Exhaust fans include toilet exhaust, kitchen exhaust, as well as fume hoods in laboratories and other spaces. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal block. An exhaust fan system may serve multiple thermal blocks. The baseline building has exhaust fans when the proposed design has exhaust fans. The exhaust air flow is the same for the baseline building and the proposed design.
Exhaust Fan Name |
|
---|---|
Applicability |
All exhaust systems serving multiple thermal blocks |
Definition |
A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal block level refer to this name. |
Units |
Text, unique |
Input Restrictions |
Where applicable, this should match the tags that are used on the plans. |
Baseline Rules |
The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Method |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
Software commonly models fans in three ways. See definition for supply system modeling method. |
Units |
List: power-per-unit-flow, static pressure or brake horsepower |
Input Restrictions |
As designed |
Baseline Rules |
If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method. |
Exhaust Fan Rated Capacity |
|
---|---|
Applicability |
All exhaust systems |
Definition |
The rated design air flow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual air flow is the sum of the flow specified for each thermal block, as modified by the schedule for each thermal block. |
Units |
cfm |
Input Restrictions |
As designed |
Baseline Rules |
Same as the proposed design. |
Fan Control Method |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
A description of how the exhaust fan(s) are controlled. The options include:
|
Units |
List (see above) |
Input Restrictions |
As designed, however, when exhaust fan flow at the thermal block level is varied through a schedule, one of the variable-flow options shall be specified. |
Baseline Rules |
The baseline building exhaust fan control shall generally be the same as the proposed design, with the following exceptions.
|
Exhaust Fan Schedule |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal block level. |
Units |
Data structure: schedule, on/off |
Input Restrictions |
The exhaust fan system shall be available during all periods when one or more thermal blocks served by the system are scheduling exhaust. |
Baseline Rules |
Same as the proposed design |
Exhaust Fan Brake Horsepower |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
The design shaft brake horsepower of the exhaust fan(s). |
Units |
Brake horsepower (bhp) |
Input Restrictions |
As designed |
Baseline Rules |
The bhp for the baseline building is the total system fan horsepower from Table 3.7.3-2 times the exhaust fan ratio. |
Exhaust Fan Design Static Pressure |
|
---|---|
Applicability |
Any system with return or relief fans that uses the static pressure method |
Definition |
The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units |
Inches of water column (in. H20) |
Input Restrictions |
As designed. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan brake horsepower (bhp) is specified. |
Baseline Rules |
The exhaust fan static pressure for the baseline building would be equal to the total fan system static pressure (specified in section Supply Fan Static Pressure) multiplied by the exhaust fan ratio. Exhaust Fan Static Pressure = (Exhaust Fan BHP x 6356 x 0.65)/cfm exhaust |
Exhaust Fan Efficiency |
|
---|---|
Applicability |
Any exhaust fan system that uses the static pressure method |
Definition |
The efficiency of the exhaust fan at rated capacity |
Units |
Unitless |
Input Restrictions |
For kitchen exhaust fans, the fan efficiency is prescribed at 50%. As designed for other exhaust fan systems. The exhaust fan efficiency does not need to be specified if the return fan brake horsepower (bhp) is specified. |
Baseline Rules |
The baseline exhaust fan efficiency is 65%. |
Exhaust Fan Motor Efficiency |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
The full-load efficiency of the motor serving the exhaust fan |
Units |
Unitless |
Input Restrictions |
As designed |
Baseline Rules |
From Table 3.7.3-4. |
Fan Part-Flow Power Curve |
|
---|---|
Applicability |
All variable flow exhaust fan systems |
Definition |
A part-load power curve which represents the ratio full-load power draw of the exhaust fan as a function of the ratio full-load air flow. |
Units |
Unitless ratio |
Input Restrictions |
As designed. The default fan curve shall be selected from COMNET Appendix H for the type of fan specified in the proposed design. |
Baseline Rules |
The baseline building fan curve shall be selected from COMNET Appendix H for the type of fan specified in the proposed design. |
Exhaust Fan Power Index |
|
---|---|
Applicability |
All exhaust systems |
Definition |
The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units |
W/cfm |
Input Restrictions |
As designed. |
Baseline Rules |
The baseline building exhaust fan power index shall be the fan system power from Table 3.7.3-2 multiplied times the exhaust fan ratio. |
Exhaust fans include toilet, kitchen and laboratory exhaust. Some systems typically operate at constant flow, while flow varies for other systems depending on, for instance, the position of the sash for fume hoods. Exhaust fan flow is specified and scheduled for each thermal zone. An exhaust fan system may serve multiple thermal zones. The baseline building has exhaust fans when the proposed design has exhaust fans. The design exhaust airflow is the same for the baseline building and the proposed building.
