Floor Name |
|
---|---|
Applicability |
All floor surfaces |
Definition |
A unique name or code that relates the exposed floor to the design documents. Exposed floors include floors exposed to the outdoors and floors over unconditioned spaces, but do not include slab-on-grade floors, below grade floors, or interior floors. |
Units |
Text, unique |
Input Restrictions |
None |
Baseline Rules |
None |
Floor Type |
|
---|---|
Applicability |
All exterior floor surfaces, optional |
Definition |
One of three categories of exposed floor assemblies used to determine minimum prescriptive insulation requirements. The three floor type categories are: a) mass floor, b) steel joist floor, and c) wood and other floors. These are defined in Standard 90.1-2013 and the associated User's Manuals. This building descriptor is not used for the purposes of this manual, since the type for the baseline building is fixed at “steel joist”. This building descriptor can often be derived from other information in the model and may not be required as an explicit input. |
Units |
List: mass floor, metal joist floor, and wood and other floors |
Input Restrictions |
This building descriptor input is optional and may be derived from other inputs. |
Baseline Rules |
The baseline building floors shall be of type “steel joist.” |
Floor Geometry |
|
---|---|
Applicability |
All exterior floors, required input |
Definition |
Floor geometry defines the position, orientation, azimuth, and tilt of the floor surface. The details of how the coordinate system is implemented may vary between software programs. The data structure for surfaces is described in the reference section of this chapter. |
Units |
Data structure: surface |
Input Restrictions |
There are no restrictions other than that the surfaces defined must agree with the building being modeled, as represented on the construction documents or as-built drawings. |
Baseline Rules |
Baseline building floor geometry is identical to the proposed design. |
Floor Construction |
|
---|---|
Applicability |
All floors, required input |
Definition |
A reference to a construction assembly for the proposed design |
Units |
Dimensionless reference |
Input Restrictions |
All floor surfaces must reference a construction assembly that meets the mandatory measures of the baseline standards. |
Baseline Rules |
Exterior floors in the baseline building are of type “steel joist.” The insulation requirements depend on the baseline standard and the climate zone and are given in Table 3.5.5-1. The baseline building constructions shall be modeled as layers, which are defined in Table 3.5.5-2. |
Table 3.5.5-1: Baseline Building R-value and U-factor Criteria for Exposed Floors
Climate Zone |
Nonresidential |
Residential |
Semi-Heated |
|||
Name |
U-factor |
Name |
U-factor |
Name |
U-factor |
|
1 |
NR |
0.350 |
NR |
0.350 |
NR |
0.350 |
2 |
R-19 |
0.052 |
R-19 |
0.052 |
||
3 |
||||||
4 |
R-30 |
0.038 |
R-13 |
0.069 |
||
5 |
||||||
6 |
R-30 |
0.038 |
||||
7 |
R-19 |
0.052 |
||||
8 |
R-38 |
0.032 |
Table 3.5.5-2: Baseline Building Exposed Floor Construction Assemblies
Construction |
Layer |
Thickness (inch) |
Conductivity (Btu/h ft F) |
Density (lb/ft²) |
Specific Heat (Btu/lb F) |
R-value (ft²·°F·h/Btu) |
U-factor (Btu/ft²·°F·h) |
Floor R-38 |
Interior air film (flow down) |
- |
- |
- |
- |
0.92 |
- |
carpet and pad |
- |
- |
- |
- |
1.23 |
- |
|
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
- |
|
R-38 insulation between joists |
- |
- |
- |
- |
28 |
- |
|
metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
- |
|
Semi-exterior air film |
- |
- |
- |
- |
0.46 |
- |
|
Total for assembly |
30.86 |
0.032 |
|||||
Floor R-30 |
Interior air film (flow down) |
- |
- |
- |
- |
0.92 |
- |
carpet and pad |
- |
- |
- |
- |
1.23 |
- |
|
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
- |
|
R-30 insulation between joists |
- |
- |
- |
- |
23.5 |
- |
|
metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
- |
|
Semi-exterior air film |
- |
- |
- |
- |
0.46 |
- |
|
Total for assembly |
26.36 |
0.038 |
|||||
Floor R-19 |
Interior air film (flow down) |
- |
- |
- |
- |
0.92 |
- |
carpet and pad |
- |
- |
- |
- |
1.23 |
- |
|
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
- |
|
R-19 insulation between joists |
- |
- |
- |
- |
16.37 |
- |
|
metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
- |
|
Semi-exterior air film |
- |
- |
- |
- |
0.46 |
- |
|
Total for assembly |
19.23 |
0.052 |
|||||
Floor R-13 |
Interior air film (flow down) |
- |
- |
- |
- |
0.92 |
- |
carpet and pad |
- |
- |
- |
- |
1.23 |
- |
|
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
- |
|
R-13 insulation between joists |
- |
- |
- |
- |
11.63 |
- |
|
metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
- |
|
Semi-exterior air film |
- |
- |
- |
- |
0.46 |
- |
|
Total for assembly |
14.49 |
0.069 |
|||||
NR |
Interior air film (flow down) |
- |
- |
- |
- |
0.92 |
- |
Carpet and pad |
- |
- |
- |
- |
1.23 |
- |
|
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
