Restrictions | As designed |
Electric Heat Pump Heating Capacity Adjustment Curve(s) | ||||||||||||||||||||||||||
Applicability | All heat pumps | |||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that represent the available heat-pump heating capacity as a function of evaporator and condenser conditions. The default curves are given as follows: (6.7.6-6) $$ Q_{available} = C\!A\!P\_FT \times Q_{rated}$$For air-cooled heat pumps: (6.7.6-7) $$ C\!A\!P\_FT = a + b \times t_{odb} + c \times \left. t_{odb}\right. ^2 + d \times \left. t_{odb}\right. ^3 $$ For water-cooled heat pumps: (6.7.6-8) $$ C\!A\!P\_FT = a + b \times t_{db} + d \times t_{wt}$$ where
[table title="Heat Pump Capacity Adjustment Curves (CAP-FT)" id="heat-pump-capacity-adjustment-curves-(CAP-FT)"]
|
|||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation shall be provided. |
Electric Heat Pump Heating Efficiency Adjustment Curve(s) | |||||||||||||||||||||||||||||||||||||||||
Applicability | All heat pumps | ||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the heat-pump heating efficiency as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.7.6-9) $$ P\!LR = \frac{Q_{operating}}{Q_{available}\left ( t_{db},t_{odb/wt}\right )}$$ (6.7.6-10) $$ E\!I\!R\_F\!P\!LR = a + b \times P\!LR + c \times P\!LR^2 + d \times P\!LR^3 $$ Air Source Heat Pumps: (6.7.6-11) $$ E\!I\!R\_FT = a + b \times \left ( \frac{t_{odb}}{t_{db}} \right ) + c \times \left ( \frac{t_{odb}}{t_{db}} \right ) ^2 + d \times \left ( \frac{t_{odb}}{t_{db}} \right )^3$$Water Source Heat Pumps: (6.7.6-12) $$ E\!I\!R\_FT = a + b \times t_{wt} + d \times t_{db}$$ (6.7.6-13) $$ P_{operating} = P_{rated} \times E\!I\!R\_F\!P\!LR \times E\!I\!R\_FT \times C\!AP\_FT $$ where
[table title="Heat Pump Heating Efficiency Adjustment (Curves)" id="heat-pump-heating-efficiency-adjustment-curves"]
|
||||||||||||||||||||||||||||||||||||||||
Units | None | ||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, documentation shall be provided. |
Electric Heat Pump Supplemental Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The design heating capacity of a heat pump supplemental heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed |
Electric Supplemental Heating Control Temp | |
Applicability | All heat pumps |
---|---|
Definition | The outside dry-bulb temperature below which the heat pump supplemental heating is allowed to operate |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Default to 40°F |
Coil Defrost | |
Applicability | Air-cooled electric heat pump |
---|---|
Definition | The defrost control mechanism for an air-cooled heat pump. The choices are:
|
Units | List (see above) |
Input Restrictions | Default to use hot-gas defrost, timed 3.5 minute cycle. User may select any of the above. |
Coil Defrost kW | |
Applicability | Heat pumps with electric resistance defrost |
---|---|
Definition | The capacity of the electric resistance defrost heater |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Crank Case Heater kW | |
Applicability | All heat pumps |
---|---|
Definition | The capacity of the electric resistance heater in the crank case of a direct expansion (DX) compressor. The crank case heater operates only when the compressor is off. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Crank Case Heater Shutoff Temperature | |
Applicability | All heat pumps |
---|---|
Definition | The outdoor air dry-bulb temperature above which the crank case heater is not permitted to operate. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. This descriptor defaults to 50°F. |
Heat Recovery
Exhaust to Outside Heat Recovery Effectiveness | |||||||||
Applicability | Any system with outside air heat recovery | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The effectiveness of an air-to-air heat exchanger between the building exhaust and entering outside air streams. Effectiveness is defined as follows: (6.7.6-14) $$ H\!R\!E\!F\!F = \frac{\left ( E\!E\!A_{db} - E\!L\!A_{db}\right )}{\left ( E\!E\!A_{db} - O\!S\!A_{db}\right )}$$where
|
||||||||
Units | Ratio | ||||||||
Input Restrictions | As designed |
Condenser Heat Recovery Effectiveness | |
Applicability | Systems that use recover heat from a condenser |
---|---|
Definition | The percentage of heat rejection at design conditions from a DX or heat pump unit in cooling mode that is available for space or water heating. |
Units | Percent (%) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
Heat Recovery Use | |
Applicability | Systems that use heat recovery |
---|---|
Definition | The end use of the heat recovered from a DX or heat pump unit. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
