VAV Air Flow
This group of building descriptors applies to proposed design systems that vary the volume of air at the zone level. The building descriptors are applicable for baseline building systems 5 through 8.
Design Airflow | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The air delivery rate at design conditions |
Units | cfm |
Input Restrictions | As designed. If the unmet load hours in the proposed design are greater than 300, the building descriptor may need to be modified to meet the criterion. |
Baseline Rules | For systems 5 through 8, the software shall automatically size the airflow to meet the baseline building loads based on a supply-air-to-room-air temperature difference of 20°F or the required ventilation air or makeup air, whichever is greater |
Terminal Minimum Stop | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The minimum airflow that will be delivered by a terminal unit before reheating occurs |
Units | Unitless fraction airflow (cfm) or specific airflow (cfm/ft²) |
Input Restrictions | This input must be greater than or equal to the outside air ventilation rate. |
Baseline Rules | For systems 5 through 8, set the minimum airflow to be the greater of 0.4 cfm/ft² of conditioned floor area or the outside air ventilation rate. |
Fan Powered Boxes
Fan Powered Box Type | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition |
Defines the type of fan-powered induction box. This is either:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable for baseline building systems 6 and 8 and the fan powered box type is parallel. |
Fan Power | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The rated power input of the fan in a fan-powered box. |
Units | W or W/cfm |
Input Restrictions | As designed |
Baseline Rules | For baseline building systems 6 and 8, power is prescribed at 0.35 W/cfm. |
Fan Power Box Induced Air Zone | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | Zone from which a series or parallel fan-powered box draws its air |
Units | List (of zones) |
Input Restrictions | As designed |
Baseline Rules | If the proposed design has a plenum, then induced air will be drawn from that plenum. If the proposed design does not have a plenum, then induced air will be drawn from the space. |
Parallel PIU Induction Ratio | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The ratio of induction-side airflow of a fan-powered box at design heating conditions to the primary airflow |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | 50% |
Parallel Fan Box Thermostat Setpoint | |
Applicability | HVAC zones that have parallel fan powered boxes |
---|---|
Definition | The temperature difference above the heating setpoint at which the parallel fan is turned on |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | 2°F above the heating setpoint schedule |
Baseline Rules | 2°F above the heating setpoint schedule |
Zone Exhaust
This group of building descriptors describes the rate of exhaust and the schedule or control for this exhaust. An exhaust system can serve one thermal block or multiple thermal blocks. Energy is summed for the exhaust system level, not the thermal block level.
Exhaust Fan Name | |
Applicability | All HVAC zones |
---|---|
Definition | A reference to an exhaust fan system that serves the thermal block |
Units | Text or other unique reference to an exhaust fan system defined in the secondary systems section. |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Exhaust Air Flow Rate | |
Applicability | All HVAC zones |
---|---|
Definition | Rate of exhaust from a thermal block |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Exhaust Fan Schedule | |
Applicability | All HVAC zones |
---|---|
Definition | Schedule indicating the pattern of use for exhaust air from the thermal block. This input should consider the position of fume hood sash opening. For toilets and other exhaust applications, the schedule may coincide with the operation of the exhaust fan system. |
Units | Data structure: schedule, fraction |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Outdoor Air Ventilation
Ventilation Source | |
Applicability | All HVAC zones |
---|---|
Definition |
The source of ventilation for an HVAC system. The choices are:
|
Units | List: natural or mechanical |
Input Restrictions | For residential units and hotel/motel guest rooms, as designed. For all other occupancies, set to mechanical. |
Baseline Rules | For residential units, set to natural, for all other occupancies, set equal to the value for the proposed design (mechanical). |
Design Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The quantity of ventilation air that is provided to the space for the specified thermal block at maximum occupancy |
Units | cfm or cfm/occupant |
Input Restrictions | For the purpose of tax deduction calculations, the California ACM values from Table 4 of Appendix B shall be used. For green building ratings and Design to Earn ENERGY STAR, the COMNET values from Table 4 of Appendix B shall be used as a default. Other values may be used with appropriate documentation. |
Baseline Rules | Same as the proposed design |
Minimum Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The minimum quantity of ventilation air that must provided to the space when the HVAC system is operating |
Units | cfm or cfm/ft² |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Ventilation Control Method | |
Applicability | All HVAC zones |
---|---|
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules |
For the federal tax credit, if the design occupancy is greater than 100 persons per 1,000 ft² and the system design outside air flow rate is greater than 3,000 cfm, set control method to CO2 sensors in the space, otherwise set to fixed ventilation rate. For green building incentive programs, set to CO2 sensors in the space if the design occupancy is greater than 40 people per 1,000 ft² and the system design outdoor air flow rate is greater than 1,200 cfm, otherwise set to fixed ventilation rate. |
VAV Air Flow
This group of building descriptors applies to proposed design systems that vary the volume of air at the zone level. The building descriptors are applicable for baseline building systems 5 through 8.
