Outside Air Controls
Maximum Outside Air Ratio | |
Applicability | All systems with modulating outside air dampers |
---|---|
Definition | The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | 1.0 |
Design Outside Air Flow | |
Applicability | All systems with outside air dampers |
---|---|
Definition | The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside air flow for each of the zones served by the system. |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design. This input along with occupant density determines if the zones served by the system shall have demand control ventilation. See ventilation control method at the zone level. |
Outdoor Air Control Method | |
Applicability | All HVAC systems that deliver outside air to zones |
---|---|
Definition | The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system report their outside air requirements on an hourly basis. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information on an hourly basis. Options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Air Side Economizers
Economizer Control Type | |
Applicability | All systems with an air-side economizer |
---|---|
Definition | An air-side economizer increases outside air ventilation during periods when refrigeration loads can be reduced from increased outside air flow. The control types include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | The control should be no economizer when the baseline building cooling capacity $\leq$50 tons AND the baseline building system total cooling capacity $\leq$95,000 Btu/h. Otherwise, the control should be based on the prescribed system type as shown in [bookref id="baseline-economizer-control-type"]. |
[table title="Baseline Economizer Control Type" id="baseline-economizer-control-type"]
Baseline building System | Economizer Control |
System 1 – PTAC | None |
System 2 – PTHP | None |
System 3 – PSZ-AC | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 4 – PSZ-HP | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 5 – Packaged VAV with Reheat | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 6 – Packaged VAV with PFP boxes | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 7 – VAV with Reheat | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 8 – VAV with PFP boxes | Differential dry-bulb None in climate zones 1a-4a and 1b |
Economizer High Temperature Lockout | |
Applicability | Systems with fixed dry-bulb economizer |
---|---|
Definition | The outside air setpoint temperature above which the economizer will return to minimum position. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Economizer Low Temperature Lockout | |
Applicability | Systems with air-side economizers |
---|---|
Definition | A feature that permits the lockout of economizer operation (return to minimum outside air position) when the outside air temperature is below the lockout setpoint. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | Not used |
Economizer High Enthalpy Lockout | |
Applicability | Systems with fixed enthalpy or differential enthalpy economizers |
---|---|
Definition | The outside air enthalpy above which the economizer will return to minimum position |
Units | Btu/lb |
Input Restrictions | As designed. The default is 25 Btu/lb. |
Baseline Rules | No lockout limit |
Outside Air Controls
Maximum Outside Air Ratio | |
Applicability | All systems with modulating outside air dampers |
---|---|
Definition | The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | 1.0 |
Design Outside Air Flow | |
Applicability | All systems with outside air dampers |
---|---|
Definition | The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside air flow for each of the zones served by the system. |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design. This input along with occupant density determines if the zones served by the system shall have demand control ventilation. See ventilation control method at the zone level. |
Outdoor Air Control Method | |
Applicability | All HVAC systems that deliver outside air to zones |
---|---|
Definition | The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system report their outside air requirements on an hourly basis. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information on an hourly basis. Options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Same as proposed design |
Air Side Economizers
Economizer Control Type | |
Applicability | All systems with an air-side economizer |
---|---|
