The HVAC system in the baseline building depends on the primary building activity, the number of floors, conditioned floor area and climate zone. Details about these systems are provided in subsequent sections.
For many of the building descriptors there is a one-to-one relationship between the proposed design and the baseline building; for example, every wall in the proposed design has a corresponding wall in the baseline building. However, for HVAC systems, this one-to-one relationship generally does not hold. There may be the different number of HVAC systems serving the proposed design compared to the baseline building, and equipment such as cooling towers, circulation pumps, etc. may be present in the baseline but not proposed design.
The HVAC system in the baseline building shall be selected from Table 3, HVAC System Map, and be based on building type, number of floors, conditioned floor area, and climate zone. The selected system shall conform to the descriptions in Table 4, HVAC System Descriptions.
For systems 1, 2, 3, 4, 9, 10, 11, 12, and 13, each thermal zone shall be modeled with its own HVAC system. For systems 5, 6, 7, and 8, each floor shall be modeled with a separate HVAC system. Floors with identical thermal zones can be grouped for modeling purposes.
Table 3. HVAC System Map
Building Type |
Size |
Baseline Building System Type |
|
Cool Climates |
Warm Climates |
||
Residential |
Any size |
System 1 PTAC |
System 2 PTHP |
Public Assembly |
< 120,000 ft² |
System 3 PSZ-AC |
System 4 PSZ-HP |
≥ 120,000 ft² |
System 12 SZ-CV-HW |
System 13 SZ-CV-ER |
|
Retail |
Low rise |
System 3 PSZ-AC |
System 4 PSZ-HP |
Other than |
Use “Other Nonresidential” |
||
Hospital |
Not more than 5 floors and not >150,000 ft2 |
System 5 PVAV with Reheat |
System 5 PVAV with Reheat |
more than 5 floors or >150,000 ft2 |
System 7 VAV with Reheat |
System 7 VAV with Reheat |
|
Heated-only Storage |
|
System 9- Heating and Ventilation |
System 10- Heating and Ventilation |
Other Nonresidential |
Small, 3 floors or less and <25,000 ft2 |
System 3 PSZ-AC |
System 4 PSZ-HP |
Medium, 4 or 5 floors and <25,000 ft2 or 5 floors or less and 25,000 ft2 to 150,000 ft2 |
System 5 PVAV with Reheat |
System 6 PVAV with PFP boxes |
|
Large, more than 5 floors or >150,000 ft2 |
7 VAV with Reheat |
8 VAV with PFP boxes |
Building Type Descriptions for Baseline System Definition:
- Residential
Residential buildings They include, but are not limited to, dwelling units, hotel/motel guest rooms, dormitories, nursing homes, patient rooms in hospitals, lodging houses, fraternity/ sorority houses, hostels, prisons, and fire stations.
- Public Assembly
Public assembly buildings include houses of worship, auditoriums, movie theaters, performance theaters, concert halls, arenas, enclosed stadiums, ice rinks, gymnasiums, convention centers, exhibition centers, museums, exercise centers and natatoriums
- Heated Only
This category applies to an entire building with heating only systems in the proposed design, such as warehouses
- Retail
Retail buildings that are two floors or less must use single-zone packaged equipment. In the baseline building, cooling will always be DX but heating will be dependent upon the climate zone. Retail buildings that are 3 or more stories are included in the Nonresidential category below. Restaurants are also included in the nonresidential category described below.
- Hospital
This excludes outpatient medical buildings and offices.
- Other Non-Residential
This category would cover all buildings that are not included any other category
Where attributes make a building eligible for more than one baseline system type, the predominant condition should be used to determine the system type for the entire building, except as notes in Section G3.1.1. of Standard 90.1-2019 and also documented in Section 3.1.1.1 of this manual.