Design Airflow | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The air delivery rate at design conditions |
Units | cfm |
Input Restrictions | As designed. If the unmet load hours in the proposed design are greater than 300, the building descriptor may need to be modified to meet the criterion. |
Baseline Rules | For systems 5 through 8, the software shall automatically size the airflow to meet the baseline building loads based on a supply-air-to-room-air temperature difference of 20°F or the required ventilation air or makeup air, whichever is greater |
Terminal Minimum Stop | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The minimum airflow that will be delivered by a terminal unit before reheating occurs |
Units | Unitless fraction airflow (cfm) or specific airflow (cfm/ft²) |
Input Restrictions | This input must be greater than or equal to the outside air ventilation rate. |
Baseline Rules | For systems 5 through 8, set the minimum airflow to be the greater of 0.4 cfm/ft² of conditioned floor area or the outside air ventilation rate. |
Fan Powered Boxes
Fan Powered Box Type | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition |
Defines the type of fan-powered induction box. This is either:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable for baseline building systems 6 and 8 and the fan powered box type is parallel. |
Fan Power | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The rated power input of the fan in a fan-powered box. |
Units | W or W/cfm |
Input Restrictions | As designed |
Baseline Rules | For baseline building systems 6 and 8, power is prescribed at 0.35 W/cfm. |
Fan Power Box Induced Air Zone | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | Zone from which a series or parallel fan-powered box draws its air |
Units | List (of zones) |
Input Restrictions | As designed |
Baseline Rules | If the proposed design has a plenum, then induced air will be drawn from that plenum. If the proposed design does not have a plenum, then induced air will be drawn from the space. |
Parallel PIU Induction Ratio | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The ratio of induction-side airflow of a fan-powered box at design heating conditions to the primary airflow |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | 50% |
Parallel Fan Box Thermostat Setpoint | |
Applicability | HVAC zones that have parallel fan powered boxes |
---|---|
Definition | The temperature difference above the heating setpoint at which the parallel fan is turned on |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | 2°F above the heating setpoint schedule |
Baseline Rules | 2°F above the heating setpoint schedule |
Zone Exhaust
This group of building descriptors describes the rate of exhaust and the schedule or control for this exhaust. An exhaust system can serve one thermal block or multiple thermal blocks. Energy is summed for the exhaust system level, not the thermal block level.