Definition | An air-side economizer increases outside air ventilation during periods when refrigeration loads can be reduced from increased outside air flow. The control types include:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | The control should be no economizer when the baseline building cooling capacity $\leq$50 tons AND the baseline building system total cooling capacity $\leq$95,000 Btu/h. Otherwise, the control should be based on the prescribed system type as shown in Table 6.7.4-1 . |
Table 6.7.4-1: Baseline Economizer Control Type
Baseline building System | Economizer Control |
System 1 – PTAC | None |
System 2 – PTHP | None |
System 3 – PSZ-AC | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 4 – PSZ-HP | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 5 – Packaged VAV with Reheat | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 6 – Packaged VAV with PFP boxes | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 7 – VAV with Reheat | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 8 – VAV with PFP boxes | Differential dry-bulb None in climate zones 1a-4a and 1b |
System 9 – Heating and Ventilation | None (no cooling) |
System 10 – Heating and Ventilation | None (no cooling) |
Economizer High Temperature Lockout | |
Applicability | Systems with fixed dry-bulb economizer |
---|---|
Definition | The outside air setpoint temperature above which the economizer will return to minimum position. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | Not applicable |
Economizer Low Temperature Lockout | |
Applicability | Systems with air-side economizers |
---|---|
Definition | A feature that permits the lockout of economizer operation (return to minimum outside air position) when the outside air temperature is below the lockout setpoint. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | Not used |
Economizer High Enthalpy Lockout | |
Applicability | Systems with fixed enthalpy or differential enthalpy economizers |
---|---|
Definition | The outside air enthalpy above which the economizer will return to minimum position |
Units | Btu/lb |
Input Restrictions | As designed. The default is 25 Btu/lb. |
Baseline Rules | No lockout limit |
Outside Air Controls
Maximum Outside Air Ratio |
|
---|---|
Applicability |
All systems with modulating outside air dampers |
Definition |
The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
Units |
Ratio |
Input Restrictions |
As designed |
Baseline Rules |
1.0 for systems 3-8 and 11-13. |
Design Outside Air Flow |
|
---|---|
Applicability |
All systems with outside air dampers |
Definition |
The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside air flow for each of the zones served by the system. |
Units |
cfm |
Input Restrictions |
As designed |
Baseline Rules |
Same as proposed design, except for the following cases:
See ventilation control method at the zone level. |
Outdoor Air Control Method |
|
---|---|
Applicability |
All HVAC systems that deliver outside air to multiple zones |
Definition |
The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system report their outside air requirements on an hourly basis. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information on an hourly basis. Options include:
The quantity of outside air can be controlled in a number of ways, but a common method is to install a flow station at the outside air supply which modulates the position of the outside air and return dampers to maintain the desired outside air flow. With the average flow, a CO2 sensor in the return air duct is another way to control the position of the outside air and return dampers. |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
Same as proposed design |
Air Side Economizers
Table 3.7.4-1 – Economizer Requirements for Baseline Building Systems 3-8 and 11-13
Thermal Zone |
Humid (A) |
Dry (B) |
Marine (C) |
0 |
Economizer not required |
Economizer not required |
Fixed drybulb economizer with high-limit shutoff of 75 °F |
1 |
|||
2 |
|
||
3 |
|||
4 |
|||
5 |
Fixed drybulb economizer with high-limit shutoff of 70 °F |
||
6 |
|||
7 |
|
||
8 |
Economizers are not required in the baseline building for systems meeting one or more of the following exceptions:
- Systems that include gas-phase air cleaning to meet the requirements of Section 6.1.2 in Standard 62.1. This exception shall be used only if the system in the proposed design does not match the building design.
- Where the use of outdoor air for cooling will affect supermarket open refrigerated casework systems. This exception shall only be used if the system in the proposed design does not use an economizer. If the exception is used, an economizer shall not be included in the baseline building design.
- System types 3 or 4 that that serve computer rooms. If system type 11 is used to serve a computer room, it shall be equipped with a water economizer.
