Chiller Name | |
Applicability | All chillers |
---|---|
Definition | A unique descriptor for each chiller |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | Chillers are only designated when the baseline system is of type 7 (VAV with reheat) or 8 (VAV with PFP Boxes) (see Table G3.1.1B). |
Chiller Type | |||||||||
Applicability | All chillers | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition | The type of chiller, either a vapor-compression chiller or an absorption chiller. Vapor compression chillers operate on the reverse-Rankine cycle, using mechanical energy to compress the refrigerant, and include:
|
||||||||
Units | List (see above) | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules |
The baseline building chiller is based on the design capacity of the proposed design as follows from ASHRAE 90.1 Appendix G:
|
Number of Identical Chiller Units | |
Applicability | All chillers |
---|---|
Definition | The number of identical units for staging. |
Units | None |
Input Restrictions | As designed. Default is 1. |
Baseline Rules | From [bookref id="type-and-number-of-chillers"] above, there is one chiller if the cooling load is 300 tons or less and two equally sized chillers for loads between 300 and 600 tons. For loads above 600 tons, two or more chillers of equal size are used, with no chiller larger than 800 tons. |
Chiller Fuel | |
Applicability | All chillers |
---|---|
Definition | The fuel source for the chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Electricity |
Chiller Rated Capacity | |
Applicability | All chillers |
---|---|
Definition | The cooling capacity of a piece of heating equipment at rated conditions. |
Units | Btu/h or tons |
Input Restrictions | As designed. If unmet load hours are greater than 300, the chiller may have to be made larger. |
Baseline Rules | Determine loads for baseline building and oversize by 15%. |
Chiller Rated Efficiency | |
Applicability | All chillers |
---|---|
Definition | The Coefficient of Performance (COP) at ARI rated conditions. |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | With the ASHRAE Standard 90.1-2007 baseline, use the minimum values of efficiency from either Table 6.8.1C for various types of chillers or the values from Tables 6.8.1H, 6.8.1I or 6.8.1J for centrifugal chillers. With the ASHRAE Standard 90.1-2001 baseline, use the minimum values of efficiency from either Table 6.2.1C for various types of chillers, or the values from Tables 6.2.1H, 6. 2.1I or 6. 2.1J for centrifugal chillers. |
Chiller Minimum Unloading Ratio | |||||||||||||||
Applicability | All chillers | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
The minimum unloading capacity of a chiller expressed as a fraction of the rated capacity. Below this level the chiller must cycle to meet the load.
|
||||||||||||||
Units | Percent (%) | ||||||||||||||
Input Restrictions | As designed. If the user does not employ the default values, supporting documentation is required. | ||||||||||||||
Baseline Rules | Use defaults listed above. |
Chiller Cooling Capacity Adjustment Curve | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves or other functions that represent the available total cooling capacity as a function of evaporator and condenser conditions and perhaps other operating conditions. The default curves are given as follows: (6.8.2-1) $$ Q_{available} = CAP \_ FT \times Q_{rated}$$ For air-cooled chillers: (6.8.2-2) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws}\right. ^2 + d \times t_{odb} + e \times \left. t_{odb}\right. ^2 + f \times t_{chws} \times t_{odb}$$ For water-cooled chillers: (6.8.2-3) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws} \right. ^2 + d \times t_{cws} + e \times \left. t_{cws} \right. ^2 + f \times t_{chws} \times t_{cws}$$ where
Note: If an air-cooled unit employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. [table title="Default Capacity Coefficients – Electric Air-Cooled Chillers" id="default-capacity-coefficients-–-electric-air---cooled-chillers"]
[table title="Default Capacity Coefficients – Electric Water-Cooled Chillers" id="default-capacity-coefficients-–-electric-water---cooled-chillers"]
[table title="Default Capacity Coefficients – Fuel- & Steam-Source Water-Cooled Chillers" id="default-capacity-coefficients-–-fuel--&-steam---source-water---cooled-chillers"]
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves, other appropriate functions, or use default curves. If the default curves are overridden, supporting documentation is required. | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Electric Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of an electric chiller as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.8.2-4) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ EIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ air-cooled \enspace EIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{odb} + \ e \times \left. t_{odb}\right. ^2+ \ f \times t_{chws} \times t_{odb}$$ $$ water-cooled \enspace EIR\_FT = a + b \times t_{chws}+ c \times \left. t_{chws}\right. ^2 + d \times t_{cws} + e \times \left. t_{cws}\right. ^2+ f \times t_{chws} \times t_{cws}$$ $$P_{operating} = P_{rated} \times EIR\_FPLR \times EIR\_FT \times CAP\_FT $$ where
Note: If an air-cooled chiller employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. [table title="Default Efficiency EIR-FT Coefficients – Air-Cooled Chillers" id="default-efficiency-eir---ft-coefficients-–-air---cooled-chillers"]
[table title="Default Efficiency EIR-FT Coefficients – Water-Cooled Chiller" id="default-efficiency-eir--ft-coefficients-–-water---cooled-chiller"]
[table title="Default Efficiency EIR-FPLR Coefficients – Air-Cooled Chillers" id="default-efficiency-eir---fplr-coefficients-–-air---cooled-chillers"]
[table title="Default Efficiency EIR-FPLR Coefficients – Water-Cooled Chillers" id="default-efficiency-eir---fplr-coefficients-–-water---cooled-chillers"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Fuel and Steam Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of a fuel-fired or steam chiller as a function of evaporator conditions, condenser conditions, and part-load ratio. The default curves are given as follows: (6.8.2-5) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{cws} + \ e \times \left. t_{cws}\right. ^2+ \ f \times t_{chws} \times t_{cws}$$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT \times CAP\_FT $$ Default Curves for Direct-Fired Double Effect Absorption Chillers (6.8.2-6) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT1 = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 $$ $$ FIR\_FT2 = d + e \times t_{cws} + \ f \times \left. t_{cws}\right. ^2 $$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT1 \times FIR\_FT2 \times CAP\_FT $$ The default curves for engine driven chillers are the same format as those for the Steam-Driven Single and Double Effect Absorption Chillers but there are three sets of curves for different ranges of operation based on the engine speed. where
[table title="Default FIR-FPLR coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers" id="default-fir---fplr-coefficients-–-fuel---&-steam---source-water---cooled-absorption-chillers"]
[table title="Default FIR-FPLR coefficients – Engine Driven Chillers" id="default-fir---fplr-coefficients-–-engine-driven-chillers"]
[table title="Default FIR-FT coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers" id="default-fir---ft-coefficients-–-fuel---&-steam---source-water---cooled-absorption-chillers"]
[table title="Default FIR-FT coefficients – Engine Driven Chillers" id="default-fir---ft-coefficients-–-engine-driven-chillers"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Chilled Water Supply Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water supply temperature of the chiller at design conditions |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | The baseline chilled water supply temperature is set to 44°F. |
Chilled Water Return Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water return temperature setpoint |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | The baseline chilled water return temperature is set to 56°F. |
Chilled Water Supply Temperature Reset | |
Applicability | All chillers |
---|---|
Definition | The reset schedule for the chilled water supply temperature. The chilled water setpoint may be reset based on demand or outdoor air temperature. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. The default is [bookref id="chilled-water-supply-temperature-reset-schedule"]. |
Baseline Rules |
The baseline chilled water supply temperature is reset from 44°F to 54°F based on outdoor air temperature as shown in the figure below. [figure title="Chilled Water Supply Temperature Reset Schedule" id="chilled-water-supply-temperature-reset-schedule"][/figure] |
Condenser Type | |
Applicability | All chillers |
---|---|
