|
Exhaust to Outside Heat Recovery Effectiveness |
|||||||||
|---|---|---|---|---|---|---|---|---|---|
|
Applicability |
Any system with outside air heat recovery |
||||||||
|
Definition |
The effectiveness of an air-to-air heat exchanger between the building exhaust and entering outside air streams. Effectiveness is defined as follows: (Equation 3.7.6-14) $$HREFF = \frac{EEA_{db}-ELA_{db}}{EEA_{db}-OSA_{db}}$$ where
|
||||||||
|
Units |
Ratio |
||||||||
|
Input Restrictions |
As designed |
||||||||
|
Baseline Rules |
Required for fan systems with a design supply air flow rate of 5,000 cfm or greater if the minimum outside air quantity is 70% of the design air flow rate. If required, the energy recovery system should have at least 50% effectiveness. Energy recovery is not required for the following situations:
|
||||||||
|
Condenser Heat Recovery Effectiveness |
|
|---|---|
|
Applicability |
Systems that use recover heat from a condenser |
|
Definition |
The percentage of heat rejection at design conditions from a DX or heat pump unit in cooling mode that is available for space or water heating. |
|
Units |
Percent (%) |
|
Input Restrictions |
As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
|
Baseline Rules |
Not applicable for most conditions. Condenser heat recovery is required for service water heating in 24-hour-per-day facilities, if the total installed heat rejection of the water cooled system exceeds 6,000,000 Btu/h and the design service water heating load exceeds 1,000,000 Btu/h. In this case the heat recovery system is required to have the capacity to provide the smaller of 60% of peak heat rejection load at design conditions or preheat the peak service hot water to 85F. Exceptions to this requirement do not apply. If a condenser heat recovery system meeting the requirements described in Section 6.5.6.2 cannot be modeled, the requirement for including such a system in the actual building shall be met as a prescriptive requirement in accordance with Section 6.5.6.2, and no heat-recovery system shall be included in the proposed or baseline building designs. |
|
Heat Recovery Use |
|
|---|---|
|
Applicability |
Systems that use heat recovery |
|
Definition |
The end use of the heat recovered from a DX or heat pump unit. The choices are:
|
|
Units |
List (see above) |
|
Input Restrictions |
As designed. The software must indicate that supporting documentation is required on the output forms if heat recovery is specified. |
|
Baseline Rules |
Not applicable for most conditions. The end use will be water heating if required for 24-hour facility operation. |
For baseline systems requiring energy recovery, the heat exchanger is assumed to be integral with the AHU. The system fan power or pressure drop will be adjusted according to the methods in Section 3.7.3.1 of this document.
For proposed systems with heat recovery, the analyst must be careful to set all descriptors, particularly those for control, parasitic energy, and exhaust airflows, to realistically represent the equipment components, operation, and maintenance of building pressurization.
When exhaust air energy recovery systems are installed in cold climates, frost control may significantly affect total recovered energy during subfreezing conditions. Pumps and dedicated fans will consume parasitic energy. Simulation program inputs and hourly reports should be reviewed to ensure all items are represented as close as possible to the actual result of the proposed control sequences.
Requirements related to condenser heat recovery are documented in Section 3.8.7 of this manual.