Exhaust Fan Name | |
Applicability | All HVAC zones |
---|---|
Definition | A reference to an exhaust fan system that serves the thermal block |
Units | Text or other unique reference to an exhaust fan system defined in the secondary systems section. |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Exhaust Air Flow Rate | |
Applicability | All HVAC zones |
---|---|
Definition | Rate of exhaust from a thermal block |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Exhaust Fan Schedule | |
Applicability | All HVAC zones |
---|---|
Definition | Schedule indicating the pattern of use for exhaust air from the thermal block. This input should consider the position of fume hood sash opening. For toilets and other exhaust applications, the schedule may coincide with the operation of the exhaust fan system. |
Units | Data structure: schedule, fraction |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Outdoor Air Ventilation
Ventilation Source | |
Applicability | All HVAC zones |
---|---|
Definition |
The source of ventilation for an HVAC system. The choices are:
|
Units | List: natural or mechanical |
Input Restrictions | For residential units and hotel/motel guest rooms, as designed. For all other occupancies, set to mechanical. |
Baseline Rules | For residential units, set to natural, for all other occupancies, set equal to the value for the proposed design (mechanical). |
Design Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The quantity of ventilation air that is provided to the space for the specified thermal block at maximum occupancy |
Units | cfm or cfm/occupant |
Input Restrictions | For green building ratings and Design to Earn ENERGY STAR, the COMNET values from Table 4 of Appendix B shall be used as a default. Other values may be used with appropriate documentation. |
Baseline Rules | Same as the proposed design |
Minimum Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The minimum quantity of ventilation air that must provided to the space when the HVAC system is operating |
Units | cfm or cfm/ft² |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Ventilation Control Method | |
Applicability | All HVAC zones |
---|---|
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | For green building incentive programs, set to CO2 sensors in the space if the design occupancy is greater than 40 people per 1,000 ft² and the system design outdoor air flow rate is greater than 1,200 cfm, otherwise set to fixed ventilation rate. |
VAV Air Flow
This group of building descriptors applies to proposed design systems that vary the volume of air at the zone level. The building descriptors are applicable for baseline building systems 5 through 8.
Design Airflow | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The air delivery rate at design conditions |
Units | cfm |
Input Restrictions | As designed. If the unmet load hours in the proposed design are greater than 300, the building descriptor may need to be modified to meet the criterion. |
Baseline Rules | For systems 5 through 8, the software shall automatically size the airflow to meet the baseline building loads based on a supply-air-to-room-air temperature difference of 20°F or the required ventilation air or makeup air, whichever is greater |
Terminal Minimum Stop | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The minimum airflow that will be delivered by a terminal unit before reheating occurs |
Units | Unitless fraction airflow (cfm) or specific airflow (cfm/ft²) |
Input Restrictions | This input must be greater than or equal to the outside air ventilation rate. |
Baseline Rules |
For systems 5 through 8, set the minimum airflow to be the greater of 30% of zone peak airflow, or the outside air ventilation rate. |
Fan Powered Boxes
Fan Powered Box Type | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition |
Defines the type of fan-powered induction box. This is either:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules | Applicable for baseline building systems 6 and 8 and the fan powered box type is parallel. |
Fan Power | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The rated power input of the fan in a fan-powered box. |
Units | W or W/cfm |
Input Restrictions | As designed |
Baseline Rules | For baseline building systems 6 and 8, power is prescribed at 0.35 W/cfm. |
Fan Power Box Induced Air Zone | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | Zone from which a series or parallel fan-powered box draws its air |
Units | List (of zones) |
Input Restrictions | As designed |
Baseline Rules | If the proposed design has a plenum, then induced air will be drawn from that plenum. If the proposed design does not have a plenum, then induced air will be drawn from the space. |
Parallel PIU Induction Ratio | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The ratio of induction-side airflow of a fan-powered box at design heating conditions to the primary airflow |
Units | Ratio |
Input Restrictions | As designed |
Baseline Rules | 50% |
Parallel Fan Box Thermostat Setpoint | |
Applicability | HVAC zones that have parallel fan powered boxes |
---|---|
Definition | The temperature difference above the heating setpoint at which the parallel fan is turned on |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | 2°F above the heating setpoint schedule |
Baseline Rules | 2°F above the heating setpoint schedule |
Zone Exhaust
This group of building descriptors describes the rate of exhaust and the schedule or control for this exhaust. An exhaust system can serve one thermal block or multiple thermal blocks. Energy is summed for the exhaust system level, not the thermal block level.
