3.8.6 Thermal Storage

There are multiple ways to model thermal storage in the proposed design. The baseline building does not have thermal storage.

90.1-2019

There are multiple ways to model thermal storage in the proposed design. The baseline building does not have thermal storage.

Storage Type  
Applicability All thermal storage systems
Definition A type of thermal energy storage (TES) that indicates the storage medium
Units List
Input Restrictions Ice, chilled water
Baseline Building No thermal storage systems

 

Configuration  
Applicability All thermal storage systems
Definition Indication of how the TES is configured and operated in relation to the chilled water cooling
Units List
Input Restrictions

Series, chiller upstream

Series, chiller downstream

Parallel

Baseline Building No thermal storage systems

 

Ice Storage Type  
Applicability All thermal storage systems with storage type = ice
Definition Indication of the storage type for ice storage
Units List, with Options for Internal Melt, External Melt
Input Restrictions Ad designed
Baseline Building No thermal storage systems

 

Storage Capacity  
Applicability All thermal storage systems using ice storage
Definition Nominal storage capacity of the tank
Units Ton-hrs
Input Restrictions None
Baseline Building No thermal storage systems

 

Tank Volume   
Applicability All thermal storage systems using ice storage
Definition Nominal storage capacity of the tank
Units ft3
Input Restrictions None
Baseline Building No thermal storage systems

 

CHW Setpoint Schedule   
Applicability All thermal storage systems using ice storage
Definition Nominal storage capacity of the tank
Units Series, °F
Input Restrictions None
Baseline Building

No thermal storage systems

 

Deadband Temperature Difference   
Applicability All thermal storage systems using chilled water
Definition The deadband temperature difference between enabling and disabling use of the TES system for cooling
Units °F
Input Restrictions None
Baseline Building

No thermal storage systems

 

Maximum Temperature Limit  
Applicability All thermal storage systems using chilled water
Definition The minimum allowed temperature of the tank, below which charging of the tank cannot occur
Units °F
Input Restrictions None
Baseline Building

No thermal storage systems

 

Storage Tank Location Indicator   
Applicability All thermal storage systems using ice storage
Definition Nominal storage capacity of the tank
Units List
Input Restrictions

Schedule, zone, or exterior

If schedule, the ambient temperature schedule must be specified. If zone, the zone name must be specified.

Baseline Building

No thermal storage systems

 

Storage Tank Heat Gain Coefficient   
Applicability All thermal storage systems using chilled water
Definition The heat transfer coefficient between the tank and the ambient surroundings
Units Btu/h-°F
Input Restrictions

None

Baseline Building

No thermal storage systems

 

Use Side Heat Transfer Effectiveness  
Applicability All thermal storage systems using chilled water
Definition The heat transfer effectiveness between the use side water and the tank water
Units None
Input Restrictions

Between 0 and 1

Baseline Building

No thermal storage systems

 

Use Side Design Flow Rate  
Applicability All thermal storage systems using chilled water
Definition Design flow rate through the use side of the storage tank
Units gpm
Input Restrictions

None

Baseline Building

No thermal storage systems

 

Source Side Heat Transfer Effectiveness  
Applicability All thermal storage systems using chilled water
Definition The heat transfer effectiveness between the source side water and the tank water
Units None
Input Restrictions

Between 0 and 1

Baseline Building

No thermal storage systems

 

Source Side Design Flow Rate   
Applicability All thermal storage systems using chilled water
Definition Design flow rate through the source side of the storage tank
Units gpm
Input Restrictions

None

Baseline Building

No thermal storage systems

 

Tank Recovery Time  
Applicability All thermal storage systems using ice storage
Definition This is the time in hours for the tank to cool from 58°F to 48°F. This input is only used if the source side design flow rate is not specified.
Units Hours
Input Restrictions

None

Baseline Building

No thermal storage systems