Definition | The type of condenser for a chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | The baseline chiller is always assumed to have a water-cooled condenser, although the chiller type will change depending on the design capacity. If the chiller size is less than 600 tons, the baseline chiller is a water-cooled screw; if the capacity is greater than or equal to 600 tons, the baseline chiller is a water-cooled centrifugal chiller. |
Air-Cooled Condenser Power | |
Applicability | All chillers |
---|---|
Definition | The energy usage of the condenser fan(s) at design conditions on an air-cooled chiller. This unit should only be used for chillers composed of separate evaporator and condenser sections where the fan energy is not part of the chiller COP. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. The user must enter data for remote air-cooled condensing units. |
Baseline Rules | Not applicable, since all baseline chillers have water-cooled condensers. |
Chiller Name | |
Applicability | All chillers |
---|---|
Definition | A unique descriptor for each chiller |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | Chillers are only designated when the baseline system is of type 7 (VAV with reheat) or 8 (VAV with PFP Boxes) (see Table G3.1.1B). |
Chiller Type | |||||||||
Applicability | All chillers | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition | The type of chiller, either a vapor-compression chiller or an absorption chiller. Vapor compression chillers operate on the reverse-Rankine cycle, using mechanical energy to compress the refrigerant, and include:
|
||||||||
Units | List (see above) | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules |
The baseline building chiller is based on the design capacity of the proposed design as follows from ASHRAE 90.1 Appendix G:
|
Number of Identical Chiller Units | |
Applicability | All chillers |
---|---|
Definition | The number of identical units for staging. |
Units | None |
Input Restrictions | As designed. Default is 1. |
Baseline Rules | From [bookref id="type-and-number-of-chillers"] above, there is one chiller if the cooling load is 300 tons or less and two equally sized chillers for loads between 300 and 600 tons. For loads above 600 tons, two or more chillers of equal size are used, with no chiller larger than 800 tons. |
Chiller Fuel | |
Applicability | All chillers |
---|---|
Definition | The fuel source for the chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Electricity |
Chiller Rated Capacity | |
Applicability | All chillers |
---|---|
Definition | The cooling capacity of a piece of heating equipment at rated conditions. |
Units | Btu/h or tons |
Input Restrictions | As designed. If unmet load hours are greater than 300, the chiller may have to be made larger. |
Baseline Rules | Determine loads for baseline building and oversize by 15%. |
Chiller Rated Efficiency | |
Applicability | All chillers |
---|---|
Definition | The Coefficient of Performance (COP) at ARI rated conditions. |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | With the ASHRAE Standard 90.1-2007 baseline, use the minimum values of efficiency from either Table 6.8.1C for various types of chillers or the values from Tables 6.8.1H, 6.8.1I or 6.8.1J for centrifugal chillers. |
Chiller Minimum Unloading Ratio | |||||||||||||||
Applicability | All chillers | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
The minimum unloading capacity of a chiller expressed as a fraction of the rated capacity. Below this level the chiller must cycle to meet the load.
|
||||||||||||||
Units | Percent (%) | ||||||||||||||
Input Restrictions | As designed. If the user does not employ the default values, supporting documentation is required. | ||||||||||||||
Baseline Rules | Use defaults listed above. |
Chiller Cooling Capacity Adjustment Curve | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves or other functions that represent the available total cooling capacity as a function of evaporator and condenser conditions and perhaps other operating conditions. The default curves are given as follows: (6.8.2-1) $$ Q_{available} = CAP \_ FT \times Q_{rated}$$ For air-cooled chillers: (6.8.2-2) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws}\right. ^2 + d \times t_{odb} + e \times \left. t_{odb}\right. ^2 + f \times t_{chws} \times t_{odb}$$ For water-cooled chillers: (6.8.2-3) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws} \right. ^2 + d \times t_{cws} + e \times \left. t_{cws} \right. ^2 + f \times t_{chws} \times t_{cws}$$ where
Note: If an air-cooled unit employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. [table title="Default Capacity Coefficients – Electric Air-Cooled Chillers" id="default-capacity-coefficients-–-electric-air---cooled-chillers"]
[table title="Default Capacity Coefficients – Electric Water-Cooled Chillers" id="default-capacity-coefficients-–-electric-water---cooled-chillers"]
[table title="Default Capacity Coefficients – Fuel- & Steam-Source Water-Cooled Chillers" id="default-capacity-coefficients-–-fuel--&-steam---source-water---cooled-chillers"]
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves, other appropriate functions, or use default curves. If the default curves are overridden, supporting documentation is required. | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Electric Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of an electric chiller as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.8.2-4) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ EIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ air-cooled \enspace EIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{odb} + \ e \times \left. t_{odb}\right. ^2+ \ f \times t_{chws} \times t_{odb}$$ $$ water-cooled \enspace EIR\_FT = a + b \times t_{chws}+ c \times \left. t_{chws}\right. ^2 + d \times t_{cws} + e \times \left. t_{cws}\right. ^2+ f \times t_{chws} \times t_{cws}$$ $$P_{operating} = P_{rated} \times EIR\_FPLR \times EIR\_FT \times CAP\_FT $$ where
Note: If an air-cooled chiller employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. [table title="Default Efficiency EIR-FT Coefficients – Air-Cooled Chillers" id="default-efficiency-eir---ft-coefficients-–-air---cooled-chillers"]
[table title="Default Efficiency EIR-FT Coefficients – Water-Cooled Chiller" id="default-efficiency-eir--ft-coefficients-–-water---cooled-chiller"]
[table title="Default Efficiency EIR-FPLR Coefficients – Air-Cooled Chillers" id="default-efficiency-eir---fplr-coefficients-–-air---cooled-chillers"]
[table title="Default Efficiency EIR-FPLR Coefficients – Water-Cooled Chillers" id="default-efficiency-eir---fplr-coefficients-–-water---cooled-chillers"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Fuel and Steam Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of a fuel-fired or steam chiller as a function of evaporator conditions, condenser conditions, and part-load ratio. The default curves are given as follows: (6.8.2-5) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{cws} + \ e \times \left. t_{cws}\right. ^2+ \ f \times t_{chws} \times t_{cws}$$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT \times CAP\_FT $$ Default Curves for Direct-Fired Double Effect Absorption Chillers (6.8.2-6) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT1 = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 $$ $$ FIR\_FT2 = d + e \times t_{cws} + \ f \times \left. t_{cws}\right. ^2 $$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT1 \times FIR\_FT2 \times CAP\_FT $$ The default curves for engine driven chillers are the same format as those for the Steam-Driven Single and Double Effect Absorption Chillers but there are three sets of curves for different ranges of operation based on the engine speed. where
[table title="Default FIR-FPLR coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers" id="default-fir---fplr-coefficients-–-fuel---&-steam---source-water---cooled-absorption-chillers"]
[table title="Default FIR-FPLR coefficients – Engine Driven Chillers" id="default-fir---fplr-coefficients-–-engine-driven-chillers"]
[table title="Default FIR-FT coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers" id="default-fir---ft-coefficients-–-fuel---&-steam---source-water---cooled-absorption-chillers"]
[table title="Default FIR-FT coefficients – Engine Driven Chillers" id="default-fir---ft-coefficients-–-engine-driven-chillers"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Chilled Water Supply Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water supply temperature of the chiller at design conditions |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | The baseline chilled water supply temperature is set to 44°F. |
Chilled Water Return Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water return temperature setpoint |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | The baseline chilled water return temperature is set to 56°F. |
Chilled Water Supply Temperature Reset | |
Applicability | All chillers |
---|---|
Definition | The reset schedule for the chilled water supply temperature. The chilled water setpoint may be reset based on demand or outdoor air temperature. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. The default is [bookref id="chilled-water-supply-temperature-reset-schedule"]. |