Exhaust Fan Name | |
Applicability | All HVAC zones |
---|---|
Definition | A reference to an exhaust fan system that serves the thermal block |
Units | Text or other unique reference to an exhaust fan system defined in the secondary systems section. |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Exhaust Air Flow Rate | |
Applicability | All HVAC zones |
---|---|
Definition | Rate of exhaust from a thermal block |
Units | cfm |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Exhaust Fan Schedule | |
Applicability | All HVAC zones |
---|---|
Definition | Schedule indicating the pattern of use for exhaust air from the thermal block. This input should consider the position of fume hood sash opening. For toilets and other exhaust applications, the schedule may coincide with the operation of the exhaust fan system. |
Units | Data structure: schedule, fraction |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Outdoor Air Ventilation
Ventilation Source | |
Applicability | All HVAC zones |
---|---|
Definition |
The source of ventilation for an HVAC system. The choices are:
|
Units | List: natural or mechanical |
Input Restrictions | For residential units and hotel/motel guest rooms, as designed. For all other occupancies, set to mechanical. |
Baseline Rules | For residential units, set to natural, for all other occupancies, set equal to the value for the proposed design (mechanical). |
Design Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The quantity of ventilation air that is provided to the space for the specified thermal block at maximum occupancy |
Units | cfm or cfm/occupant |
Input Restrictions | For green building ratings and Design to Earn ENERGY STAR, the COMNET values from Table 4 of Appendix B shall be used as a default. Other values may be used with appropriate documentation. |
Baseline Rules |
Same as the proposed design except in the following cases:
|
Minimum Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The minimum quantity of ventilation air that must provided to the space when the HVAC system is operating |
Units | cfm or cfm/ft² |
Input Restrictions | As designed |
Baseline Rules | Same as the proposed design |
Ventilation Control Method | |
Applicability | All HVAC zones |
---|---|
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units | List (see above) |
Input Restrictions | As designed |
Baseline Rules |
For green building incentive programs, set to CO2 sensors in the space if the design occupancy is greater than 40 people per 1,000 ft² and the system design outdoor air flow rate is greater than 1,200 cfm, otherwise set to fixed ventilation rate.
For green building incentive programs, set to CO2 sensors in the space if the design occupancy is greater than 40 people per 1,000 ft² and the system design outdoor air flow rate is greater than 1,200 cfm, otherwise set to fixed ventilation rate.
|
This section addresses:
VAV Airflow
This group of building descriptors applies to proposed design systems that vary the volume of air at the zone level. The building descriptors are applicable for baseline building systems 5 through 8 and system 11.
Design Airflow |
|
Applicability |
Systems 5 through 8 and 11 that vary the volume of air at the zone level |
Definition |
The air delivery rate to each zone at design conditions |
Units |
cfm |
Input Restrictions |
As designed. If the UMLH in the proposed design are greater than 300, the simulation should not proceed and the user may have to modify the design airflow value. |
Baseline Building |
For systems 5 through 8 and 11, the software shall automatically size the system airflow to meet the baseline building loads based on
The baseline system airflow is determined by the load to be met by the airflow and the 20°F (11°C) temperature difference. The loads to be used would be the design load as determined by the sizing runs specified in Section G3.1.2.2, not the cooling or heating capacity of the system as determined using the sizing factors, also specified in G3.1.2.2. Using the system cooling and heating capacity will result in oversized baseline system airflows and energy cost because of the oversizing factors used in G3.1.2.2. For zones served by baseline systems with multiple zone thermostat setpoints (systems 5 to 8), the design set points used should result in either the lowest supply air cooling setpoint or highest heating supply air heating setpoint. If the proposed design HVAC system airflow rate based on latent loads greater than the same based on sensible loads, then the same supply-air-to-room humidity ratio difference (gr/lb) used to calculate the proposed design airflow should be used to calculate the design airflow rates for the baseline building. For baseline systems 9 and 10, the design supply airflow rates shall be based on the temperature difference between a SAT setpoint of 105°F and the design space heating temperature setpoint, the minimum outdoor airflow rate or the airflow rate required to comply with applicable codes, whichever is greater. |
