Preheat Setpoint |
|
---|---|
Applicability |
Systems with a preheat coil located in the outside air stream |
Definition |
The control temperature leaving the preheat coil |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Rules |
Not applicable |
Heating Supply Air Temperature |
|
---|---|
Applicability |
All systems |
Definition |
The supply air temperature leaving the air handler when the system is in a heating mode (not the air temperature leaving the reheat coils in VAV boxes) |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Rules |
20 °F above space temperature setpoint for systems 1-4. Same as maximum reset cooling supply air temperature for systems 5-8 and 105 °F for systems 9 and 10. |
Heating Supply Air Temperature Control |
|
---|---|
Applicability |
Systems with the capability to vary heating SAT |
Definition |
The method of controlling heating SAT. Choices are:
|
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Rules |
Fixed (constant) |
Heating Reset Schedule by OSA |
|
---|---|
Applicability |
Systems that reset the heating SAT by outside dry-bulb temperature (this typically applies to dual-duct systems or to single zone systems with hydronic heating coils) |
Definition |
A linear reset schedule that represents the heating supply air temperature or hot deck supply air temperature (for dual duct systems) as a function of outdoor air dry-bulb temperature. This schedule is defined by the following data points (see below):
Figure 3.7.2-2: Example of SAT heating setpoint reset based on outdoor air temperature (OAT) |
Units |
Data structure (°F) |
Input Restrictions |
As designed |
Baseline Rules |
Not applicable |
This section addresses building descriptors related to heating and preheating control. Section 3.7.6 addresses all other details related to heating systems.
Preheat Setpoint |
|
---|---|
Applicability |
Systems 5 though 8 |
Definition |
The control temperature leaving the preheat coil |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Building |
The baseline will be modeled with preheat coil in the mixed air stream controlled to a fixed setpoint 20°F less than the design room heating temperature setpoint |
Heating Supply Air Temperature |
|
---|---|
Applicability |
All systems |
Definition |
The SAT leaving the air handler when the system is in design heating mode (not the air temperature leaving the reheat coils in VAV boxes) |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Building |
20°F above zone temperature setpoint for systems 1 through 4 and 12 through 13. Same as maximum reset cooling SAT for systems 5 through 8 and 105°F for systems 9 and 10. For baseline system 11, the heating supply air temperature shall be modulated to maintain space temperature and fan volume shall be fixed at minimum airflow. |
Heating Supply Air Temperature Controls |
|
---|---|
Applicability |
Systems with the capability to vary heating SAT setpoint |
Definition |
The method of controlling heating SAT. Choices are:
|
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Building |
No control is specified for heating SAT for systems 1 through 4, 9, 10, and 11 through 13. For systems 5 through 8, the heating SAT is fixed to the maximum reset cooling SAT. |