Baseline Rules |
The baseline chilled water supply temperature is reset from 44°F to 54°F based on outdoor air temperature as shown in the figure below. [figure title="Chilled Water Supply Temperature Reset Schedule" id="chilled-water-supply-temperature-reset-schedule"][/figure] |
Condenser Type | |
Applicability | All chillers |
---|---|
Definition | The type of condenser for a chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | The baseline chiller is always assumed to have a water-cooled condenser, although the chiller type will change depending on the design capacity. If the chiller size is less than 600 tons, the baseline chiller is a water-cooled screw; if the capacity is greater than or equal to 600 tons, the baseline chiller is a water-cooled centrifugal chiller. |
Air-Cooled Condenser Power | |
Applicability | All chillers |
---|---|
Definition | The energy usage of the condenser fan(s) at design conditions on an air-cooled chiller. This unit should only be used for chillers composed of separate evaporator and condenser sections where the fan energy is not part of the chiller COP. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. The user must enter data for remote air-cooled condensing units. |
Baseline Rules | Not applicable, since all baseline chillers have water-cooled condensers. |
Chiller Name | |
Applicability | All chillers |
---|---|
Definition | A unique descriptor for each chiller |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Baseline Rules | Chillers are only designated when the baseline system is of type 7 (VAV with reheat) or 8 (VAV with PFP Boxes) (see Table G3.1.1B). |
Chiller Type | |||||||||
Applicability | All chillers | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition | The type of chiller, either a vapor-compression chiller or an absorption chiller. Vapor compression chillers operate on the reverse-Rankine cycle, using mechanical energy to compress the refrigerant, and include:
|
||||||||
Units | List (see above) | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules |
The baseline building chiller is based on the design capacity of the proposed design as follows from ASHRAE 90.1 Appendix G:
Table 6.8.2-1: Type and Number of Chillers
|
Number of Identical Chiller Units | |
Applicability | All chillers |
---|---|
Definition | The number of identical units for staging. |
Units | None |
Input Restrictions | As designed. Default is 1. |
Baseline Rules | From Table 7.8.2-1 above, there is one chiller if the cooling load is 300 tons or less and two equally sized chillers for loads between 300 and 600 tons. For loads above 600 tons, two or more chillers of equal size are used, with no chiller larger than 800 tons. |
Chiller Fuel | |
Applicability | All chillers |
---|---|
Definition | The fuel source for the chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. |
Baseline Rules | Electricity |
Chiller Rated Capacity | |
Applicability | All chillers |
---|---|
Definition | The cooling capacity of a piece of heating equipment at rated conditions. |
Units | Btu/h or tons |
Input Restrictions | As designed. If unmet load hours are greater than 300, the chiller may have to be made larger. |
Baseline Rules | Determine loads for baseline building and oversize by 15%. |
Chiller Rated Efficiency | |
Applicability | All chillers |
---|---|
Definition | The Coefficient of Performance (COP) at ARI rated conditions. |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | With the ASHRAE Standard 90.1-2007 baseline, use the minimum values of efficiency from either Table 6.8.1C for various types of chillers or the values from Tables 6.8.1H, 6.8.1I or 6.8.1J for centrifugal chillers. |
Chiller Minimum Unloading Ratio | |||||||||||||||
Applicability | All chillers | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
The minimum unloading capacity of a chiller expressed as a fraction of the rated capacity. Below this level the chiller must cycle to meet the load.
|
||||||||||||||
Units | Percent (%) | ||||||||||||||
Input Restrictions | As designed. If the user does not employ the default values, supporting documentation is required. | ||||||||||||||
Baseline Rules | Use defaults listed above. |
Chiller Cooling Capacity Adjustment Curve | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves or other functions that represent the available total cooling capacity as a function of evaporator and condenser conditions and perhaps other operating conditions. The default curves are given as follows: (6.8.2-1) $$ Q_{available} = CAP \_ FT \times Q_{rated}$$ For air-cooled chillers: (6.8.2-2) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws}\right. ^2 + d \times t_{odb} + e \times \left. t_{odb}\right. ^2 + f \times t_{chws} \times t_{odb}$$ For water-cooled chillers: (6.8.2-3) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws} \right. ^2 + d \times t_{cws} + e \times \left. t_{cws} \right. ^2 + f \times t_{chws} \times t_{cws}$$ where
Note: If an air-cooled unit employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit.
Table 6.8.2-3: Default Capacity Coefficients – Electric Air-Cooled Chillers
Table 6.8.2-4: Default Capacity Coefficients – Electric Water-Cooled Chillers
Table 6.8.2-5: Default Capacity Coefficients – Fuel- & Steam-Source Water-Cooled Chillers
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves, other appropriate functions, or use default curves. If the default curves are overridden, supporting documentation is required. | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Electric Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of an electric chiller as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.8.2-4) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ EIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ air-cooled \enspace EIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{odb} + \ e \times \left. t_{odb}\right. ^2+ \ f \times t_{chws} \times t_{odb}$$ $$ water-cooled \enspace EIR\_FT = a + b \times t_{chws}+ c \times \left. t_{chws}\right. ^2 + d \times t_{cws} + e \times \left. t_{cws}\right. ^2+ f \times t_{chws} \times t_{cws}$$ $$P_{operating} = P_{rated} \times EIR\_FPLR \times EIR\_FT \times CAP\_FT $$ where
Note: If an air-cooled chiller employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit.
Table 6.8.2-6: Default Efficiency EIR-FT Coefficients – Air-Cooled Chillers
Table 6.8.2-7: Default Efficiency EIR-FT Coefficients – Water-Cooled Chiller
Table 6.8.2-8: Default Efficiency EIR-FPLR Coefficients – Air-Cooled Chillers
Table 6.8.2-9: Default Efficiency EIR-FPLR Coefficients – Water-Cooled Chillers
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Fuel and Steam Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of a fuel-fired or steam chiller as a function of evaporator conditions, condenser conditions, and part-load ratio. The default curves are given as follows: (6.8.2-5) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{cws} + \ e \times \left. t_{cws}\right. ^2+ \ f \times t_{chws} \times t_{cws}$$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT \times CAP\_FT $$ Default Curves for Direct-Fired Double Effect Absorption Chillers (6.8.2-6) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT1 = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 $$ $$ FIR\_FT2 = d + e \times t_{cws} + \ f \times \left. t_{cws}\right. ^2 $$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT1 \times FIR\_FT2 \times CAP\_FT $$ The default curves for engine driven chillers are the same format as those for the Steam-Driven Single and Double Effect Absorption Chillers but there are three sets of curves for different ranges of operation based on the engine speed. where
Table 6.8.2-10: Default FIR-FPLR coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers
Table 6.8.2-11: Default FIR-FPLR coefficients – Engine Driven Chillers
Table 6.8.2-12: Default FIR-FT coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers
Table 6.8.2-13: Default FIR-FT coefficients – Engine Driven Chillers
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Rules | Use default curves. |
Chilled Water Supply Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water supply temperature of the chiller at design conditions |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | The baseline chilled water supply temperature is set to 44°F. |
Chilled Water Return Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water return temperature setpoint |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Baseline Rules | The baseline chilled water return temperature is set to 56°F. |
Chilled Water Supply Temperature Reset | |
Applicability | All chillers |
---|---|
Definition | The reset schedule for the chilled water supply temperature. The chilled water setpoint may be reset based on demand or outdoor air temperature. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed. The default is Figure 6.8.2-1. |
Baseline Rules |
The baseline chilled water supply temperature is reset from 44°F to 54°F based on outdoor air temperature as shown in the figure below.