||
Metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
- |
|
Semi-exterior air film |
- |
- |
- |
- |
0.46 |
- |
|
Total for assembly |
2.86 |
0.350 |
Floor Name |
|
Applicability |
All floor surfaces |
Definition |
A unique name or code that relates the exposed floor to the design documents. Exposed floors include floors exposed to the outdoors and floors over unconditioned spaces, but do not include slab-on-grade floors, below-grade floors, or interior floors. |
Units |
|
Input Restrictions |
None |
Baseline Building |
None |
Floor Type |
|
Applicability |
All exterior floor surfaces, optional |
Definition |
The category that defines the baseline building prescriptive floor requirements |
Units |
|
Input Restrictions |
As designed |
Baseline Building |
The baseline building floors shall be of type “steel-joist” |
Floor Geometry |
|
Applicability |
All exterior floors, required input |
Definition |
Floor geometry defines the position, orientation, azimuth, and tilt of the floor surface. The details of how the coordinate system is implemented may vary among software programs. The data structure for surfaces is described in the reference section of this chapter. |
Units |
|
Input Restrictions |
As designed |
Baseline Building |
Baseline building floor geometry is identical to the proposed design |
Floor Construction |
|
Applicability |
All floors, required input |
Definition |
A specification containing a series of layers that result in a construction assembly for the proposed design. The first layer in the series represents the outside (or exterior) layer and the last layer represents the inside (or interior) layer. See the building descriptors above for floor construction type. |
Units |
|
Input Restrictions |
As designed, with the construction assembly defined by a series of layers. Each layer specified, must consist of materials as described in Section 3.5.2. NOTE: Standard 90.1-2019, Table A9.2-1 in Appendix A specifies the effective insulation/framing layer R-values for roof and floor insulation installed between metal framing 4’ OC. These values are intended to be used for all other framing, 16”, 2’, and 3’. |
Baseline Building |
The exterior floor type for the baseline building is steel joist. The baseline building wall construction shall be modeled as layers. The U-factor required for baseline wall construction is defined in Table 25. The layer by layer construction corresponding to each U-factor shall be modeled as shown in Table 26. For existing buildings, the baseline walls shall follow the same rules as new buildings. |
Table 25. Standard 90.1-2019 Requirements for Baseline Steel Joist Floors for Non-Residential Space Conditioning Categories
|
U-factor (Btu/ft2. °F. h) |
||
Nonresidential |
Residential |
Semiheated |
|
Climate Zone 0 and 1 |
U-0.35 |
U-0.35 |
U-0.35 |
Climate Zone 2 |
U-0.052 |
U-0.052 |
U-0.35 |
Climate Zone 3 |
U-0.052 |
U-0.052 |
U-0.069 |
Climate Zone 4 |
U-0.052 |
U-0.038 |
U-0.069 |
Climate Zone 5 |
U-0.052 |
U-0.038 |
U-0.069 |
Climate Zone 6 |
U-0.038 |
U-0.038 |
U-0.069 |
Climate Zone 7 |
U-0.038 |
U-0.038 |
U-0.052 |
Climate Zone 8 |
U-0.038 |
U-0.032 |
U-0.052 |
Table 26. Baseline Building Exterior Floor Construction Assemblies
Construction |
Layer |
Thickness (inch) |
Conductivity (Btu/h ft °F) |
Density (lb/ft²) |
Specific Heat |
R-value (ft²·°F·h/Btu) |
|
U-value (Btu /ft²·°F·h) |
Floor R-38 |
Interior air film (flow down) |
0.92 |
|
|||||
Carpet and pad |
1.23 |
|
||||||
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
|
||
R-38 insulation between joists |
28 |
|
||||||
Metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
|
||
Semi-exterior air film |
0.46 |
|
||||||
Total for assembly |
30.86 |
0.032 |
||||||
Floor R-30 |
Interior air film (flow down) |
0.92 |
|
|||||
Carpet and pad |
1.23 |
|
||||||
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
|
||
R-30 insulation between joists |
23.5 |
|
||||||
Metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
|
||
Semi-exterior air film |
0.46 |
|
||||||
Total for assembly |
26.36 |
0.038 |
||||||
Floor R-19 |
Interior air film (flow down) |
0.92 |
|
|||||
Carpet and pad |
1.23 |
|
||||||
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
|
||
R-19 insulation between joists |
16.37 |
|
||||||
Metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
|
||
Semi-exterior air film |
0.46 |
|
||||||
Total for Assembly |
19.23 |
0.052 |
||||||
Floor R-13 |
Interior air film (flow down) |
0.92 |
|
|||||
Carpet and pad |
1.23 |
|
||||||
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
|
||
R-13 insulation between joists |
11.63 |
|
||||||
Metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
|
||
Semi-exterior air film |
0.46 |
|
||||||
Total for assembly |
14.49 |
0.069 |
||||||
NR |
Interior air film (flow down) |
0.92 |
|
|||||
Carpet and pad |
1.23 |
|
||||||
4" concrete |
4 |
1.3333 |
140 |
0.2 |
0.25 |
|
||
Metal deck |
0.06 |
26 |
480 |
0.1 |
0.00 |
|
||
Semi-exterior air film |
0.46 |
|
||||||
Total for assembly |
2.86 |
0.35 |