General
Heating Source | |
Applicability | All systems that provide heating |
---|---|
Definition | The source of heating for the heating and preheat coils. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Preheat Coil
Preheat Coil Capacity | |
Applicability | Systems with a preheat coil located in the outside air stream |
---|---|
Definition | The heating capacity of a preheating coil at design conditions. |
Units | Btu/h |
Input Restrictions | As designed |
Heating Coils
Heating Coil Capacity | |
Applicability | All systems with a heating coil |
---|---|
Definition | The heating capacity of a heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Furnace
Furnace Capacity | |
Applicability | Systems with a furnace |
---|---|
Definition | The full load heating capacity of the unit |
Units | Btu/h |
Input Restrictions | As designed. Adjust the capacity if the number of unmet load hours exceeds 300. |
Furnace Fuel Heating Efficiency | |||||
Applicability | Systems with a furnace | ||||
---|---|---|---|---|---|
Definition | The full load thermal efficiency of either a gas or oil furnace at design conditions. The software must accommodate input in either Thermal Efficiency (Et) or Annual Fuel Utilization Efficiency (AFUE). Where AFUE is provided, Et shall be calculated as follows:
(6.7.6-1) $ 1) All\ Single\ Package\ Equipment$ where
|
||||
Units | Fraction | ||||
Input Restrictions | As designed |
Furnace Fuel Heating Part Load Efficiency Curve | |||||||||||||||||||
Applicability | Systems with furnaces | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition | An adjustment factor that represents the percentage of full load fuel consumption as a function of the percentage full load capacity. This curve shall take the form of a quadratic equation as follows:
(6.7.6-2) $$ Fuel_{partload} = Fuel_{rated} \times F\!HeatP\!LC$$ (6.7.6-3) $$ F\!HeatP\!LC = \left ( a + b \times \frac{Q_{partload}}{Q_{rated}} + c \times \left( \frac{Q_{partload}}{Q_{rated}} \right )^2 \right )$$ where
[table title="Furnace Efficiency Curve Coefficients" id="furnace-efficiency-curve-coefficients"]
|
||||||||||||||||||
Units | Data structure | ||||||||||||||||||
Input Restrictions | As designed when data is available, otherwise use the default values are provided above. |
Furnace Fuel Heating Pilot | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fuel input for a pilot light on a furnace |
Units | Btu/h |
Input Restrictions | As designed |
Furnace Fuel Heating Fan/Auxiliary | |
Applicability | Systems that use a furnace for heating |
---|---|
Definition | The fan energy in forced draft furnaces and the auxiliary (pumps and outdoor fan) energy in fuel-fired heat pumps |
Units | Kilowatts (kW) |
Input Restrictions | As designed |
Electric Heat Pump
Electric Heat Pump Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The full load heating capacity of the unit, excluding supplemental heating capacity at ARI rated conditions |
Units | Btu/h |
Input Restrictions | As designed |
Electric Heat Pump Supplemental Heating Source | |
Applicability | All heat pumps |
---|---|
Definition | The auxiliary heating source for a heat pump heating system. The common control sequence is to lock out the heat pump compressor when the supplemental heat is activated. Other building descriptors may be needed if this is not the case. Choices for supplemental heat include:
|
Units | List (see above) |
Input Restrictions | As designed |
Electric Heat Pump Heating Efficiency | |||||||||
Applicability | All heat pumps | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The heating efficiency of a heat pump at ARI rated conditions as a dimensionless ratio of output over input. The software must accommodate user input in terms of either the Coefficient of Performance (COP) or the Heating Season Performance Factor (HSPF). Where HSPF is provided, COP shall be calculated as follows: (6.7.6-4) $ 1) All\ Single\ Package\ Equipment$ For all unitary and applied equipment where the fan energy is part of the equipment efficiency rating, the COP shall be adjusted as follows to remove the fan energy: (6.7.6-5) $$ C\!O\!P_{adj} = \frac{\frac{H\!C\!A\!P_{rated}}{3.413} - B\!H\!P_{supply} \times 0.7457}{\frac{H\!C\!A\!P_{rated}}{C\!O\!P \times 3.413} - B\!H\!P_{supply} \times 0.7457}$$ where
Refer to building descriptor Supply Fan BHP. |
||||||||
Units | Unitless | ||||||||
Input Restrictions | As designed |
Electric Heat Pump Heating Capacity Adjustment Curve(s) | ||||||||||||||||||||||||||