|
Exhaust Air Energy Recovery |
|
|---|---|
|
Applicability |
Any system with outside air heat recovery |
|
Definition |
Provision of exhaust air energy recovery system. Provisions shall be made to bypass heat recovery system to permit air-side economizer operation as specified in Section 3.7.4.2 of this document. |
|
Units |
Unitless |
|
Input Restrictions |
As designed |
|
Baseline Building |
Required for fan systems with a design supply air flow rate of 5,000 cfm or greater, if the minimum outside air quantity is 70% of the design air flow rate. Energy recovery is not required for the following situations:
|
|
Enthalpy Recovery Ratio |
|||
|---|---|---|---|
|
Applicability |
Any system with outside air heat recovery |
||
|
Definition |
The general effectiveness of an air-to-air heat exchanger as characterized by the reduction in heating or cooling load between the building exhaust and entering outside air streams. Enthalpy Recovery Ratio is defined as follows:
Where: ERRH = The air-to-air heat exchanger enthalpy recovery OSAH = The total enthalpy of the outside air entering the exchanger OSLAH = The total enthalpy of the outside air leaving the heat exchanger ELAH = The total enthalpy of the exhaust air entering the heat exchanger |
||
|
Units |
Fraction (between 0 and 1) |
||
|
Input Restrictions |
As designed in accordance to the formula above |
||
|
Baseline Building |
The baseline would have 50% energy recovery effectiveness based on design conditions. Fifty percent energy recovery effectiveness shall mean a change in the enthalpy of the outdoor air supply equal to 50% of the difference between the outdoor air and return air enthalpies at design conditions. |
||
|
Exhaust Air Energy Recovery Economizer Interaction |
|
|---|---|
|
Applicability |
Any system with outside air enthalpy heat recovery |
|
Definition |
Energy recovery control during economizer operation |
|
Units |
Lockout, no lockout |
|
Input Restrictions |
As designed |
|
Baseline Building |
Lockout. The baseline system should bypass the energy recovery device during economizer operation. Refer to Section 3.7.4 of this document for baseline economizer requirements. During economizer operation, parasitic losses of energy recovery device and fan energy impact of pressure drop through energy recovery device should not occur. |
|
Applicability |
Systems that use heat recovery |
|
Definition |
This input is used to model electric power consumption by controls (transformers, relays, etc.) and/or a motor for a rotary heat exchanger. None of this electric power contributes thermal load to the supply or exhaust air streams. |
|
Units |
Watts (W) |
|
Input Restrictions |
As designed. A default of 50W is assumed which can be overridden by the user. |
|
Baseline Building |
50W |
|
Heat Exchanger Fan Energy Consumption |
|
|---|---|
|
Applicability |
Systems that use heat recovery |
|
Definition |
The additional fan energy needed for the energy recovery device. For all energy recovery ventilator (ERV) systems that include a bypass during economizer operations, the fan energy consumption for ERV systems should only be modeled when the ERV runs and should not be considered when the ERV is bypassed for economizer operation. |
|
Units |
Watts (W) |
|
Input Restrictions |
As designed |
|
Baseline Building |
The ERV fan power for the baseline system can be calculated as follows: Bhp = [ (0.6 × OAcfm) + (0.6 × 0.9 × OAcfm)] /4131 W = bhp x 746/nm This has been calculated from: Bhp = [((2.2 × HREFF) - dpoa) x OAcfm]/4131 + [ ((2.2 × HREFF × Ef) – dpex) × OAcfm ]/4131
Where: Bhp = Fan brake horse power HREFF = Heat exchanger effectiveness dpoa = ERV pressure drop on the outdoor air side (is assumed to be 0.5 in. w.c.) dpex = ERV pressure drop on the exhaust air side (is assumed to be 0.5 in. w.c.) Ef = Exhaust airflow fraction (exhaust airflow is 90% of outdoor airflow after considering leakage and zone exhaust) W = Fan power nm = Fan motor efficiency of supply fan. For EnergyPlus fan, energy for an ERV is not an input of the ERV module and the ERV fan energy should not simply be added to the system supply fan if the ERV includes a bypass during economizer operations as required in the baseline. The following workaround should be used instead. The fan energy associated with energy recovery is modeled as additional ERV parasitic power. This results in the ERV fan energy occurring only when the ERV runs, which is the desired behavior. If there is not a bypass in the proposed design, ERV fan energy shall be included in the HVAC system fan so that its impact is accounted for whenever the fans are running. |
For projects subject to Standard 90.1-2022 Section G3.2 baseline systems requiring energy recovery, the heat exchanger is assumed to be integral with the AHU. For projects subject to Standard 90.1-2022 Section G3.3 baseline systems, the energy recovery system type is the same as designed. The system fan power or pressure drop will be adjusted according to the methods in Section 3.7.3.1 of this document.
For proposed systems with heat recovery, the analyst must be careful to set all descriptors, particularly those for control, parasitic energy, and exhaust airflows, to realistically represent the equipment components, operation, and maintenance of building pressurization.
When exhaust air energy recovery systems are installed in cold climates, frost control may significantly affect total recovered energy during subfreezing conditions. Pumps and dedicated fans will consume parasitic energy. Simulation program inputs and hourly reports should be reviewed to ensure all items are represented as close as possible to the actual result of the proposed control sequences.
Requirements related to condenser heat recovery are documented in Section 3.8.7 of this manual.
|
Exhaust Air Energy Recovery |
|
|---|---|
|
Applicability |
Any system with outside air heat recovery |
|
Definition |
Provision of exhaust air energy recovery system. Provisions shall be made to bypass heat recovery system to permit air-side economizer operation as specified in Section 3.7.4.2 of this document. |
|
Units |
Unitless |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations Required for fan systems with a design supply air flow rate of 5,000 cfm or greater, if the minimum outside air quantity is 70% of the design air flow rate. Energy recovery is not required for the following situations:
G3.3 Minor Alterations The baseline should be modeled as minimally compliant with the exhaust air recovery requirements Standard 90.1-2022 Section 6.5.6.1. Standard 90.1-2022 Section 6.5.6.1 requires nontransient dwelling units to include outdoor air energy recovery ventilation systems and that each fan system serving spaces other than nontransient dwelling units to have an energy recovery system when the design supply fan airflow rate exceeds the value listed in Standard 90.1-2022 Tables 6.5.6.1.2-1 and 6.5.6.1.2-2, based on the climate zone and percentage of outdoor air at design airflow conditions. Exceptions to 90.1-2022 Section 6.5.6.1.
Applicable to nontransitent dwelling units:
a. used for another energy recovery system, b. not allowed by ASHRAE/ASHE Standard 170 for use in energy recovery systems with leakage potential, or c. of Class 4 as defined in ASHRAE Standard 62.1.
Exception: the baseline and proposed should be modeled identically if, based on the requirements of 90.1-2022 Section 6.1.4 and the scope of the alteration, 90.1-2022 Section 6.5.6.1 requirements are inapplicable. |
|
Enthalpy Recovery Ratio |
|||
|---|---|---|---|
|
Applicability |
Any system with outside air heat recovery |
||
|
Definition |
The general effectiveness of an air-to-air heat exchanger as characterized by the reduction in heating or cooling load between the building exhaust and entering outside air streams. Enthalpy Recovery Ratio is defined as follows:
Where: ERRH = The air-to-air heat exchanger enthalpy recovery OSAH = The total enthalpy of the outside air entering the exchanger OSLAH = The total enthalpy of the outside air leaving the heat exchanger ELAH = The total enthalpy of the exhaust air entering the heat exchanger |
||
|
Units |
Fraction (between 0 and 1) |
||
|
Input Restrictions |
As designed in accordance with the formula above. |
||
|
Baseline Building |
G3.2 New Construction/Major Alterations A 50% enthalpy recovery ratio is required to be modeled. Various combinations of latent and sensible effectiveness values can result in an enthalpy recovery ratio of 50% depending on the exact specification of the energy recovery device. By definition a 50% latent and sensible energy recovery effectiveness is equivalent to a 50% enthalpy recovery ratio. In the absence of a manufacturer specification establishing a combination of latent and sensible effectiveness values that result in a 50% enthalpy recovery ratio, a 50% latent and sensible energy recovery effectiveness should be modeled in the baseline. A fifty percent enthalpy recovery ratio means that the change in the enthalpy of the outdoor air supply divided by the difference between the outdoor air and entering exhaust air enthalpies at design conditions equals fifty percent. G3.3 Minor Alterations When exhaust air energy recovery is included in the scope of the alteration and required to be modeled in the baseline based on the language in 90.1 Sections 6.1.4 and 6.5.6.1 the following enthalpy recovery ratios shall be modeled. 50% enthalpy recovery ratio at cooling design conditions for both nontransient dwelling unit and other spaces. For Nontransient Dwelling Units: At the heating design condition, energy recovery performance shall be as follows: a. Where active humidification is provided to spaces served by the system, energy recovery systems shall result in an enthalpy recovery ratio of at least 60%. b. Where active humidification is not provided to spaces served by the system, energy recovery systems shall result in a sensible energy recovery ratio of at least 60%. Exceptions for nontransient dwelling units:
