3.7.4.2 Air-Side Economizers

90.1-2019

Economizer Control Type

Applicability

All systems with an air-side economizer

Definition

An air-side economizer increases outside air ventilation during periods when cooling loads can be reduced from increased outside airflow. The control types include:

  • No economizer.
  • Fixed dry-bulb. The economizer is enabled when the temperature of the outside air is lower than a fixed setpoint.
  • Differential dry-bulb. The economizer is enabled when the temperature of the outside air is lower than the return air temperature.
  • Fixed enthalpy. The economizer is enabled when the enthalpy of the outside air is lower than a fixed setpoint
  • Differential enthalpy. The economizer is enabled when the enthalpy of the outside air is lower than the return air enthalpy.
  • Differential dry-bulb and enthalpy. The economizer is enabled when the outside air dry-bulb is less than the return air dry-bulb AND the outside air enthalpy is less than the return air enthalpy.
  • Fixed dewpoint and dry-bulb. The economizer is enabled when the dewpoint and dry-bulb temperature of the outside air are below the specified setpoints.

Units

List (see above)

Input Restrictions

As designed

Baseline Building

Outdoor air economizers shall not be included in baseline HVAC systems 1, 2, 9, and 10. Outside air economizers shall be included in baseline HVAC systems 3 through 8, 11, 12, and 13, in climate zones 2B, 3B, 3C, 4C, 5B, 5C, 6B, 7, and 8. Economizers are not required in other climate zones. Economizer control shall be fixed dry bulb with a temperature setpoint as indicated under Economizer High-Temperature Lockout below.

Exceptions: Economizers shall not be included for systems meeting one or more of the exceptions listed below.

a. Systems that include gas-phase air cleaning to meet the requirements of Section 6.1.2 in Standard 62.1. In the scenario, where there isn’t a one-to-one mapping between the systems in the proposed and baseline building, all systems serving the zones that qualify for the exception in the proposed building will not have economizers.

b. Where the use of outdoor air for cooling will affect supermarket open refrigerated casework systems. This exception shall only be used if the system in the proposed design does not use an economizer.

c. Systems serving computer rooms which are baseline systems 3-4 shall not have an economizer. Systems that server computer rooms that are baseline system 11 shall include an integrated fluid economizer meeting the requirements of Standard 90.1-2019 Section 6.5.1.2, also summarized below and in Section 3.8.4 of this manual.

Fluid Economizers

Fluid economizer systems shall be capable of providing up to 100% of the expected system cooling load at outdoor air temperatures of 50°F dry bulb/45°F wet bulb and below. Exceptions:

  • Systems primarily serving computer rooms in which 100% of the expected system cooling load at the dry-bulb and wet-bulb temperatures listed in Table 6.5.1.2.1 of Standard 90.1-2019 is met with water-cooled fluid economizers..
  • Systems primarily serving computer rooms in which 100% of the expected system cooling load at the dry-bulb temperatures listed in Table 6.5.1.2.1 of Standard 90.1-2019 is met with air-cooled fluid economizers.
  • Systems where dehumidification requirements cannot be met using outdoor air temperatures of 50°F dry-bulb/45°F wet-bulb and where 100% of the expected system cooling load at 45°F dry-bulb/40°F wet-bulb is met with water-cooled fluid economizers.

 

Economizer Integration

Applicability

Airside economizers

Definition

This input specifies whether or not the economizer is integrated with mechanical cooling. It is up to the modeling software to translate this into software-specific inputs to model this feature. The input could take the following values:

  • Non-integrated: The system runs the economizer as the first stage of cooling. When the economizer is unable to meet the load, the economizer returns the outside air damper to the minimum position and the compressor turns on as the second stage of cooling.
  • Integrated: The system can operate with the economizer fully open to outside air and mechanical cooling active (compressor running) simultaneously, even on the lowest cooling stage.

Units

List: Non-integrated, Integrated

Input Restrictions

 As designed

Baseline Building

Integrated

 

Economizer High-Temperature Lockout

Applicability

Systems with fixed dry-bulb economizer

Definition

The outside air setpoint temperature above which the economizer will return to minimum position

Units

Degrees Fahrenheit (°F)

Input Restrictions

As designed

Baseline Building

Economizer control shall be fixed dry bulb with a temperature setpoint of 70°F in climate zones 5A and 6A and 75°F in all other climate zones where economizers are required

 

Economizer Low-Temperature Lockout

Applicability

Systems with air-side economizers

Definition

A feature that permits the lockout of economizer operation (return to minimum outside air position) when the outside air temperature is below the lockout setpoint

Units

Degrees Fahrenheit (°F)

Input Restrictions

As designed

Baseline Building

None

 

Economizer High Enthalpy Lockout

Applicability

Systems with fixed enthalpy or differential enthalpy economizers

Definition

The outside air enthalpy above which the economizer will return to minimum position

Units

Btu/lb

Input Restrictions

As designed. The default is 28 Btu/lb. (High altitude locations may require different setpoints.) The software shall apply a fixed offset and add 2 Btu/lb to the user-entered value.

Baseline Building

Not applicable since no baseline building system has an enthalpy economizer