Applicability | All heat pumps | |||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that represent the available heat-pump heating capacity as a function of evaporator and condenser conditions. The default curves are given as follows: (6.7.6-6) $$ Q_{available} = C\!A\!P\_FT \times Q_{rated}$$For air-cooled heat pumps: (6.7.6-7) $$ C\!A\!P\_FT = a + b \times t_{odb} + c \times \left. t_{odb}\right. ^2 + d \times \left. t_{odb}\right. ^3 $$ For water-cooled heat pumps: (6.7.6-8) $$ C\!A\!P\_FT = a + b \times t_{db} + d \times t_{wt}$$ where
[table title="Heat Pump Capacity Adjustment Curves (CAP-FT)" id="heat-pump-capacity-adjustment-curves-(CAP-FT)"]
|
|||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation shall be provided. |
Electric Heat Pump Heating Efficiency Adjustment Curve(s) | |||||||||||||||||||||||||||||||||||||||||
Applicability | All heat pumps | ||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the heat-pump heating efficiency as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.7.6-9) $$ P\!LR = \frac{Q_{operating}}{Q_{available}\left ( t_{db},t_{odb/wt}\right )}$$ (6.7.6-10) $$ E\!I\!R\_F\!P\!LR = a + b \times P\!LR + c \times P\!LR^2 + d \times P\!LR^3 $$ Air Source Heat Pumps: (6.7.6-11) $$ E\!I\!R\_FT = a + b \times \left ( \frac{t_{odb}}{t_{db}} \right ) + c \times \left ( \frac{t_{odb}}{t_{db}} \right ) ^2 + d \times \left ( \frac{t_{odb}}{t_{db}} \right )^3$$Water Source Heat Pumps: (6.7.6-12) $$ E\!I\!R\_FT = a + b \times t_{wt} + d \times t_{db}$$ (6.7.6-13) $$ P_{operating} = P_{rated} \times E\!I\!R\_F\!P\!LR \times E\!I\!R\_FT \times C\!AP\_FT $$ where
[table title="Heat Pump Heating Efficiency Adjustment (Curves)" id="heat-pump-heating-efficiency-adjustment-curves"]
|
||||||||||||||||||||||||||||||||||||||||
Units | None | ||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, documentation shall be provided. |
Electric Heat Pump Supplemental Heating Capacity | |
Applicability | All heat pumps |
---|---|
Definition | The design heating capacity of a heat pump supplemental heating coil at ARI conditions |
Units | Btu/h |
Input Restrictions | As designed |
Electric Supplemental Heating Control Temp | |
Applicability | All heat pumps |
---|---|
Definition | The outside dry-bulb temperature below which the heat pump supplemental heating is allowed to operate |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. Default to 40°F |
Coil Defrost | |
Applicability | Air-cooled electric heat pump |
---|---|
Definition | The defrost control mechanism for an air-cooled heat pump. The choices are:
|
Units | List (see above) |
Input Restrictions | Default to use hot-gas defrost, timed 3.5 minute cycle. User may select any of the above. |
Coil Defrost kW | |
Applicability | Heat pumps with electric resistance defrost |
---|---|
Definition | The capacity of the electric resistance defrost heater |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Crank Case Heater kW | |
Applicability | All heat pumps |
---|---|
Definition | The capacity of the electric resistance heater in the crank case of a direct expansion (DX) compressor. The crank case heater operates only when the compressor is off. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. This descriptor defaults to 0 if nothing is entered. |
Crank Case Heater Shutoff Temperature | |
Applicability | All heat pumps |
---|---|
Definition | The outdoor air dry-bulb temperature above which the crank case heater is not permitted to operate. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. This descriptor defaults to 50°F. |
Heat Recovery
Exhaust to Outside Heat Recovery Effectiveness | |||||||||
Applicability | Any system with outside air heat recovery | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition |
The effectiveness of an air-to-air heat exchanger between the building exhaust and entering outside air streams. Effectiveness is defined as follows: (6.7.6-14) $$ H\!R\!E\!F\!F = \frac{\left ( E\!E\!A_{db} - E\!L\!A_{db}\right )}{\left ( E\!E\!A_{db} - O\!S\!A_{db}\right )}$$where
|
||||||||
Units | Ratio | ||||||||
Input Restrictions | As designed |
Condenser Heat Recovery Effectiveness | |
Applicability | Systems that use recover heat from a condenser |
---|---|
Definition | The percentage of heat rejection at design conditions from a DX or heat pump unit in cooling mode that is available for space or water heating. |
Units | Percent (%) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
Heat Recovery Use | |
Applicability | Systems that use heat recovery |
---|---|
Definition | The end use of the heat recovered from a DX or heat pump unit. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |