3.9.1.2 Water Heaters

90.1-2019

This section describes the building descriptors for water heaters. Typically, a building will have multiple water heating systems and each system can have multiple water heaters, so these building descriptors may need to be specified more than once.

 

Water Heater Name

Applicability

All water heaters

Definition

A unique descriptor for each water heater in the system. Some systems will have multiple pieces of equipment, for instance a series of water heaters plumbed in parallel or a boiler with a separate storage tank.

Units

Text, unique

Input Restrictions

Where applicable, this should match the tags that are used on the plans such that a plan reviewer can make a connection

Baseline Building

The naming convention for the baseline building system shall be similar to the proposed design

 

Water Heater Type and Size

Applicability

All water heaters

Definition

This building descriptor includes information needed to determine the criteria from baseline standards. The choices are listed below.

  • Electric water heaters (storage and instantaneous)

– Small (≤ 12 kW)

– Large (> 12 kW)

– Heat pump

  • Gas storage water heaters

– Small (≤ 75,000 Btu/h)

– Large (> 75,000 Btu/h)

  • Gas instantaneous water heaters

– Small (> 50,000 and < 200,000 Btu/h)

– Large (≥ 200,000 Btu/h), <10 gal

– Large (≥ 200,000 Btu/h), >= 10 gal

  • Oil storage water heaters

– Small (≤ 105,000 Btu/h)

– Large (> 105,000 Btu/h)

  • Oil instantaneous water heaters

– Small (≤ 210,000 Btu/h)

– Large (> 210,000 Btu/h), <10 gal

– Large (> 210,000 Btu/h), >= 10 gal

  • Gas hot water supply boiler
  • Oil hot water supply boiler
  • Heat exchanger from steam or district hot water

Units

List (see above)

Input Restrictions

The water heater type shall agree with equipment specified in the construction documents.

If no service hot water system exists or has been specified, but the building will have service hot water loads, a service water system shall be modeled that matches the system type in the baseline building design.

For buildings that will have no service hot water load, no service water heating system shall be modeled.

Baseline Building

Where a complete water heating system exists or a new service water heating system has been specified in the proposed design, the water heaters in the baseline system will be based on the building area type classification. See Table 96 below.

For new service hot water systems, the system will be sized according to the provisions of Standard 90.1-2019, Section 7.4.1, and the equipment shall match the minimum efficiency requirements in Standard 90.1-2019, Section 7.4.2. Where the energy source is electricity, the heating method shall be electrical resistance. When the energy source is ‘Gas Storage’, the water heater shall be modeled using natural gas as their fuel. Where natural gas is not available or the proposed building site, as determined by the rating authority, gas storage water heaters shall be modeled using propane as their fuel.

If no service hot water system exists or has been specified, but the building will have service hot water loads, a service water system shall be modeled for each building area type in the proposed design, in accordance to Table 96. and matching minimum efficiency requirements of Standard 90.1-2019, Section 7.4.2.

Table 96. Baseline Building Water Heater Type (Standard 90.1-2019 Table G3.1.1-2)

Gas Storage

Electric Resistance Storage

Automotive facility

Dining: Bar lounge/leisure

Dining: Cafeteria/fast food

Dining: Family

Dormitory

Exercise center

Fire station

Grocery Store

Gymnasium

Hospital and Outpatient Surgery Center

Hotel

Manufacturing facility

Motel

Multifamily

Penitentiary

Performing arts theater

School/university

Sports arena

All Others

Convenience Store

Convention center

Courthouse

Health-care clinic

Library

Motion picture theater

Museum

Office

Parking garage

Police station

Post office

Religious building

Retail

Town hall

Transportation

Warehouse

Workshop

 

 

Rated Capacity

Applicability

All water heaters

Definition

The heating capacity of a water heater at the rated conditions specified in DOE 10 CFR Part 430 or ANSI Z21.10

Units

Thousands of British thermal units per hour (MBH)

Input Restrictions

As designed. If the loads are not met, then the system needs to be autosized.

Baseline Building

Autosize

 

Storage Volume

Applicability

All water heaters

Definition

The storage volume of a gas-fired water heater. This is used in the standby loss calculations and baseline calculations of energy factor (EF).

Units

gallons

Input Restrictions

As designed. If the loads are not met, then the system needs to be autosized.

Baseline Building

Autosize

 

Energy Factor

Applicability

Equipment covered by the National Appliance Energy Conservation Act (NAECA), which includes small storage and instantaneous water heaters

Definition

The EF is the ratio of the energy delivered by the water heater divided by the energy used, in the same units. EF is calculated according to the DOE 10 CFR Part 430 test procedure, which specifies a 24-hour pattern of draws, a storage temperature, inlet water temperature, and other test conditions. These conditions result in the energy delivered for the test period. Energy inputs are measured for the same test period and the EF ratio is calculated.

Units

Unitless ratio (between 0 and 1)

Input Restrictions

Building descriptors for the proposed design should be consistent with equipment specified on the construction documents or observed in the candidate building

Baseline Building

The EF for the baseline building system shall be determined from Table 7.8 of Standard 90.1-2019. Additional UEF efficiency requirements can be found in Table F-2 of Standard 90.1-2019.

 

Thermal Efficiency

Applicability

Oil and gas-fired water heaters not covered by NAECA

Definition

The full load efficiency of a water heater at rated conditions expressed as a dimensionless ratio of output over input

Units

Unitless ratio (between 0 and 1)

Input Restrictions

Building descriptors for the proposed design should be consistent with equipment specified on the construction documents or observed in the candidate building

Baseline Building

From Table 7.8 of Standard 90.1-2019

 

Tank Standby Loss

Applicability

Water heaters not covered by NAECA

Definition

The tank standby loss for storage tanks, which includes the effect of recovery efficiency

Units

Btu/h for the entire tank

Input Restrictions

As specified in manufacturer data and documented on the construction documents

Baseline Building

As specified in Table 7.8 of Standard 90.1-2019

 

Tank Off-Cycle Loss Coefficient

Applicability

Water heaters

Definition

The tank standby loss coefficient (UA) for the water heater. For small water heaters covered by NAECA, the loss coefficient is a derived parameter, a function of the energy factor and recovery efficiency.

Units

Btu/h-°F

Input Restrictions

For NAECA covered water heaters, the loss coefficient is calculated by the following:

$$UA=\frac{1/EF - 1/RE}{67.5\times \left( \frac{24}{41094}-\frac{1}{RE\cdot Pon} \right)}$$

Where:

EF    =   The energy factor of the rated water heater (unitless)

RE    =   The recovery efficiency of the rated water heater. If this data is not available, the default shall be 0.78 for gas water heaters and 0.93 for electric water heaters.

Pon  =   The input power to the water heater, in Btu/h

Baseline Building

The baseline loss coefficient for NAECA water heaters shall be:

10 Btu/h-°F for gas-fired water heaters

 

Off Cycle Parasitic Losses

Applicability

Water heater

Definition

The rate of parasitic losses, such as a pilot light or controls, when the water heater is not heating. If modeled explicitly, pilot lights should contribute to off-cycle heating.

Units

Watts

Input Restrictions

As designed

Baseline Building

0

 

Off Cycle Fuel Type

Applicability

Water heater

Definition

The type of fuel that serves energy using parasitic equipment, such as a pilot light or controls, when the water heater is not heating

Units

List: Electricity, Gas, Oil, Propane

Input Restrictions

As designed

Baseline Building

Not applicable

 

On Cycle Parasitic Losses

Applicability

Water heater

Definition

The rate of parasitic losses, such as a pilot light or draft fan controls, when the water heater is heating. This may be different than off cycle losses if the flue energy is considered.

Units

Watts

Input Restrictions

As designed

Baseline Building

0

 

On Cycle Fuel Type

Applicability

Water heater

Definition

The type of fuel that serves energy using parasitic equipment, such as a pilot light or controls, when the water heater is not heating

Units

List: Electricity, Gas, Oil, Propane

Input Restrictions

As designed

Baseline Building

Not applicable

 

Water Heater Ambient Temperature Indicator

Applicability

Water heater

Definition

The location of the water heater for determining losses and energy interaction with the surroundings

Units

List: Schedule, Zone, Outdoors

Input Restrictions

As designed. When “Schedule” is used, a time of day schedule needs to be specified with temperature schedule for each hour.

Baseline Building

Same as proposed

 

Fuel Water Heater Part Load Efficiency Curve

Applicability

Water heating equipment for which a thermal efficiency as opposed to an EF is specified

Definition

A set of factors that adjust the full-load thermal efficiency for part load conditions. The factor is set as a curve.

Units

Percent (%)

Input Restrictions

The following default curve shall be used unless detailed information is provided to justify alternative values. The default curve shall take the form of a quadratic equation as follows:

$$FHeatPLC=a+b\times\frac{Q_{partload}}{Q_{rated}} +c\times\left(\frac{Q_{partload}}{Q_{rated}} \right)^2$$

(59)

Where:

FHeatPLC    =     The fuel heating part load efficiency curve

Fuelpartload    =     The fuel consumption at part load conditions (Btu/h)

Fuel design      =     The fuel consumption at design conditions (Btu/h)

Qpartload         =     The water heater capacity at part load conditions (Btu/h)

Qrated             =     The water heater capacity at design conditions (Btu/h)

a                   =     Constant, 0.021826

b                   =     Constant, 0.977630

c                   =     Constant, 0.000543

Baseline Building

The baseline shall use the default curve