Cooling Supply Air Temperature |
|
---|---|
Applicability |
Applicable to all systems |
Definition |
The supply air temperature setpoint at design cooling conditions |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
As designed |
Baseline Rules |
20°F below the space setpoint |
Cooling Supply Air Temperature Control |
|
---|---|
Applicability |
Any cooling system |
Definition |
The method of controlling the supply air temperature. Choices are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
For baseline building systems 1 through 4, the SAT control is fixed. For systems 5 through 8, the air temperature for coolingshall be reset higher by 5°F under the minimum cooling load conditions using a reset by warmest zone, flow first strategy This strategy sets the cooling coil temperature each hour to adequately cool the zone with the highest temperature. find the lowest supply air flow rate that will satisfy all the zone cooling loads at the maximum setpoint temperature. If this flow is greater than the maximum, the flow is set to the maximum and the setpoint temperature is reduced to satisfy the cooling loads. The airflow first strategy minimizes zone reheat coil energy (or overcooling) and central chiller energy consumption at the cost of possible increased fan energy. This SAT reset may driven back to the design SAT if a maximum humidity setpoint is not met. For system 9 and 10 (heating and ventilation) this input is not applicable. |
Cooling Reset Schedule by OSA |
|
---|---|
Applicability |
When the proposed design resets SAT by outside air dry-bulb temperature |
Definition |
A linear reset schedule that represents the SAT setpoint as a function of outdoor air dry-bulb temperature. This schedule is defined by the following data points (see figures below:
Figure 3.7.2-1: SAT Cooling Setpoint Reset based on Outdoor Air Temperature (OAT) |
Units |
Data structure (two matched pairs of SAT and OAT, see above) |
Input Restrictions |
As designed. |
Baseline Rules |
The schedule defaults to: Supply Air High = Supply Air Low + 5 Supply Low = (greater of SAT or 50F) Outside High = 80°F Outside Low = 60°F |