Spaces Other than Nontransient Dwelling Units: At the heating design condition, energy recovery performance shall be as follows: a. Where active humidification is provided to spaces served by the system, energy recovery systems shall result in an enthalpy recovery ratio of at least 50%. b. Where active humidification is not provided to spaces served by the system, energy recovery systems shall result in a sensible energy recovery ratio of at least 50% The energy recovery system shall provide the required enthalpy recovery ratio or sensible energy recovery ratio at both heating and cooling design conditions unless one mode is not required for the climate zone by the exception to Section 6.5.6.1. Exceptions for spaces other than nontransient dwelling units:
See the G3.2 section for a discussion on establishing the model inputs to model the required enthalpy recovery ratios. Otherwise, model the exhaust air energy recovery enthalpy ratio identically in the baseline and proposed. |
||
|
Exhaust Air Energy Recovery Economizer Interaction |
|
|---|---|
|
Applicability |
Any system with outside air enthalpy heat recovery |
|
Definition |
Energy recovery control during economizer operation |
|
Units |
Lockout, no lockout |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations Lockout. The baseline system should bypass the energy recovery device during economizer operation. Refer to Section 3.7.4 of this document for baseline economizer requirements. During economizer operation, parasitic losses of energy recovery device and fan energy impact of pressure drop through energy recovery device should not occur. G3.3 Minor Alterations When exhaust air energy recovery is part of the scope of the alteration and is required to be modeled in the baseline based on the language in 90.1 Sections 6.1.4 and 6.5.6.1 lockout should be modeled unless the energy recovery system includes 80% or more outdoor air at full design air-flow rate and does not exceed 10,000 cfm (Exception to 90.1-2022 6.5.6.1.2.2). Otherwise, model the exhaust air energy recovery economizer interaction identically in the baseline and proposed. |
|
Applicability |
Systems that use heat recovery |
|
Definition |
This input is used to model electric power consumption by controls (transformers, relays, etc.) and/or a motor for a rotary heat exchanger. None of this electric power contributes thermal load to the supply or exhaust air streams. |
|
Units |
Watts (W) |
|
Input Restrictions |
As designed. A default of 50W is assumed which can be overridden by the user. |
|
Baseline Building |
G3.2 New Construction/Major Alterations 50W G3.3 Minor Alterations Same as proposed. |
|
Heat Exchanger Fan Energy Consumption |
|
|---|---|
|
Applicability |
Systems that use heat recovery |
|
Definition |
The additional fan energy needed for the energy recovery device. For all energy recovery ventilator (ERV) systems that include a bypass during economizer operations, the fan energy consumption for ERV systems should only be modeled when the ERV runs and should not be considered when the ERV is bypassed for economizer operation. |
|
Units |
Watts (W) |
|
Input Restrictions |
As designed |
|
Baseline Building |
The ERV fan power for the baseline system (only applies when exhaust air energy recovery is required to be modeled in the baseline) can be calculated as follows: Bhp = [ (0.6 × OAcfm) + (0.6 × 0.9 × OAcfm)] /4131 W = bhp x 746/nm This has been calculated from: Bhp = [((2.2 × HREFF) - dpoa) x OAcfm]/4131 + [ ((2.2 × HREFF × Ef) – dpex) × OAcfm ]/4131
Where: Bhp = Fan brake horse power HREFF = Heat exchanger effectiveness dpoa = ERV pressure drop on the outdoor air side (is assumed to be 0.5 in. w.c.) dpex = ERV pressure drop on the exhaust air side (is assumed to be 0.5 in. w.c.) Ef = Exhaust airflow fraction (exhaust airflow is 90% of outdoor airflow after considering leakage and zone exhaust) W = Fan power nm = Fan motor efficiency of supply fan. For EnergyPlus fan, energy for an ERV is not an input of the ERV module and the ERV fan energy should not simply be added to the system supply fan if the ERV includes a bypass during economizer operations as required in the baseline. The following workaround should be used instead. The fan energy associated with energy recovery is modeled as additional ERV parasitic power. This results in the ERV fan energy occurring only when the ERV runs, which is the desired behavior. If there is not a bypass in the proposed design, ERV fan energy shall be included in the HVAC system fan so that its impact is accounted for whenever the fans are running. |