This group of building descriptors describes the rate of exhaust and the schedule or control for this exhaust. An exhaust system can serve one thermal block or multiple thermal blocks. Energy is summed at the exhaust system level, not the thermal block level.
Kitchen Exhaust Hood Length |
|
Applicability |
Exhaust fans in spaces of type Kitchen |
Definition |
The exhaust hood length |
Units |
ft |
Input Restrictions |
As designed |
Baseline building |
Same as the proposed design |
Kitchen Exhaust Hood Style |
|
Applicability |
Exhaust fans in spaces of type Kitchen |
Definition |
The hood style as defined in Table 140.9-A of the Standards |
Units |
List: Wall-mounted canopy, Single Island, Double Island, Eyebrow, Backshelf/Passover |
Input Restrictions |
As designed |
Baseline building |
Same as the proposed design |
Kitchen Exhaust Hood Cooking Duty |
|
Applicability |
Exhaust fans in spaces of type Kitchen |
Definition |
The hood cooking duty as defined in Table 6.5.7.1.3 of the 90.1 2010 Standards |
Units |
List: Light Duty, Medium Duty, Heavy Duty, Extra Heavy Duty |
Input Restrictions |
As designed |
Baseline building |
Same as the proposed design |
Kitchen: Exhaust Air Flow Rate |
|||||||||||||||||||||||||||||||
Applicability |
All Kitchen HVAC zones |
||||||||||||||||||||||||||||||
Definition |
Rate of exhaust from a thermal zone. Standard 90.1 2010 Section 6.5.7.1.3 requires each hood in kitchen/dining facility with total kitchen hood exhaust airflow rate greater than 5,000 cfm to have an exhaust rate that complies with Table 3.6.5-1. If a single hood, or hood section, is installed over appliances with different duty ratings, then the maximum allowable flow rate for the hood or hood section shall not exceed the Table 3.6.5-1 values for the highest appliance duty rating under the hood or hood section. Table 3.6.5-1: Maximum Net Exhaust Flow Rate, CFM per Linear Foot of Hood LengthSource: Table 6.5.7.1.3 of Standard 90.1-2016
|
||||||||||||||||||||||||||||||
Units |
cfm |
||||||||||||||||||||||||||||||
Input Restrictions |
As designed |
||||||||||||||||||||||||||||||
Baseline building |
If the exhaust airflow rate of the proposed design is less than or equal to the exhaust flow rate prescribed in Table 3.6.5-1 above, then the baseline exhaust flow rate will be same as proposed. However, if the kitchen hood exhaust air flow rate for the proposed design is greater than the airflow rate prescribed, then the baseline buildings uses airflow rates equal to that in the table. |
Kitchen: Demand Ventilation |
|
Applicability |
All Kitchen HVAC Zones |
Definition |
A demand ventilation system uses a light beam and a photo detector to detect the presence of smoke. It also has a temperature sensor to detect heat. The exhaust fan slows down below design levels and both exhaust and replacement airflow rates are reduced when the system detects no smoke or heat. |
Units |
Unitless |
Input Restrictions |
As designed |
Baseline building |
For proposed designs with exhaust air flow rate greater than 5000 CFM, baseline models is required to use demand ventilation system on 75% of the exhaust air and makeup air. Airflow will be reduced by 50% during 50% of kitchen occupied hours. |
Laboratory Exhaust Rate Type |
|
Applicability |
All laboratory zones |
Definition |
The type of load that dictates lab exhaust rate requirements |
Units |
List, either: Hood dominated or Load dominated |
Input Restrictions |
As designed |
Baseline building |
Same as the proposed design |
Laboratory: Exhaust Minimum Air Flow Rate |
---|
Applicability |
All laboratory zones |
Definition |
Rate of exhaust from a zone |
Units |
cfm |
Input Restrictions |
Baseline Building |
Baseline Rules |
Same As Proposed except for the unoccupied periods, where systems serving laboratory spaces shall reduce the exhaust and makeup air volume during unoccupied periods to the largest of 50% of zone peak air flow, the minimum outdoor air flow rate, or the air flow rate required to comply with applicable codes or accreditation standards. |
Exhaust Fan Name |
|
---|---|
Applicability |
All HVAC zones |
Definition |
A reference to an exhaust fan system that serves the thermal block |
Units |
Text or other unique reference to an exhaust fan system defined in the secondary systems section. |
Input Restrictions |
As designed |
Baseline Rules |
Same as the proposed design |
Exhaust Air Flow Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
Rate of exhaust from a thermal block |
Units |
cfm |
Input Restrictions |
As designed |
Baseline Rules |
Same as the proposed design |
Exhaust Fan Schedule |
|
---|---|
Applicability |
All HVAC zones |
Definition |
Schedule indicating the pattern of use for exhaust air from the thermal block. This input should consider the position of fume hood sash opening. For toilets and other exhaust applications, the schedule may coincide with the operation of the exhaust fan system. |
Units |
Data structure: schedule, fraction |
Input Restrictions |
As designed |
Baseline Rules |
Same as the proposed design |