Terminal Minimum Stop |
|
Applicability |
Systems that vary the volume of air at the zone level |
Definition |
The minimum airflow that will be delivered to a zone. For systems with reheat (system 5 to 8) the minimum flow before reheating occurs |
Units |
Unitless fraction of airflow (cfm) or specific airflow (cfm/ft²) |
Input Restrictions |
This input must be greater than or equal to the outside air ventilation rate |
Baseline Building |
For systems 5 to 8, the minimum airflow for the VAV reheat boxes should be set to 30% of the zone peak supply air volume or the outside air ventilation rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is larger. Refer to the section Zone Exhaust for requirements related to systems serving laboratory spaces. For baseline system 11, minimum volume setpoint shall be 50% of the maximum design airflow rate, the minimum ventilation outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is larger. Fan volume shall be reset from 100% airflow at 100% cooling load to minimum airflow at 50% cooling load. In heating mode, supply air temperature shall be modulated to maintain space temperature and fan volume shall be fixed at the minimum airflow. Systems serving laboratory spaces shall reduce the exhaust and makeup air volume during unoccupied periods to the largest of 50% of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards. |
Terminal Heating Control Type |
|
Applicability |
VAV boxes with reheat |
Definition |
The control strategy for the heating mode. The nomenclature in simulation programs to simulate this may differ from that provided below. Single Maximum In the single maximum control mode, the airflow is set to a minimum constant value in both the deadband and heating mode. This airflow can vary but is typically 30% to 50% of maximum. This control mode typically has a higher minimum airflow than the minimum used in the dual maximum below, resulting in more frequent reheat.
Figure 6. Single Maximum VAV Box Control (Courtesy: Taylor Engineering) Dual Maximum: raises the SAT as the first stage of heating, and increases the airflow to the zone as the second stage of heating. 1. The first stage of heating consists of modulating the zone SAT setpoint up to a maximum setpoint no larger than 95ºF while the airflow is maintained at the dead band flow rate. 2. The second stage of heating consists of modulating the airflow rate from the dead band flow rate up to the heating maximum flow rate (50% of design flow rate) while maintaining the maximum setpoint temperature.
Figure 7. Dual Maximum Control Sequence |
Units |
List: Single Maximum, Dual Maximum |
Input Restrictions |
As designed |
Baseline Building |
Single maximum at 30% of zone peak airflow or the outside air ventilation rate, or the airflow rate required to comply with applicable codes or accreditation standards, whichever is larger. The ventilation outdoor air and exhaust/relief dampers should be shut-off during preoccupancy building warm-up, cool down and setback except for economizer operation. Refer to the section Zone Exhaust for requirements related to laboratory spaces. For baseline system 11, fan volume shall be reset from 100% airflow at 100% load to minimum airflow at 50% cooling load. The minimum airflow shall be 50% of the maximum design airflow rate, the minimum ventilation rate or the airflow required to comply with applicable codes or accreditation stations, whichever is larger. Systems serving laboratory spaces shall reduce the exhaust and makeup air volume during unoccupied periods to the largest of 50% of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards. |
This group of building descriptors applies to terminal equipment that includes zone fans for overhead VAV systems. The building descriptors are applicable for baseline building systems 6 and 8. When parallel fan powered boxes are required for the baseline building, terminal fans shall run as the first stage of heating before the reheat coil is energized. Fans in parallel VAV fan-powered boxes shall be sized for 50% of the peak design primary air (from the VAV air-handling unit) flow rate and shall be modeled with 0.35 W/cfm fan power. Minimum volume setpoints for fan-powered boxes shall be equal to 30% of peak design primary airflow rate or the rate required to meet the minimum outdoor air ventilation requirement, whichever is larger. The supply air temperature setpoint shall be constant at the design condition.