Table 4. HVAC System Descriptions
System No. |
System Type |
Fan Control |
Cooling Type |
Heating Type (note 3) |
1 – PTAC |
Package terminal air conditioner |
Constant volume |
Direct expansion |
Hot water fossil fuel boiler |
2 – PTHP |
Packaged terminal heat pump |
Constant volume |
Direct expansion |
Electric heat pump |
3 – PSZ AC |
Packaged roof top air conditioner |
Constant volume |
Direct expansion |
Fossil fuel furnace |
4 – PSZ HP |
Packaged roof top heat pump |
Constant volume |
Direct expansion |
Electric heat pump |
5 – PVAV Reheat |
Packaged rooftop VAV with reheat |
Variable volume |
Direct expansion |
Hot water fossil fuel boiler |
6 – Packaged VAV with PFP Boxes |
Packaged rooftop VAV with PFP boxes and reheat |
Variable volume |
Direct expansion |
Electric resistance |
7 – VAV with Reheat |
Rooftop VAV with reheat |
Variable volume |
Chilled water |
Hot water fossil fuel boiler |
8 – VAV with PFP Boxes |
VAV with parallel fan-powered boxes and reheat |
Variable volume |
Chilled water |
Electric resistance |
9 – Heating and Ventilation |
Warm air furnace, gas fired |
Constant volume |
None |
Fossil fuel furnace |
10 – Heating and Ventilation |
Warm air furnace, electric |
Constant volume |
None |
Electric resistance |
11 – SZ-VAV |
Single zone VAV |
Variable air volume |
Chilled Water |
See Note 2 |
12 – SZ-CV-HW |
Single zone with hot water heat |
Constant volume |
Chilled Water |
Hot water fossil fuel boiler |
13 – SZ-CV-ER |
Single zone with electric resistance heat |
Constant volume |
Chilled Water |
Electric resistance |
Notes:
|
G3.2 New Construction/Major Alterations
The HVAC system in the baseline building depends on the primary building activity, the number of floors, conditioned floor area and climate zone. Details about these systems are provided in subsequent sections.
For many of the building descriptors there is a one-to-one relationship between the proposed design and the baseline building; for example, every wall in the proposed design has a corresponding wall in the baseline building. However, for HVAC systems, this one-to-one relationship generally does not hold. There may be a different number of HVAC systems serving the proposed design compared to the baseline building, and equipment such as cooling towers, circulation pumps, etc. may be present in the baseline but not proposed design.
The HVAC system in the baseline building shall be selected from Table 3, HVAC System Map, and be based on building type, number of floors in the building, conditioned floor area of the building type, and climate zone. The selected system shall conform to the descriptions in Table 4, HVAC System Descriptions.
For systems 1, 2, 3, 4, 9, 10, 11, 12, and 13, each thermal zone shall be modeled with its own HVAC system. For systems 5, 6, 7, and 8, each floor shall be modeled with a separate HVAC system. Floors with identical thermal zones can be grouped for modeling purposes.
Table 3. Standard 90.1 Section G3.2 HVAC System Map
Building Area Type |
Size (Combined gross conditioned floor area and semiheated floor area, of the building area type) |
Baseline Building System Type |
|
Cool Climates |
Warm Climates |
||
Residential |
Any size |
System 1 PTAC |
System 2 PTHP |
Public Assembly |
< 120,000 ft² |
System 3 PSZ-AC |
System 4 PSZ-HP |
≥ 120,000 ft² |
System 12 SZ-CV-HW |
System 13 SZ-CV-ER |
|
Retail |
In a building that is 1 or 2 stories |
System 3 PSZ-AC |
System 4 PSZ-HP |
Other than |
Use “Other Nonresidential” |
||
Hospital |
Larger than 150,000 ft2 or in a building greater than 5 stories |
System 7 VAV with Reheat |
System 7 VAV with Reheat |
All other hospital |
System 5 PVAV with Reheat |
System 5 PVAV with Reheat |
|
Heated-only Storage |
|
System 9- Heating and Ventilation |
System 10- Heating and Ventilation |
Other Nonresidential |
In a building 3 floors or less and <25,000 ft2 |
System 3 PSZ-AC |
System 4 PSZ-HP |
In a building with 4 or 5 floors and <25,000 ft2 |
System 5 PVAV with Reheat |
System 6 PVAV with PFP boxes |
|
In a building 5 floors or less and 25,000 ft2 to 150,000 ft2 |
System 5 PVAV with Reheat |
System 6 PVAV with PFP boxes |
|
In a building more than 5 floors or >150,000 ft2 |
7 VAV with Reheat |
8 VAV with PFP boxes |
Building Type Descriptions for Baseline System Definition:
- Residential
HVAC zones that include dwelling units, guest rooms, living quarters, private living spaces, and sleeping quarters. Residential associated HVAC zones shall be classified as residential. Other space types, including patient rooms in hospitals, shall not be classified as residential.