Exhaust Fan Name |
|
---|---|
Applicability |
All exhaust systems serving multiple thermal zones |
Definition |
A unique descriptor for each exhaust fan. This should be keyed to the construction documents, if possible, to facilitate plan checking. Exhaust rates and schedules at the thermal zone level refer to this name. |
Units |
Text, unique |
Input Restrictions |
Where applicable, this should match the tags that are used on the plans |
Baseline Building |
The baseline building will have an exhaust system that corresponds to the proposed design. The name can be identical to that used for the proposed design or some other appropriate name may be used. |
Exhaust Fan System Modeling Method |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
Software commonly models fans in three ways. See definition for supply system modeling method. |
Units |
List: Power-Per-Unit-Flow, Static Pressure, or Brake Horsepower |
Input Restrictions |
As designed |
Baseline Building |
If the proposed design uses the power-per-unit-flow method, the baseline building shall also use this method, otherwise the baseline building shall use the static pressure method |
Exhaust Fan Rated Capacity |
|
---|---|
Applicability |
All exhaust systems |
Definition |
The rated design airflow rate of the exhaust fan system. This building descriptor defines the 100% flow case for the part-flow curve. Actual airflow is the sum of the flow specified for each thermal zone, as modified by the schedule for each thermal zone. |
Units |
cfm |
Input Restrictions |
As designed |
Baseline Building |
Same as the proposed design except that baseline building kitchen exhaust rate may not exceed the maximum levels defined by Section 3.6.5.3 of this document |
Fan Control Method |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
A description of how the exhaust fan(s) are controlled. The options include:
|
Units |
List (see above) |
Input Restrictions |
As designed, however, when exhaust fan flow at the thermal zone level is varied through a schedule, one of the variable-flow options shall be specified |
Baseline Building |
The baseline building exhaust fan control shall generally be the same as the proposed design. Exceptions: Exhaust fans s serving laboratory spaces shall reduce the exhaust air volume during unoccupied periods to the largest of 50% of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards as described in Section 3.6.5.3 under descriptor Laboratory: Exhaust Minimum Airflow Rate. |
Exhaust Fan Schedule |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
A schedule that indicates when the exhaust fan system is available for operation. Exhaust fan flow is specified at the thermal zone level. |
Units |
Data structure: schedule, on/off |
Input Restrictions |
As designed |
Baseline Building |
Same as the proposed design for exhaust fans not serving kitchen or laboratory spaces For kitchen and laboratory zone exhaust, refer to Section 3.6.5.3 of this document |
Exhaust Fan Brake Horsepower |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
The design shaft brake horsepower of the exhaust fan(s) |
Units |
Brake horsepower (bhp) |
Input Restrictions |
As designed |
Baseline Building |
The bhp for the baseline building is the total system fan horsepower from Table 53 of this document multiplied by the exhaust fan ratio |
Exhaust Fan Design Static Pressure |
|
---|---|
Applicability |
Any system with return or relief fans that uses the static pressure method |
Definition |
The design static pressure for exhaust fan system. This is important for both fan electric energy usage and duct heat gain calculations. |
Units |
Inches of water column (in. H2O) |
Input Restrictions |
As designed for exhaust fans not serving kitchens. The design static pressure for the exhaust fan does not need to be specified if the exhaust fan bhp is specified. |
Baseline Building |
The exhaust fan static pressure for the baseline building would be equal to the total fan system static pressure (specified in section Supply Fan Static Pressure) multiplied by the exhaust fan ratio Exhaust Fan Static Pressure = (Exhaust Fan BHP x 6356 x 0.65)/cfm exhaust |
Exhaust Fan Efficiency |
|
---|---|
Applicability |
Any exhaust fan system that uses the static pressure method |
Definition |
The efficiency of the exhaust fan at rated capacity; this is the static efficiency and does not include losses through the motor |
Units |
Unitless |
Input Restrictions |
As designed. The exhaust fan efficiency does not need to be specified if the return fan bhp is specified. |
Baseline Building |
For baseline system, fan efficiency is 65% |
Exhaust Fan Motor Efficiency |
|
---|---|
Applicability |
All exhaust fan systems |
Definition |
The full-load efficiency of the motor serving the exhaust fan |
Units |
Unitless |
Input Restrictions |
As designed |
Baseline Building |
From Table G3.9.1 of Standard 90.1-2019 for the next motor size greater than the bhp calculated, through the process described above, using a totally enclosed fan motor at 1800 rpm |
Fan Part-Flow Power Curve |
|
---|---|
Applicability |
All variable flow exhaust fan systems |
Definition |
A part-load power curve that represents the power draw of the exhaust fan as a function of the airflow |
Units |
Unitless ratio |
Input Restrictions |
As designed. The default fan curve shall be selected from Equation (10) and Table 57 for the type of fan specified in the proposed design. |
Baseline Building |
Same as proposed |
Exhaust Fan Power Index |
|
---|---|
Applicability |
All exhaust systems |
Definition |
The fan power of the exhaust fan per unit of flow. This building descriptor is applicable only with the power-per-unit-flow method. |
Units |
kW/cfm |
Input Restrictions |
As designed |
Baseline Building |
The fan system power from Table 53 multiplied by the exhaust fan ratio |