Figure 6.8.2-1: Chilled Water Supply Temperature Reset Schedule |
Condenser Type | |
Applicability | All chillers |
---|---|
Definition | The type of condenser for a chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | The baseline chiller is always assumed to have a water-cooled condenser, although the chiller type will change depending on the design capacity. If the chiller size is less than 600 tons, the baseline chiller is a water-cooled screw; if the capacity is greater than or equal to 600 tons, the baseline chiller is a water-cooled centrifugal chiller. |
Air-Cooled Condenser Power | |
Applicability | All chillers |
---|---|
Definition | The energy usage of the condenser fan(s) at design conditions on an air-cooled chiller. This unit should only be used for chillers composed of separate evaporator and condenser sections where the fan energy is not part of the chiller COP. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. The user must enter data for remote air-cooled condensing units. |
Baseline Rules | Not applicable, since all baseline chillers have water-cooled condensers. |
Chiller Name |
|
---|---|
Applicability |
All chillers |
Definition |
A unique descriptor for each chiller |
Units |
Text, unique |
Input Restrictions |
User entry. Where applicable, this should match the tags that are used on the plans. |
Baseline Rules |
Baseline HVAC systems 7, 8, 11, 12, and 13 have chillers. |
Chiller Type |
|||||||||
---|---|---|---|---|---|---|---|---|---|
Applicability |
All chillers |
||||||||
Definition |
The type of chiller, either a vapor-compression chiller or an absorption chiller.
|
||||||||
Units |
List (see above) |
||||||||
Input Restrictions |
As designed |
||||||||
Baseline Rules |
The baseline building chiller is based on the baseline building peak cooling load, as follows: Table 3.8.2-1: Chiller Type
|
Number of Identical Chiller Units |
|
---|---|
Applicability |
All chillers |
Definition |
The number of identical units for staging. |
Units |
Unitless integer |
Input Restrictions |
As designed. Default is 1. |
Baseline Rules |
There is one chiller if the cooling load is 300 tons or less and two equally sized chillers for loads between 300 and 600 tons. For loads above 600 tons, two or more chillers of equal size are used, with no chiller larger than 800 tons. See Table 3.8.2-1. |
Chiller Fuel |
|||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All chillers |
||||||||||||||||||||||||||||||||||||||||
Definition |
The fuel source for the chiller. The choices are:
|
||||||||||||||||||||||||||||||||||||||||
Units |
List (see above) This input is restricted, based on the choice of Chiller Type, according to the following rules: Table 3.8.2-2: Chiller Fuel
|
||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. |
||||||||||||||||||||||||||||||||||||||||
Baseline Rules |
Electricity |
Chiller Rated Capacity |
|
---|---|
Applicability |
All chillers |
Definition |
The cooling capacity of a piece of heating equipment at rated conditions. |
Units |
Btu/h or tons |
Input Restrictions |
As designed. If unmet load hours are greater than 300, the chiller may have to be made larger. |
Baseline Rules |
Determine loads for baseline building and oversize by 15%. |
Chiller Rated Efficiency |
||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All chillers |
|||||||||||||||||||||||||||||||||||||||||||
Definition |
The efficiency of the chiller expressed as EER for air cooled chillers, kW/ton for water cooled, positive displacement chillers, and COP for fuel-fired and heat driven chillers. COP is also sometimes used for electric chillers. The applicable test procedure is AHRI Standard 550/590. The test conditions for the full load (FL) rating are summarized below:
Chillers are also rated at part load conditions known as IPLV (integrated part load value). The IPLV is the weighted average of the chiller efficiency at 100%, 75%, 50% and 25%. The corresponding weights for these part-load conditions are are 17%, 39%, 33%, and 11%. |
|||||||||||||||||||||||||||||||||||||||||||
Units |
kW/ton, EER or COP, depending on chiller type |
|||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed, but chillers must meet minimum efficiency standards |
|||||||||||||||||||||||||||||||||||||||||||
Baseline Rules |
The baseline chiller efficiencies are as follows: Table 3.8.2-3: Baseline Chiller Rated Efficiency
|
Chiller Minimum Unloading Ratio |
|||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All chillers |
||||||||||||||
Definition |
The minimum unloading capacity of a chiller expressed as a fraction of the rated capacity. Below this level the chiller must cycle to meet the load. The following are default values for various types of chillers Table 3.8.2-4: Baseline Chiller Minimum Unloading Ratio
|
||||||||||||||
Units |
Percent (%) |
||||||||||||||
Input Restrictions |
As designed. If the user does not employ the default values, supporting documentation is required. |
||||||||||||||
Baseline Rules |
The baseline HVAC chiller will be either a screw or centrifugal. Use the defaults for these chiller types from the above table: 15% for screw and 10% for centrifugal. |
Chiller Cooling Capacity Adjustment Curve |
|||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All chillers |
||||||||||||
Definition |
A curve or group of curves or other functions that represent the available total cooling capacity as a function of evaporator and condenser conditions and perhaps other operating conditions. The default curves are given as follows: (Equation 3.8.2-1) $$Q_{available} = CAP\_FT \times Q_{rated}$$ For air-cooled chillers: (Equation 3.8.2-2) $$CAP\_FT = a + b \cdot t_{chws} + c \cdot t_{chws}^{2} + d \cdot t_{odb} + e \cdot t_{odb}^{2} +f \cdot t_{chws} \cdot t_{odb}$$ For water-cooled chillers: (Equation 3.8.2-3) $$CAP\_FT = a + b \cdot t_{chws} + c \cdot t_{chws}^{2} + d \cdot t_{cws} + e \cdot t_{cws}^{2} +f \cdot t_{chws} \cdot t_{cws}$$ where
Note: If an air-cooled unit employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. |
||||||||||||
Units |
Data structure |
||||||||||||
Input Restrictions |
User may input curves, other appropriate functions, or use default curves. If the default curves are overridden, supporting documentation is required. |
||||||||||||
Baseline Rules |
Use default equations and coefficients for the baseline chillers.. |
Electric Chiller Cooling Efficiency Adjustment Curves |
|||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All chillers |
||||||||||||||||||
Definition |
A curve or group of curves that varies the cooling efficiency of an electric chiller as a function of evaporator conditions, condenser conditions and part-load ratio. Note that for variable-speed chillers, the part-load cooling efficiency curve is a function of both part-load ratio and leaving condenser water temperature. The default curves are given as follows: (Equation 3.8.2-4) $$PLR = \frac{Q_{operating}}{Q_{available}(t_{chws},t_{cws/odb})}$$ $$EIR\_FPLR = a + b \cdot PLR + c \cdot PLR^{2}$$ Variable speed $$EIR\_FPLR = a + b \cdot PLR + c \cdot PLR^{2} + d \cdot t_{cws} + e \cdot t_{cws}^{2} + f \cdot PLR \cdot t_{cws} + g \cdot PLR^{3} + h \cdot t_{cws}^{3} + i \cdot PLR^{2} \cdot t_{cws} + j \cdot PLR \cdot t_{cws}^{2}$$ Air cooled $$EIR\_FT = a + b \cdot t_{chws} + c \cdot t_{chws}^{2} + d \cdot t_{odb} + e \cdot t_{odb}^{2} + f \cdot t_{chws}\cdot t_{odb} $$ Water cooled $$EIR\_FT = a + b \cdot t_{chws} + c \cdot t_{chws}^{2} + d \cdot t_{cws} + e \cdot t_{cws}^{2} + f \cdot t_{chws}\cdot t_{cws} $$ Where
Note: If an air-cooled chiller employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. |
||||||||||||||||||
Units |
Data structure |
||||||||||||||||||
Input Restrictions |
User may input curves or use default curves. If defaults are overridden, supporting documentation is required. |
||||||||||||||||||
Baseline Rules |
Use default equations and coefficients for the baseline HVAC chillers. |
Fuel and Steam Chiller Cooling Efficiency Adjustment Curves |
|||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All chillers |
||||||||||||||||||||||||||||
Definition |
