Heating Source |
|
---|---|
Applicability |
All systems that provide heating |
Definition |
The source of heating for the heating and preheat coils. The choices are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
Based on the prescribed system type. See Table 3.1.2-3 |
Heating Source |
|||||||||||||||||||||||||||||
Applicability |
All systems that provide heating |
||||||||||||||||||||||||||||
Definition |
The source of heating for the heating and preheat coils. The choices are:
|
||||||||||||||||||||||||||||
Units |
List (see above) |
||||||||||||||||||||||||||||
Input Restrictions |
As designed |
||||||||||||||||||||||||||||
Baseline Building |
Based on the prescribed system type Table 73. Heating Source for Baseline Building
|
Total Heating Coil Capacity |
|
Applicability |
All systems with heating coils |
Definition |
The heating capacity of a heating coil at ARI conditions |
Units |
Btu/h |
Input Restrictions |
As designed. The capacity would need to be adjusted if the number of UMLH exceeds 300. |
Baseline Building |
Autosize with a heating oversizing factor of 25%. Sizing calculations shall be based on the heating design day and cooling design day conditions, as defined in Section 3.2.3 of this document. Oversizing would be carried out at zone level where the sizing parameters would be applied to the zone design heating loads, but not the airflow rates. Refer to Section 2.7.2 of this document for more details. |
Number of Heating Stages |
|
Applicability |
Heating systems with multiple stages |
Definition |
The number of heating stages provided by the system. Multiple stages could be provided via a heat pump or via a multiple-stage gas furnace. |
Units |
Integer |
Input Restrictions |
As designed |
Baseline Building |
Single stage |
Heating Capacity by Stage |
|
Applicability |
Heating systems with multiple stages |
Definition |
Provides the total heating capacity of each heating stage, at ARI rated conditions. The capacity is expressed as an array, with each entry a fraction of the total rated cooling capacity for the unit. For example, if the stage heating capacity is 48,000 Btu/h and the heating capacity is 96,000 Btu/h, the capacity is expressed as “0.5” for that stage. |
Units |
Array of fractions |
Input Restrictions |
As designed |
Baseline Building |
Not applicable |