3.1.1.3 Purchased Heat and Purchased Chilled Water

90.1-2019

Purchased Heat

For systems using purchased hot water or steam, the heating source shall be modeled as purchased hot water or steam in both the proposed and baseline building designs. Hot water or steam costs shall be based on actual utility rates, and on-site boilers, electric heat, and furnaces shall not be modeled in the baseline building design.

Purchased Chilled Water

For systems using purchased chilled water, the cooling source shall be modeled as purchased chilled water in both the proposed and baseline building designs. Purchased chilled water costs shall be based on actual utility rates, and on-site chillers and DX equipment shall not be modeled in the baseline building design.

Baseline system requirements for proposed designs using purchased heat or chilled water for heating or cooling are mentioned in Table 8. Modeling requirements for on-site distribution pumps are documented in Section 3.8.5.

Table 8. Baseline Requirements for Purchased Heat and Purchased Chilled Water Systems

Proposed

Baseline System

Heating

Cooling

Purchased heat

Chiller or DX

The baseline heating and cooling source shall be based on the applicable cooling system as determined by Table 3 and Table 4.

Boiler/electric resistance or gas furnace

Purchased chilled water

Table 3 and Table 4 shall be used to select the baseline HVAC system type, with the following modifications:

  • Purchased chilled water shall be substituted for the cooling source in Table 4.
  • Systems 1 and 2 shall be constant volume fan coil units with fossil fuel boiler(s).
  • Systems 3 and 4 shall be constant volume single zone air handlers with fossil fuel furnace(s). Refer to Section 3.7.6 of this document for details.
  • System 7 shall be used in place of System 5. Refer to Section 3.8.1 of this document for details.
  • System 8 shall be used in place of System 6. Refer to Section 3.8.2 of this document for details.

Purchased heat

Purchased chilled water

Table 3 and Table 4 shall be used to determine the baseline HVAC system type, with the following modifications:

  • Purchased heat and purchased chilled water shall be substituted for the heating types and cooling types in Table 4.
  • System 1 will be constant volume fan coil units. Refer to Section 3.7.5.5 of this document for details on this system type.
  • System 3 will be a constant volume single zone air handler. Refer to Section 3.7.5.2 of this document for details.
  • System 7 will be used in place of System 5. Refer to Section 3.8.2 of this document for details.