Maximum Outside Air Ratio |
|
---|---|
Applicability |
All systems with modulating outside air dampers |
Definition |
The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
Units |
Ratio |
Input Restrictions |
As designed. Maximum of 1.0. |
Baseline Building |
1.0 for all systems with economizers. For others, equal to the ratio of required outdoor air to the peak supply airflow at design conditions. |
Design Outside Airflow |
|
---|---|
Applicability |
All systems with outside air dampers |
Definition |
The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside airflow for each of the zones served by the system. |
Units |
cfm |
Input Restrictions |
As designed |
Baseline Building |
Same as proposed. This input along with occupant density determines if the zones served by this system are required to have demand control ventilation. This value might also be different for buildings using the ASHRAE 62.1 Ventilation Rate Procedure as described in Section 3.6.5.5 of this document. See Section 3.6.5.4 of this document for ventilation control method at the zone level. |
Outdoor Air Control Method |
|
---|---|
Applicability |
All HVAC systems that deliver outside air to multiple zones. (These requirements don’t apply to systems supplying air to single zones.) |
Definition |
The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system reports its outside air requirements hourly. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information hourly. Options include:
The quantity of outside air can be controlled in a number of ways, but a common method is to install a flow station at the outside air supply that modulates the position of the outside air and return dampers to maintain the desired outside airflow. With the average flow, a CO2 sensor in the return air duct is another way to control the position of the outside air and return dampers. |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
Same as proposed. See Section 3.6.5.5 for details. |
Outdoor Air Minimum Flow Schedule |
|
---|---|
Applicability |
All HVAC systems that deliver outside air |
Definition |
The schedule shall allow the system to provide the minimum system outdoor air requirements based on a time of day schedule. This input is specifically helpful when ventilation intake needs to be modified for fan cycling operation during unoccupied hours. This schedule would be an “on/off” schedule that determines when the design outside air is supplied by the system. |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
In the following cases minimum design ventilation will be provided based on the HVAC availability schedule and outside air dampers shall be closed during night cycle and morning warm-up:
In all other cases outside air shall be provided anytime the system operates. |