The baseline system shall be modeled with a preheat coil controlled to a fixed setpoint 20°F less than the design room heating temperature setpoint.
Preheat Coil Capacity |
|
---|---|
Applicability |
Systems with a preheat coil located in the outside air stream |
Definition |
The heating capacity of a preheating coil at design conditions. |
Units |
Btu/h |
Input Restrictions |
As designed |
Baseline Rules |
For baseline systems 5 through 8, the baseline system shall be modeled with a preheat coil controlled to a fixed setpoint of 20 °F less than the design room heating setpoint. See G3.1.3.19. |
Preheat Coil Type |
|
---|---|
Applicability |
Systems with a preheat coil located in the outside air stream |
Definition |
The heating source of a preheating coil. The choices are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
The heating source for the baseline preheat coil shall be the same as the baseline system. For baseline systems, 5 and 7, the preheat coils will be hydronic. Buildings with baseline system 6 and 8 will be modeled with electric resistance preheat coils. |
Preheat Coil Efficiency |
|
---|---|
Applicability |
Systems with a gas preheat coil |
Definition |
The heating efficiency of a preheating coil at design conditions |
Units |
Unitless |
Input Restrictions |
As designed, default is 80% |
Baseline Rules |
Not applicable. Baseline building would have preheat coils only for systems 5-8 which would either be electric resistance or hydronic. |
For systems 5 through 8, the baseline will be modeled with preheat coil in the mixed air stream controlled to a fixed setpoint 20°F less than the design zone heating temperature setpoint
Preheat Coil Capacity |
|
Applicability |
Proposed buildings with preheat coils and baseline systems 5 through 8 |
Definition |
The heating capacity of a preheating coil at design conditions |
Units |
Btu/h |
Input Restrictions |
As designed |
Baseline Building |
For baseline systems 5 through 8, the baseline will be modeled with preheat coil controlled to a fixed setpoint 20°F less than the design zone heating temperature setpoint. If there are multiple zone heating setpoints, the preheat setpoint will be determined by the zone with the highest heating temperature setpoint. The preheat coil capacity will be oversized by 25%. Sizing calculations shall be based on the heating design day and cooling design day conditions, as defined in Section 3.2.3 of this document. Oversizing would be carried out at zone level where the sizing parameters would be applied to the zone design’s heating coil loads. |
Preheat Coil Type |
|
Applicability |
Baseline systems 5 through 8 |
Definition |
The heating source of a preheating coil. The preheat coil could be electric resistance, gas fired, or a hydronic heating coil. |
Units |
List: Electric Resistance, Gas Fired, Hydronic |
Input Restrictions |
As designed |
Baseline Building |
The heating source for baseline systems 5 and 7 will be hydronic. Buildings with baseline systems 6 and 8 will be modeled with electric resistance preheat coils. |
Preheat Coil Efficiency |
|
Applicability |
Systems with a preheat coil with gas heating |
Definition |
The heating efficiency of a preheating coil at design conditions |
Units |
Percentage |
Input Restrictions |
As designed |
Baseline Building |
Not applicable. Baseline building would have preheat coils only for systems 5 through 8 that would either be electric resistance or hydronic. |