- Residential Associated HVAC Zone
Any HVAC zone that primarily includes nonresidential spaces designed to serve occupants of residential spaces, including but not limited to corridors, stairwells, elevator lobbies, and common restrooms, on a floor where over 75% of the gross conditioned floor area are residential spaces. This definition does not apply to HVAC zones within hospitals.
- Public Assembly
Public assembly buildings include houses of worship, auditoriums, movie theaters, performance theaters, concert halls, arenas, enclosed stadiums, ice rinks, gymnasiums, convention centers, exhibition centers, museums, exercise centers and natatoriums. HVAC zones that include these area types in other buildings shall also be classified as public assembly.
- Heated Only
This category applies to nonrefrigerated warehouse buildings. Ventilated parking garages that do not meet the definitions of either a conditioned or semiheated space are considered unenclosed spaces and do not apply to this category. The HVAC system types should be modeled identically in the baseline and proposed for such parking garages.
- Retail
Retail buildings that are two floors or less including grocery stories, retail stores, and supermarket buildings. Retail buildings that are 3 or more stories are included in the Nonresidential category below. Restaurants are also included in the nonresidential category described below.
- Hospital
Includes patents rooms and excludes outpatient medical buildings and offices.
- Other Non-Residential
This category covers all buildings that are not included any other categories.
Table 4. Standard 90.1 Section G3.2 HVAC System Descriptions
System No. |
System Type |
Fan Control |
Cooling Type1 |
Heating Type 1 |
1 – PTAC |
Package terminal air conditioner |
Constant volume |
Direct expansion |
Hot water fossil fuel boiler |
2 – PTHP |
Packaged terminal heat pump |
Constant volume |
Direct expansion |
Electric heat pump |
3 – PSZ AC |
Packaged roof top air conditioner |
Constant volume |
Direct expansion |
Fossil fuel furnace |
4 – PSZ HP |
Packaged roof top heat pump |
Constant volume |
Direct expansion |
Electric heat pump |
5 – PVAV Reheat |
Packaged rooftop VAV with reheat |
Variable volume |
Direct expansion |
Hot water fossil fuel boiler |
6 – Packaged VAV with PFP Boxes |
Packaged rooftop VAV with PFP boxes and reheat |
Variable volume |
Direct expansion |
Electric resistance |
7 – VAV with Reheat |
Rooftop VAV with reheat |
Variable volume |
Chilled water |
Hot water fossil fuel boiler |
8 – VAV with PFP Boxes |
VAV with parallel fan-powered boxes and reheat |
Variable volume |
Chilled water |
Electric resistance |
9 – Heating and Ventilation |
Warm air furnace, gas fired |
Constant volume |
None |
Fossil fuel furnace |
10 – Heating and Ventilation |
Warm air furnace, electric |
Constant volume |
None |
Electric resistance |
11 – SZ-VAV |
Single zone VAV |
Variable air volume |
Chilled Water |
See Note 2 |
12 – SZ-CV-HW |
Single zone with hot water heat |
Constant volume |
Chilled Water |
Hot water fossil fuel boiler |
13 – SZ-CV-ER |
Single zone with electric resistance heat |
Constant volume |
Chilled Water |
Electric resistance |
Notes:
|