A curve or group of curves that varies the cooling efficiency of a fuel-fired or steam chiller as a function of evaporator conditions, condenser conditions, and part-load ratio. The default curves are given as follows: Default Curves for Steam-Driven Single and Double Effect Absorption Chillers (Equation 3.8.2-5) $$PLR = \frac{Q_{operating}}{Q_{available}(t_{chws},t_{cws/odb})}$$ $$FIR\_FPLR = a + b \cdot PLR + c \cdot PLR^{2}$$ $$FIR\_FT = a + b \cdot t_{chws} + c \cdot t_{chws}^{2} + d \cdot t_{cws} + e \cdot t_{cws}^{2} + f \cdot t_{chws} \cdot t_{cws}$$ Default Curves for Direct-Fired Double Effect Absorption Chillers (Equation 3.8.2-6) $$PLR = \frac{Q_{operating}}{Q_{available}(t_{chws},t_{cws/odb})}$$ $$FIR\_FPLR = a + b \cdot PLR + c \cdot PLR^{2}$$ $$FIR\_FT1 = a + b \cdot t_{chws} + c \cdot t_{chws}^{2}$$ $$FIR\_FT2 = d + e \cdot t_{cws} + f \cdot t_{cws}^{2}$$ $$Fuel_{partload} = Fuel_{rated} \cdot FIR\_FPLR \cdot FIR1\_FT1 \cdot FIR1\_FT2 \cdot CAP\_FT$$ The default curves for engine driven chillers are the same format as those for the Steam-Driven Single and Double Effect Absorption Chillers but there are three sets of curves for different ranges of operation based on the engine speed. where
|
||||||||||||||||||||||||||||
Units |
Data structure |
||||||||||||||||||||||||||||
Input Restrictions |
User may input curves or use default curves. If defaults are overridden, supporting documentation is required. |
||||||||||||||||||||||||||||
Baseline Rules |
Not applicable. The baseline HVAC system has electric chillers. |
Chilled Water Supply Temperature |
|
---|---|
Applicability |
All chillers |
Definition |
The chilled water supply temperature of the chiller at design conditions |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Rules |
The baseline chilled water supply temperature is set to 44°F. |
Chilled Water Return Temperature |
|
---|---|
Applicability |
All chillers |
Definition |
The chilled water return temperature setpoint |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Rules |
The baseline chilled water return temperature is set to 56°F. |
Chilled Supply Temperature Control Type |
|
---|---|
Applicability |
All chillers |
Definition |
The method by which the chilled water setpoint temperature is reset. The chilled water setpoint may be reset based on demand or outdoor air temperature. |
Units |
List: demand or outdoor air temperature |
Input Restrictions |
As designed |
Baseline Rules |
Outdoor air temperature |
Chilled Water Supply Temperature Reset |
|
---|---|
Applicability |
All chillers |
Definition |
The reset schedule for the chilled water supply temperature. The chilled water setpoint may be reset based on demand or outdoor air temperature. |
Units |
Data structure |
Input Restrictions |
As designed. The default to reset based on outdoor air temperature as follows:
|
Baseline Rules |
The baseline chilled water supply temperature reset uses the defaults. However, if the baseline chilled-water system serves a computer room HVAC system, the supply chilled-water temperature shall be reset higher based on the HVAC system requiring the most cooling; i.e., the chilled-water setpoint is reset higher until one cooling coil valve is nearly wide open. The maximum reset chilled-water supply temperature shall be 54°F. Temperature reset is not required for systems served by purchased chilled water. |
Condenser Type |
|
---|---|
Applicability |
All chillers |
Definition |
The type of condenser for a chiller. The choices are:
Air-cooled chillers use air to cool the condenser coils. Water-cooled chillers use cold water to cool the condenser and additionally need either a cooling tower or a local source of cold water. Evaporatively-cooled chillers are similar to air-cooled chillers, except they use a water mist to cool the condenser coil which makes them more efficient. |
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
The baseline chiller is always assumed to have a water-cooled condenser, although the chiller type will change depending on the design capacity. |
Air-Cooled Condenser Power |
|
---|---|
Applicability |
All chillers with air-cooled condensers where fan energy is not part of the COP. |
Definition |
The energy usage of the condenser fan(s) at design conditions on an air-cooled chiller. This unit should only be used for chillers composed of separate evaporator and condenser sections where the fan energy is not part of the chiller COP. |
Units |
Kilowatts (kW) |
Input Restrictions |
As designed. The user must enter data for remote air-cooled condensing units. |
Baseline Rules |
Not applicable, since all baseline chillers have water-cooled condensers. |
Chiller Name | |
---|---|
Applicability | All chillers |
Definition | Unique descriptor for each chiller |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Baseline Building | Chillers are only designated when the baseline system is of type 7 (VAV with reheat), 8 (VAV with PFP boxes) 11, 12, and 13 |
Chiller Type | |||||||||
---|---|---|---|---|---|---|---|---|---|
Applicability | All chillers | ||||||||
Definition |
The type of chiller, either a vapor-compression chiller or an absorption chiller. Vapor compression chillers operate on the reverse-Rankine cycle, using mechanical energy to compress the refrigerant, and include: · Positive displacement: Includes reciprocating (piston-style), scroll and screw compressors. · Centrifugal: Uses rotating impeller blades to compress the refrigerant and impart velocity. · Single effect absorption: Uses a single generator and condenser. · Double effect absorption: Uses two generators/concentrators and condensers, one at a lower temperature and the other at a higher temperature. It is more efficient than the single effect, but it must use a higher temperature heat source. · Double effect absorption, indirect-fired. · Gas engine driven chiller. · Positive displacement: Includes reciprocating (piston-style), scroll and screw compressors. |
||||||||
Units | List (see above) | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Building |
The baseline building will use electric chillers regardless of the cooling energy source. The baseline building chiller is based on the baseline building peak cooling load, as follows: Table 81. Type and Number Chillers
|
Number of Identical Chiller Units | |
---|---|
Applicability | All chillers |
Definition | The number of identical units for staging |
Units | None |
Input Restrictions | As designed. Default is 1 |
Baseline Building | From Table 81 above, there is one chiller if the baseline system cooling load is 300 tons or less and two equally sized chillers for baseline system loads between 300 and 600 tons. For loads above 600 tons, two or more chillers of equal size are used, with no chiller larger than 800 tons. |
Chiller Fuel | |||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||
Definition |
The fuel source for the chiller. The choices are: · Electricity (for all vapor-compression chillers) · Gas (absorption units only, designated as direct-fired units) · Oil (absorption units only, designated as direct-fired units) · Hot Water (absorption units only, designated as indirect-fired units) · Steam (absorption units only, designated as indirect-fired units) |
||||||||||||||||||||||||||||||||||||||||
Units | List (see above) | ||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. This input is restricted, based on the choice of chiller type, according to the following rules:
|
||||||||||||||||||||||||||||||||||||||||
Baseline Building | Electricity |
Chiller Capacity | |
---|---|
Applicability | All chillers |
Definition | The cooling capacity of a chiller at rated conditions |
Units | Btu/h or tons |
Input Restrictions | As designed. If UMLH are greater than 300, the chiller may have to be made larger. |
Baseline Building | The zone loads and airflow rates are oversized by 15% and the chiller is sized to the sum of the individual oversized zone peak loads. The zones shall be sized using weather files containing 1% dry-bulb and 1% wet-bulb cooling design temperatures. Section 3.1.5 has more details regarding design day data to be used for equipment sizing. |
Chiller Rated Efficiency | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All chillers | |||||||||||||||
Definition |