Economizer Control Type |
|
---|---|
Applicability |
All systems with an air-side economizer |
Definition |
An air-side economizer increases outside air ventilation during periods when refrigeration loads can be reduced from increased outside air flow. The control types include:
Differential dry-bulb or enthalpy economizers are also known as integrated economizers. |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
Fixed dry-bulb economizers are required for baseline building systems 3-8 and 11-13 except for climates identified in Table 3.7.4-1 |
Economizer High Temperature Lockout |
|
---|---|
Applicability |
Systems with fixed dry-bulb economizer |
Definition |
The outside air setpoint temperature above which the economizer will return to minimum position. |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Rules |
75 °F in all climates that require an economizer, except 70 °F in climate zones 6a and 7a. See Table 3.7.4-1. |
Economizer Low Temperature Lockout |
|
---|---|
Applicability |
Systems with air-side economizers |
Definition |
A feature that permits the lockout of economizer operation (return to minimum outside air position) when the outside air temperature is below the lockout setpoint. |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Rules |
Not used |
Economizer High Enthalpy Lockout |
|
---|---|
Applicability |
Systems with fixed enthalpy or differential enthalpy economizers |
Definition |
The outside air enthalpy above which the economizer will return to minimum position |
Units |
Btu/lb |
Input Restrictions |
As designed. The default is 25 Btu/lb. |
Baseline Rules |
Not applicable since no baseline building system has an enthalpy economizer |
Outside Air Controls
Maximum Outside Air Ratio | |
Applicability | All systems with modulating outside air dampers |
---|---|
Definition | The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
Units | Ratio |
Input Restrictions | As designed |
Design Outside Air Flow | |
Applicability | All systems with outside air dampers |
---|---|
Definition | The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside air flow for each of the zones served by the system. |
Units | cfm |
Input Restrictions | As designed |
Outdoor Air Control Method | |
Applicability | All HVAC systems that deliver outside air to zones |
---|---|
Definition | The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system report their outside air requirements on an hourly basis. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information on an hourly basis. Options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Air Side Economizers
Economizer Control Type | |
Applicability | All systems with an air-side economizer |
---|---|
Definition | An air-side economizer increases outside air ventilation during periods when refrigeration loads can be reduced from increased outside air flow. The control types include:
|
Units | List (see above) |
Input Restrictions | As designed |
Economizer High Temperature Lockout | |
Applicability | Systems with fixed dry-bulb economizer |
---|---|
Definition | The outside air setpoint temperature above which the economizer will return to minimum position. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Economizer Low Temperature Lockout | |
Applicability | Systems with air-side economizers |
---|---|
Definition | A feature that permits the lockout of economizer operation (return to minimum outside air position) when the outside air temperature is below the lockout setpoint. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Economizer High Enthalpy Lockout | |
Applicability | Systems with fixed enthalpy or differential enthalpy economizers |
---|---|
Definition | The outside air enthalpy above which the economizer will return to minimum position |
Units | Btu/lb |
Input Restrictions | As designed. The default is 25 Btu/lb. |
Outside Air Controls
Maximum Outside Air Ratio | |
Applicability | All systems with modulating outside air dampers |
---|---|
Definition | The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
Units | Ratio |
Input Restrictions | As designed |
Design Outside Air Flow | |
Applicability | All systems with outside air dampers |
---|---|
Definition | The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside air flow for each of the zones served by the system. |
Units | cfm |
Input Restrictions | As designed |
Outdoor Air Control Method | |
Applicability | All HVAC systems that deliver outside air to zones |
---|---|
Definition | The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system report their outside air requirements on an hourly basis. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information on an hourly basis. Options include:
|
Units | List (see above) |
Input Restrictions | As designed |
Air Side Economizers
Economizer Control Type | |
Applicability | All systems with an air-side economizer |
---|---|
Definition | An air-side economizer increases outside air ventilation during periods when refrigeration loads can be reduced from increased outside air flow. The control types include:
|
Units | List (see above) |
Input Restrictions | As designed |
Economizer High Temperature Lockout | |
Applicability | Systems with fixed dry-bulb economizer |
---|---|
Definition | The outside air setpoint temperature above which the economizer will return to minimum position. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Economizer Low Temperature Lockout | |
Applicability | Systems with air-side economizers |
---|---|
Definition | A feature that permits the lockout of economizer operation (return to minimum outside air position) when the outside air temperature is below the lockout setpoint. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Economizer High Enthalpy Lockout | |
Applicability | Systems with fixed enthalpy or differential enthalpy economizers |
---|---|
Definition | The outside air enthalpy above which the economizer will return to minimum position |
Units | Btu/lb |
Input Restrictions | As designed. The default is 25 Btu/lb. |