3.10.1.3 Collector Performance

90.1-2019

The collector performance can be characterized by the following five variables that are available from PV array manufacturers: the open-circuit voltage, the short-circuit current, the voltage and current at the maximum power-point, and the temperature coefficient of the open-circuit voltage. These are described below.

 

Short-Circuit Current

Applicability

All PV systems

Definition

Isc - current measured with zero voltage

Units

Amps

Input Restrictions

From manufacturer's specification

Baseline Building

None (PV not modeled for the baseline building)

 

Open-Circuit Voltage

Applicability

All PV systems

Definition

Voc - voltage measured with an open circuit

Units

Volts

Input Restrictions

From manufacturer's specification

Baseline Building

None (PV not modeled for the baseline building)

 

Maximum Power-Point Voltage and Current

Applicability

All PV systems

Definition

Imp, Vmp - current and voltage at the maximum power-point condition. These parameters are typically reported at Standard Test Conditions of 1000 W/m2 and a cell temperature of 25°C.

Units

Amps and Volts

Input Restrictions

From manufacturer’s specification

Baseline Building

None (PV not modeled for the baseline building)

 

Open-Circuit Temperature Coefficient

Applicability

All PV systems

Definition

Temperature coefficient of the open circuit voltage (Voc) measures the changing open circuit voltage values of the PV module when the temperature increases (or decreases)

Units

%/ºC

Input Restrictions

From manufacturer's specification

Baseline Building

None (PV not modeled for the baseline building)

 

Short Circuit Temperature Coefficient

Applicability

All PV systems

Definition

Temperature coefficient of the short-circuit current (Isc) measures the changing short-circuit current values of the PV module when the solar cell temperature increases (or decreases)

Units

%/ºC

Input Restrictions

From manufacturer’s specification

Baseline Building

None (PV not modeled for the baseline building)

 

Nominal Operating Cell Temperature (NOCT)

Applicability

All PV systems

Definition

The normal operating cell temperature, typically between 45°C and 55°C

Units

Degrees Celsius (°C)

Input Restrictions

From manufacturer’s specification

Baseline Building

None (PV not modeled for the baseline building)

 

PV Array Mounting Type

Applicability

All PV systems

Definition

The array type describes whether the PV modules in the array are fixed, or whether they move to track the movement of the sun across the sky with one or two axes of rotation.

Units

List: Fixed, one axis tracking, two axis tracking

Input Restrictions

As designed. The default value is a fixed, or no tracking.

Baseline Building

None (PV not modeled for the baseline building)

 

PV Array Mounting Type

Applicability

All PV systems

Definition

The array type describes whether the PV modules in the array are fixed, or whether they move to track the movement of the sun across the sky with one or two axes of rotation

Units

List: Fixed, one axis tracking, two axis tracking

Input Restrictions

As designed. The default value is a fixed, or no tracking.

Baseline Building

None (PV not modeled for the baseline building)