The efficiency of the chiller: EER for air cooled chillers, kW/ton for water cooled, positive displacement chillers, and COP for fuel-fired and heat driven chillers at ARI 550/590 rated full-load conditions. The test conditions for the full load (FL) rating are summarized below: · 44°F leaving chilled-fluid temperature · 2.4 gpm/ton evaporator fluid flow · 85°F entering condenser-fluid temperature · 3.0 gpm/ton condenser-fluid flow |
|||||||||||||||
Units | Ratio (kW/ton, EER, or COP based on chiller type and condenser type) | |||||||||||||||
Input Restrictions | As designed. Must meet the minimum requirements of Table 6.8.1C of Standard 90.1-2019. | |||||||||||||||
Baseline Building |
Use the minimum efficiency requirements EER or kW/ton values from Table 82 (Standard 90.1-2019 Table G3.5.3). Table 82. Minimum Efficiency Requirements for Water Chilling Packages
FL= Full Load; IPLV = Integrated Part Load Value |
Integrated Part Load Value | |
---|---|
Applicability | All chillers |
Definition | The part-load efficiency of a chiller developed from a weighted average of four rating conditions, according to AHRI Standard 550 |
Units |
Ratio (kW/ton, COP, or EER, depending on chiller type and condenser type) Water cooled electric chiller: kW/ton Air cooled or evaporatively cooled electric chiller: EER All non-electric chillers: COP |
Input Restrictions | As designed. Must meet the minimum requirements of Table 6.8.1C of Standard 90.1-2019. |
Baseline Building | The baseline building is analyzed with the minimum full load efficiency as specified in Table 82. The IPLV is calculated by the simulation software according to ANSI/AHRI Standard 550/590 based on the full load efficiency and the performance curves. |
Chiller Minimum Unloading Ratio | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All chillers | ||||||||||||||
Definition |
The minimum unloading capacity of a chiller expressed as a fraction of the rated capacity. Below this level the chiller must cycle to meet the load. Table 83. Default Minimum Unloading Ratios
|
||||||||||||||
Units |
Percent (%) |
||||||||||||||
Input Restrictions | As designed. If the user does not employ the default values, supporting documentation is required. | ||||||||||||||
Baseline Building | Same as proposed (if the proposed includes a chiller). Else, use defaults listed above. |
Chiller Minimum Part Load Ratio | |
---|---|
Applicability | All chillers |
Definition | The minimum unloading capacity of a chiller expressed as a fraction of the rated capacity. Below this level the chiller must cycle to meet the load. If the chiller minimum part-load ratio (PLR) is less than the chiller minimum unloading ratio, then the software shall assume hot-gas bypass operation between the minimum PLR and the minimum unloading ratio. Standard 90.1-2019 Section 6.5.9 specifies a limit for maximum hot-gas bypass as a percentage of the total cooling capacity of the cooling system. The difference between the maximum unloading ratio and minimum part load ratio cannot exceed this limit for hot gas bypass operation. |
Units |
Percent (%) |
Input Restrictions | As designed, but constrained to a minimum value of 10%. If the user does not employ the default values, supporting documentation is required. |
Baseline Building | When the baseline design has a screw chiller, the minimum part load ratio is 15%. When the baseline design has a centrifugal chiller, the minimum part load ratio is 10%. |
Chiller Cooling Capacity Adjustment Curve | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All chillers | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Definition |
A curve or group of curves or other functions that represent the available total cooling capacity as a function of evaporator and condenser conditions and perhaps other operating conditions. The default curves are given as follows: ??????????=???_??×?????? (52) For air cooled chillers: ???_??=?+?×??ℎ??+?×??ℎ??2+?×????+?×????2+ (53) ?×??ℎ??×???? For water cooled chillers: ???_??=?+?×??ℎ??+?×??ℎ??2+?×????+?×????2+ (54) ?×??ℎ??×????
Where: Qavailable = Available cooling capacity at present evaporator and condenser conditions (MBH) tchws = The chilled water supply temperature (°F) tcws = The condenser water supply temperature (°F) todb = The outside air dry-bulb temperature (°F) Qrated = Rated capacity at ARI conditions (MBH) Note: If an air cooled unit employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. Separate curves are provided for Path A and Path B chillers in COMNET Appendix H (COMNET 2017). Table 84. Default Capacity Coefficients – Electric Air Cooled Chillers
Table 85. Default Capacity Coefficients – Electric Water Cooled Chillers
Table 86. Default Capacity Coefficients – Fuel- and Steam-Source Water Cooled Chillers
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units |
Data structure |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | The user may input curves or use default curves. If the default curves are overridden, supporting documentation is required. | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Building | Use default curve |
Electric Chiller Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Definition |
A curve or group of curves that varies the cooling efficiency of an electric chiller as a function of evaporator conditions, condenser conditions, and part-load ratio. Note that for variable-speed chillers, the part-load cooling efficiency curve is a function of both part-load ratio and leaving condenser water temperature. The default curves are given as follows: Table 87. Default Efficiency EIR-FT Coefficients – Air Cooled Chillers
Table 88. Default Efficiency EIR-FT Coefficients – Water Cooled Chillers
Table 89. Default Efficiency EIR-FPLR Coefficients – Air Cooled Chillers
Table 90. Default Efficiency EIR-FPLR Coefficients – Water Cooled Chillers
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Air Cooled Condenser Power | |
---|---|
Applicability | All chillers with air cooled condensers where fan energy is not part of the COP |
Definition | The energy usage of the condenser fan(s) at design conditions on an air cooled chiller. This unit should only be used for chillers composed of separate evaporator and condenser sections where the fan energy is not part of the chiller COP. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. The user must enter data for remote air cooled condensing units. |
Baseline Building | Not applicable, since all baseline chillers have water cooled condensers |
Chiller Name | |
Applicability | All chillers |
---|---|
Definition | A unique descriptor for each chiller |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Chiller Type | |||||||||
Applicability | All chillers | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition | The type of chiller, either a vapor-compression chiller or an absorption chiller. Vapor compression chillers operate on the reverse-Rankine cycle, using mechanical energy to compress the refrigerant, and include:
|
||||||||
Units | List (see above) | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules |
The baseline building chiller is based on the design capacity of the proposed design as follows from ASHRAE 90.1 Appendix G:
|
Number of Identical Chiller Units | |
Applicability | All chillers |
---|---|
Definition | The number of identical units for staging. |
Units | None |
Input Restrictions | As designed. Default is 1. |
Chiller Fuel | |
Applicability | All chillers |
---|---|
Definition | The fuel source for the chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. |
Chiller Rated Capacity | |
Applicability | All chillers |
---|---|
Definition | The cooling capacity of a piece of heating equipment at rated conditions. |
Units | Btu/h or tons |
Input Restrictions | As designed. If unmet load hours are greater than 300, the chiller may have to be made larger. |
Chiller Rated Efficiency | |
Applicability | All chillers |
---|---|
Definition | The Coefficient of Performance (COP) at ARI rated conditions. |
Units | Ratio |
Input Restrictions | As designed |
Chiller Minimum Unloading Ratio | |||||||||||||||
Applicability | All chillers | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
The minimum unloading capacity of a chiller expressed as a fraction of the rated capacity. Below this level the chiller must cycle to meet the load.