Fan-Powered Box Type |
|
Applicability |
HVAC zones that have fan-powered boxes |
Definition |
Defines the type of fan-powered induction box. This is either:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
Applicable to baseline systems 6 and 8 and the fan-powered box type is parallel, with a constant volume fan |
Fan Power |
|
Applicability |
HVAC zones that have fan-powered boxes |
Definition |
The rated power input of the fan in a fan-powered box |
Units |
W or W/cfm |
Input Restrictions |
As designed |
Baseline Building |
For baseline building systems 6 and 8, power is prescribed at 0.35 W/cfm |
Parallel Fan-Powered Box-Induced Air Zone |
|
Applicability |
HVAC zones that have fan-powered boxes |
Definition |
Zone from which a series or parallel fan-powered box draws its air |
Units |
List (of zones) |
Input Restrictions |
As designed |
Baseline Building |
If the proposed design has a plenum, then induced air will be drawn from that plenum. If the proposed design does not have a plenum, then induced air will be drawn from the space. |
Parallel Fan-Powered Box- Induction Ratio |
|
Applicability |
HVAC zones that have fan-powered boxes |
Definition |
The ratio of induction-side airflow of a fan-powered box at design heating conditions to the design primary airflow |
Units |
Ratio |
Input Restrictions |
As designed |
Baseline Building |
50% |
Parallel Fan Box Thermostat Setpoint |
|
Applicability |
HVAC zones that have parallel fan-powered boxes |
Definition |
The temperature difference above the heating setpoint at which the parallel fan is turned on |
Units |
Degrees Fahrenheit (°F) |
Input Restrictions |
2°F above the heating setpoint schedule |
Baseline Building |
2°F above the heating setpoint schedule |
Fan-Powered Boxes: Terminal Heating Control Type |
|
Applicability |
HVAC zones that have parallel fan-powered boxes |
Definition |
Fan Control: With parallel style fan-powered VAV boxes, the constant volume terminal unit fan is only on when the primary airflow is at design minimum and the zone temperature is less than 2°F above the heating setpoint schedule. When the system is scheduled to operate and the zone terminal fan is running, the box mixes plenum air with primary air. Heating Operation: During heating mode, the terminal unit discharge air temperature is increased from minimum to the design heating temperature. Throughout occupied heating the cooling, primary airflow is kept at design minimum and the terminal unit fan is running. Deadband Operation: The cooling primary airflow is kept at minimum airflow and the heating valve is closed. The terminal unit fan will energize as the first stage of heating when the zone temperature drops to 2°F. above heating setpoint. Cooling Operation: As the space temperature increases, the cooling supply airflow is increased from minimum to design cooling maximum. Throughout cooling the box fan is off. To comply with Standard 90.1-2019 Section 6.5.2.1, Exception (1), the minimum primary airflow for this control logic must be no larger than 30% of the zone design cooling airflow or the minimum airflow for ventilation. Night Cycle Heating Control: A call for heating during night cycle control shall be met by running the terminal fan and increasing the terminal unit discharge air temperature from minimum to the design heating temperature without the use of primary air.
Single Maximum Parallel Fan Powered VAV Box Control:
Figure 8. Single Maximum Control Sequence for Parallel Fan Powered VAV with Reheat Boxes |
Units |
List: Single Maximum, Other |
Input Restrictions |
As designed |
Baseline Building |
Single maximum with minimum airflow rate set to 30% of peak design primary airflow rate or the outside air ventilation rate, whichever is larger |
This group of building descriptors describes the rate of exhaust and the schedule or control for this exhaust. An exhaust system can serve one thermal zone or multiple thermal zones. Energy is summed for the exhaust system level, not the thermal zone level.
