Baseline Fan System Summary

90.1-2016 BM

The baseline building fan system is summarized in this section. See Table 3.1-1 for the HVAC baseline building system mapping.

Total baseline building fan system power for the baseline building fan systems is given in Table 3.7.3-1. In this table, "cfms" is the supply fan air flow at peak design conditions. This is calculated for the baseline building with the sizing procedure described in Figure 2.4-1. This brake horsepower includes the supply fan, the return fan, and exhaust fans. Exhaust fans include kitchen hoods, toilets, fume hoods, and other miscellaneous fans that operate at design conditions.

Table 3.7.3-1: Building Descriptor Applicability for Fan Systems

Inputs

Supply Fan

Return/Relief Fan

Exhaust Fans (Hoods)

Modeling Method

Yes

Same as supply

Yes

Air Rated Capacity

Yes

Yes

Yes

Plenum Zone

Not applicable

Yes

Not applicable

Return Air Path

Not applicable

Yes

Yes

Fan Control Method

Yes

Same as supply

Yes

Brake Horsepower (bhp)

Yes

Yes

Yes

Static Pressure

Yes

Yes

Yes

Fan Efficiency

Yes

Yes

Yes

Fan Motor Efficiency (hm)

Yes

Yes

Yes

Fan Position

Yes

Not applicable

Not applicable

Motor Position

Yes

Yes

Not applicable

Part-LoadFan Power Curve(W)

Yes

Yes

Yes

Fan KW

Yes

Yes

Yes

 

Table 3.7.3-2: Baseline Building Fan System Details

Baseline System Type

Baseline Break Horsepower

Baseline System Fan Power

Baseline Motor Efficiency

1 PTAC

n. a.

P = 0.3 x CFMs

n. a.

2 PTHP

3 PSZ-AC

bhp = CFMs Í 0.00094 + A

P = (bhp x 746) / hm

See Table 3.7.3-4

4 PSZ-HP

5 PVAV

bhp = CFMs Í 0.0013 + A

6 PVAV / PFP

7 VAV

8 VAV / PFP

9 HV Furnace

n. a.

P = 0.3 x CFMs  OR
P = 0.054 x CFMnmc

n. a.

10 HV Electric

11 SZ-VAV

bhp = CFMs Í 0.00062 + A

P = (bhp x 746) / hm

See Table 3.7.3-4

12 SZ-CV-HW

bhp = CFMs Í 0.00094 + A

13 SZ-CV-ER

P           Total baseline fan power to be distributed among the supply, relief, and exhaust fans in the same proportion as the proposed design.

bhp       The baseline building break horsepower (applicable to systems 3-8  and 11-13).

A           A break horsepower adder due to special conditions. See Table 3.7.3-3.

CFMs    The air volume in cubic feet per minute delivered by the supply fan.

CFMnmc The air volume in cubic feet per minute delivered by the supply fan for non-mechanical cooling systems (applicable to systems 9 and 10).

hm              The baseline system fan motor efficiency taken from Table 3.7.3-4.

 


Table 3.7.3-3: Baseline Building: Fan Power Limitation Static Pressure Adjustment

Source: Table 6.5.3.1-2 of Standard 90.1-2016

 

Device

Adjustment (A)

Credits

Fully ducted return and/or exhaust air systems

0.5 in. w.c. (2.15 in. w.c. for laboratory and vivarium systems)

Return and/or exhaust airflow control devices

0.5 in. w.c.

Exhaust filters, scrubbers, or other exhaust treatment

The pressure drop of device calculated at fan system design condition

Particulate Filtration Credit: MERV 9 through 12

0.5 in. w.c.

Particulate Filtration Credit: MERV 13 through 15

0.9 in. w.c.

Particulate Filtration Credit: MERV 16 and greater and electronically enhanced filters

Pressure drop calculated at 2× clean filter pressure drop at fan system design condition

Carbon and other gas-phase air cleaners

Clean filter pressure drop at fan system design condition

Biosafety Cabinet

Pressure drop of device at fan system design condition

Energy Recovery Device and other Coil Runaround Loop

(2.2 × Energy Recovery Effectiveness) - 0.5 in w.c. for each airstream

Coil Runaround Loop

0.6 in. w.c. for each airstream

Evaporative humidifier/cooler in series with another cooling coil

Pressure drop of device at fan system design condition

Sound Attenuation Section

0.15 in. w.c.

Exhaust Systems serving fume hoods

0.35 in. w.c.

Laboratory and Vivarium exhaust systems in high-rise buildings

0.25 in. wc./100 ft. of vertical duct exceeding 75 ft.

Deductions  

Systems without central cooling device

-0.6 in. w.c.

Systems without central heating device

-0.3 in. w.c.

Systems without central electric resistance heat

-0.2 in. w.c.