|
||||||||||||||
Units | Percent (%) | ||||||||||||||
Input Restrictions | As designed. If the user does not employ the default values, supporting documentation is required. |
Chiller Cooling Capacity Adjustment Curve | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves or other functions that represent the available total cooling capacity as a function of evaporator and condenser conditions and perhaps other operating conditions. The default curves are given as follows: (6.8.2-1) $$ Q_{available} = CAP \_ FT \times Q_{rated}$$ For air-cooled chillers: (6.8.2-2) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws}\right. ^2 + d \times t_{odb} + e \times \left. t_{odb}\right. ^2 + f \times t_{chws} \times t_{odb}$$ For water-cooled chillers: (6.8.2-3) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws} \right. ^2 + d \times t_{cws} + e \times \left. t_{cws} \right. ^2 + f \times t_{chws} \times t_{cws}$$ where
Note: If an air-cooled unit employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. [table title="Default Capacity Coefficients – Electric Air-Cooled Chillers" id="default-capacity-coefficients-–-electric-air---cooled-chillers"]
[table title="Default Capacity Coefficients – Electric Water-Cooled Chillers" id="default-capacity-coefficients-–-electric-water---cooled-chillers"]
[table title="Default Capacity Coefficients – Fuel- & Steam-Source Water-Cooled Chillers" id="default-capacity-coefficients-–-fuel--&-steam---source-water---cooled-chillers"]
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves, other appropriate functions, or use default curves. If the default curves are overridden, supporting documentation is required. |
Electric Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of an electric chiller as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.8.2-4) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ EIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ air-cooled \enspace EIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{odb} + \ e \times \left. t_{odb}\right. ^2+ \ f \times t_{chws} \times t_{odb}$$ $$ water-cooled \enspace EIR\_FT = a + b \times t_{chws}+ c \times \left. t_{chws}\right. ^2 + d \times t_{cws} + e \times \left. t_{cws}\right. ^2+ f \times t_{chws} \times t_{cws}$$ $$P_{operating} = P_{rated} \times EIR\_FPLR \times EIR\_FT \times CAP\_FT $$ where
Note: If an air-cooled chiller employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. [table title="Default Efficiency EIR-FT Coefficients – Air-Cooled Chillers" id="default-efficiency-eir---ft-coefficients-–-air---cooled-chillers"]
[table title="Default Efficiency EIR-FT Coefficients – Water-Cooled Chiller" id="default-efficiency-eir--ft-coefficients-–-water---cooled-chiller"]
[table title="Default Efficiency EIR-FPLR Coefficients – Air-Cooled Chillers" id="default-efficiency-eir---fplr-coefficients-–-air---cooled-chillers"]
[table title="Default Efficiency EIR-FPLR Coefficients – Water-Cooled Chillers" id="default-efficiency-eir---fplr-coefficients-–-water---cooled-chillers"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. |
Fuel and Steam Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of a fuel-fired or steam chiller as a function of evaporator conditions, condenser conditions, and part-load ratio. The default curves are given as follows: (6.8.2-5) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{cws} + \ e \times \left. t_{cws}\right. ^2+ \ f \times t_{chws} \times t_{cws}$$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT \times CAP\_FT $$ Default Curves for Direct-Fired Double Effect Absorption Chillers (6.8.2-6) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT1 = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 $$ $$ FIR\_FT2 = d + e \times t_{cws} + \ f \times \left. t_{cws}\right. ^2 $$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT1 \times FIR\_FT2 \times CAP\_FT $$ The default curves for engine driven chillers are the same format as those for the Steam-Driven Single and Double Effect Absorption Chillers but there are three sets of curves for different ranges of operation based on the engine speed. where
[table title="Default FIR-FPLR coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers" id="default-fir---fplr-coefficients-–-fuel---&-steam---source-water---cooled-absorption-chillers"]
[table title="Default FIR-FPLR coefficients – Engine Driven Chillers" id="default-fir---fplr-coefficients-–-engine-driven-chillers"]
[table title="Default FIR-FT coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers" id="default-fir---ft-coefficients-–-fuel---&-steam---source-water---cooled-absorption-chillers"]
[table title="Default FIR-FT coefficients – Engine Driven Chillers" id="default-fir---ft-coefficients-–-engine-driven-chillers"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. |
Chilled Water Supply Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water supply temperature of the chiller at design conditions |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Chilled Water Return Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water return temperature setpoint |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Chilled Water Supply Temperature Reset | |
Applicability | All chillers |
---|---|
Definition | The reset schedule for the chilled water supply temperature. The chilled water setpoint may be reset based on demand or outdoor air temperature. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions |
As designed. The default is [bookref id="chilled-water-supply-temperature-reset-schedule"]. [figure title="Chilled Water Supply Temperature Reset Schedule" id="chilled-water-supply-temperature-reset-schedule"][/figure] |
Condenser Type | |
Applicability | All chillers |
---|---|
Definition | The type of condenser for a chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Air-Cooled Condenser Power | |
Applicability | All chillers |
---|---|
Definition | The energy usage of the condenser fan(s) at design conditions on an air-cooled chiller. This unit should only be used for chillers composed of separate evaporator and condenser sections where the fan energy is not part of the chiller COP. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. The user must enter data for remote air-cooled condensing units. |
Chiller Name | |
Applicability | All chillers |
---|---|
Definition | A unique descriptor for each chiller |
Units | Text, unique |
Input Restrictions | User entry. Where applicable, this should match the tags that are used on the plans. |
Chiller Type | |||||||||
Applicability | All chillers | ||||||||
---|---|---|---|---|---|---|---|---|---|
Definition | The type of chiller, either a vapor-compression chiller or an absorption chiller. Vapor compression chillers operate on the reverse-Rankine cycle, using mechanical energy to compress the refrigerant, and include:
|
||||||||
Units | List (see above) | ||||||||
Input Restrictions | As designed | ||||||||
Baseline Rules |
The baseline building chiller is based on the design capacity of the proposed design as follows from ASHRAE 90.1 Appendix G:
|
Number of Identical Chiller Units | |
Applicability | All chillers |
---|---|
Definition | The number of identical units for staging. |
Units | None |
Input Restrictions | As designed. Default is 1. |
Chiller Fuel | |
Applicability | All chillers |
---|---|
Definition | The fuel source for the chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed. |
Chiller Rated Capacity | |
Applicability | All chillers |
---|---|
Definition | The cooling capacity of a piece of heating equipment at rated conditions. |
Units | Btu/h or tons |
Input Restrictions | As designed. If unmet load hours are greater than 300, the chiller may have to be made larger. |
Chiller Rated Efficiency | |
Applicability | All chillers |
---|---|
Definition | The Coefficient of Performance (COP) at ARI rated conditions. |
Units | Ratio |
Input Restrictions | As designed |
Chiller Minimum Unloading Ratio | |||||||||||||||
Applicability | All chillers | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
The minimum unloading capacity of a chiller expressed as a fraction of the rated capacity. Below this level the chiller must cycle to meet the load.
