3.7.6.1 General

90.1-2016 BM

Heating Source

Applicability

All systems that provide heating

Definition

The source of heating for the heating and preheat coils. The choices are:

  • Hot water
  • Steam
  • Electric resistance
  • Electric heat pump
  • Gas furnace
  • Gas heat pump (optional feature)
  • Oil furnace
  • Heat recovery (for preheat coils in proposed designs)

Units

List (see above)

Input Restrictions

As designed

Baseline Rules

Based on the prescribed system type. See Table 3.1.2-3

90.1-2019

Heating Source

Applicability

All systems that provide heating

Definition

The source of heating for the heating and preheat coils. The choices are:

  • Hot water
  • Steam
  • Electric resistance
  • Electric heat pump
  • Gas furnace
  • Gas heat pump
  • Oil furnace
  • Heat recovery

Units

List (see above)

Input Restrictions

As designed

Baseline Building

Based on the prescribed system type

Table 73. Heating Source for Baseline Building

Baseline Building System

Heating Type

1 – PTAC

Hot water fossil fuel boiler

2 – PTHP

Electric heat pump

3 – PSZ AC

Fossil fuel furnace

4 – PSZ HP

Electric heat pump

5 – PVAV reheat

Hot water fossil fuel boiler

6 – Packaged VAV with PFP Boxes

Electric resistance

7 – VAV with Reheat

Hot water fossil fuel boiler

8 – VAV with PFP Boxes

Electric resistance

9– Heating and Ventilation

Fossil fuel furnace

10 – Heating and Ventilation

Electric Resistance

11- Single Zone VAV

 

For climate zones 0-3A, the heating system will be electric resistance. All other will be hot-water fossil fuel boilers.

12- Single Zone CAV HW

Hot water fossil fuel boiler

13- Single Zone CAV ER

Electric resistance

 

 

Total Heating Coil Capacity

Applicability

All systems with heating coils

Definition

The heating capacity of a heating coil at ARI conditions

Units

Btu/h

Input Restrictions

As designed. The capacity would need to be adjusted if the number of UMLH exceeds 300.

Baseline Building

Autosize with a heating oversizing factor of 25%. Sizing calculations shall be based on the heating design day and cooling design day conditions, as defined in Section 3.2.3 of this document. Oversizing would be carried out at zone level where the sizing parameters would be applied to the zone design heating loads, but not the airflow rates. Refer to Section 2.7.2 of this document for more details.

 

Number of Heating Stages

Applicability

Heating systems with multiple stages

Definition

The number of heating stages provided by the system. Multiple stages could be provided via a heat pump or via a multiple-stage gas furnace.

Units

Integer

Input Restrictions

As designed

Baseline Building

Single stage

 

Heating Capacity by Stage

Applicability

Heating systems with multiple stages

Definition

Provides the total heating capacity of each heating stage, at ARI rated conditions. The capacity is expressed as an array, with each entry a fraction of the total rated cooling capacity for the unit. For example, if the stage heating capacity is 48,000 Btu/h and the heating capacity is 96,000 Btu/h, the capacity is expressed as “0.5” for that stage.

Units

Array of fractions

Input Restrictions

As designed

Baseline Building

Not applicable