|
||||||||||||||
Units | Percent (%) | ||||||||||||||
Input Restrictions | As designed. If the user does not employ the default values, supporting documentation is required. |
Chiller Cooling Capacity Adjustment Curve | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves or other functions that represent the available total cooling capacity as a function of evaporator and condenser conditions and perhaps other operating conditions. The default curves are given as follows: (6.8.2-1) $$ Q_{available} = CAP \_ FT \times Q_{rated}$$ For air-cooled chillers: (6.8.2-2) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws}\right. ^2 + d \times t_{odb} + e \times \left. t_{odb}\right. ^2 + f \times t_{chws} \times t_{odb}$$ For water-cooled chillers: (6.8.2-3) $$ CAP \_FT = a + b \times t_{chws} + c \times \left. t_{chws} \right. ^2 + d \times t_{cws} + e \times \left. t_{cws} \right. ^2 + f \times t_{chws} \times t_{cws}$$ where
Note: If an air-cooled unit employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. [table title="Default Capacity Coefficients – Electric Air-Cooled Chillers" id="default-capacity-coefficients-–-electric-air---cooled-chillers"]
[table title="Default Capacity Coefficients – Electric Water-Cooled Chillers" id="default-capacity-coefficients-–-electric-water---cooled-chillers"]
[table title="Default Capacity Coefficients – Fuel- & Steam-Source Water-Cooled Chillers" id="default-capacity-coefficients-–-fuel--&-steam---source-water---cooled-chillers"]
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves, other appropriate functions, or use default curves. If the default curves are overridden, supporting documentation is required. |
Electric Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of an electric chiller as a function of evaporator conditions, condenser conditions and part-load ratio. The default curves are given as follows: (6.8.2-4) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ EIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ air-cooled \enspace EIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{odb} + \ e \times \left. t_{odb}\right. ^2+ \ f \times t_{chws} \times t_{odb}$$ $$ water-cooled \enspace EIR\_FT = a + b \times t_{chws}+ c \times \left. t_{chws}\right. ^2 + d \times t_{cws} + e \times \left. t_{cws}\right. ^2+ f \times t_{chws} \times t_{cws}$$ $$P_{operating} = P_{rated} \times EIR\_FPLR \times EIR\_FT \times CAP\_FT $$ where
Note: If an air-cooled chiller employs an evaporative condenser, todb is the effective dry-bulb temperature of the air leaving the evaporative cooling unit. [table title="Default Efficiency EIR-FT Coefficients – Air-Cooled Chillers" id="default-efficiency-eir---ft-coefficients-–-air---cooled-chillers"]
[table title="Default Efficiency EIR-FT Coefficients – Water-Cooled Chiller" id="default-efficiency-eir--ft-coefficients-–-water---cooled-chiller"]
[table title="Default Efficiency EIR-FPLR Coefficients – Air-Cooled Chillers" id="default-efficiency-eir---fplr-coefficients-–-air---cooled-chillers"]
[table title="Default Efficiency EIR-FPLR Coefficients – Water-Cooled Chillers" id="default-efficiency-eir---fplr-coefficients-–-water---cooled-chillers"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. |
Fuel and Steam Chiller Cooling Efficiency Adjustment Curves | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Applicability | All chillers | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Definition |
A curve or group of curves that varies the cooling efficiency of a fuel-fired or steam chiller as a function of evaporator conditions, condenser conditions, and part-load ratio. The default curves are given as follows: (6.8.2-5) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 + \ d \times t_{cws} + \ e \times \left. t_{cws}\right. ^2+ \ f \times t_{chws} \times t_{cws}$$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT \times CAP\_FT $$ Default Curves for Direct-Fired Double Effect Absorption Chillers (6.8.2-6) $$ PLR = \frac {Q_{operating}}{Q_{available}\left ( t_{chws} , t_{cws/odb}\right )}$$ $$ FIR\_FPLR = a + b \times PLR + c \times PLR^2$$ $$ FIR\_FT1 = a + \ b \times t_{chws}+ \ c \times \left. t_{chws}\right. ^2 $$ $$ FIR\_FT2 = d + e \times t_{cws} + \ f \times \left. t_{cws}\right. ^2 $$ $$Fuel_{partload} = Fuel_{rated} \times FIR\_FPLR \times FIR\_FT1 \times FIR\_FT2 \times CAP\_FT $$ The default curves for engine driven chillers are the same format as those for the Steam-Driven Single and Double Effect Absorption Chillers but there are three sets of curves for different ranges of operation based on the engine speed. where
[table title="Default FIR-FPLR coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers" id="default-fir---fplr-coefficients-–-fuel---&-steam---source-water---cooled-absorption-chillers"]
[table title="Default FIR-FPLR coefficients – Engine Driven Chillers" id="default-fir---fplr-coefficients-–-engine-driven-chillers"]
[table title="Default FIR-FT coefficients – Fuel- & Steam-Source Water-Cooled Absorption Chillers" id="default-fir---ft-coefficients-–-fuel---&-steam---source-water---cooled-absorption-chillers"]
[table title="Default FIR-FT coefficients – Engine Driven Chillers" id="default-fir---ft-coefficients-–-engine-driven-chillers"]
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units | Data structure | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | User may input curves or use default curves. If defaults are overridden, supporting documentation is required. |
Chilled Water Supply Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water supply temperature of the chiller at design conditions |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Chilled Water Return Temperature | |
Applicability | All chillers |
---|---|
Definition | The chilled water return temperature setpoint |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | As designed |
Chilled Water Supply Temperature Reset | |
Applicability | All chillers |
---|---|
Definition | The reset schedule for the chilled water supply temperature. The chilled water setpoint may be reset based on demand or outdoor air temperature. |
Units | Degrees Fahrenheit (°F) |
Input Restrictions |
As designed. The default is [bookref id="chilled-water-supply-temperature-reset-schedule"]. [figure title="Chilled Water Supply Temperature Reset Schedule" id="chilled-water-supply-temperature-reset-schedule"][/figure] |
Condenser Type | |
Applicability | All chillers |
---|---|
Definition | The type of condenser for a chiller. The choices are:
|
Units | List (see above) |
Input Restrictions | As designed |
Air-Cooled Condenser Power | |
Applicability | All chillers |
---|---|
Definition | The energy usage of the condenser fan(s) at design conditions on an air-cooled chiller. This unit should only be used for chillers composed of separate evaporator and condenser sections where the fan energy is not part of the chiller COP. |
Units | Kilowatts (kW) |
Input Restrictions | As designed. The user must enter data for remote air-cooled condensing units. |