Kitchen: Exhaust Hood Length |
|
Applicability |
Exhaust fans in spaces of type kitchen |
Definition |
The exhaust hood length |
Units |
ft |
Input Restrictions |
As designed |
Baseline Building |
Same as the proposed design |
Kitchen: Exhaust Hood Style |
|
Applicability |
Exhaust fans in spaces of type kitchen |
Definition |
This input defines the style of the kitchen hood |
Units |
List: Wall-Mounted Canopy, Single Island, Double Island, Eyebrow, Backshelf/Passover |
Input Restrictions |
As designed |
Baseline Building |
Same as the proposed design |
Kitchen: Exhaust Hood Cooking Duty |
|
Applicability |
Exhaust fans in spaces of type kitchen |
Definition |
The hood cooking duty as defined in Table 6.5.7.2.2 of Standard 90.1-2019 |
Units |
List: Light Duty, Medium Duty, Heavy Duty, Extra Heavy Duty |
Input Restrictions |
As designed |
Baseline Building |
Same as the proposed design |
Kitchen: Exhaust Airflow Rate |
|||||||||||||||||||||||||||||||
Applicability |
Exhaust fans in spaces of type kitchen |
||||||||||||||||||||||||||||||
Definition |
Rate of exhaust from a thermal zone. Standard 90.1-2019, Section 6.5.7.2.2, requires each hood in a kitchen/dining facility with a total kitchen hood exhaust airflow rate greater than 5,000 cfm to have an exhaust rate that complies with Table 39. If a single hood, or hood section, is installed over appliances with different duty ratings, then the maximum allowable flow rate for the hood or hood section shall not exceed the Table 39 values for the highest appliance duty rating under the hood or hood section.
Table 39. Maximum Net Exhaust Flow Rate, cfm per Linear Foot of Hood Length
|
||||||||||||||||||||||||||||||
Units |
cfm |
||||||||||||||||||||||||||||||
Input Restrictions |
As designed |
||||||||||||||||||||||||||||||
Baseline Building |
The exhaust air flow rate for the baseline building should be equal to the exhaust flow rate prescribed in Table 39 |
Kitchen: Demand Ventilation |
|
Applicability |
All kitchen HVAC zones |
Definition |
A demand ventilation system uses a light beam and a photo detector to detect the presence of smoke. It also has a temperature sensor to detect heat. The exhaust fan slows down below design levels and both exhaust and replacement airflow rates are reduced when the system detects no smoke or heat. |
Units |
Unitless |
Input Restrictions |
As designed. Exhaust fans controlled with a demand ventilation system with a minimum flow no more than 50% shall be modeled as running at 75% during all exhaust fan operating hours. |
Baseline Building |
Same as proposed except fan speed would not be reduced due to demand ventilation systems |
Laboratory: Exhaust Minimum Airflow Rate |
|
Applicability |
All laboratory zones |
Definition |
Rate of exhaust from a zone |
Units |
cfm |
Input Restrictions |
As designed |
Baseline Building |
Same as proposed except for the unoccupied periods, where systems serving laboratory spaces shall reduce the exhaust and makeup air volume during unoccupied periods to the largest of 50% of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards. Baseline systems serving only laboratory spaces that are prohibited from recirculating return air by code or accretion standard, the baseline system shall be modeled with 100% outdoor air. |
Exhaust Fan Name |
|
Applicability |
All HVAC zones |
Definition |
A reference to an exhaust fan system that serves the thermal zone |
Units |
Text or other unique reference to an exhaust fan system defined in the secondary systems section |
Input Restrictions |
As designed |
Baseline Building |
Same as the proposed design |
Exhaust Fan Operation Schedule |
|
Applicability |
All HVAC zones |
Definition |
Schedule indicating the pattern of use for exhaust air from the thermal zone. For laboratory exhaust hoods, this input should consider the position of fume hood sash opening. For toilets and other exhaust applications, the schedule may coincide with the operation of the exhaust fan system. |
Units |
Data structure: schedule, fraction |
Input Restrictions |
As designed |
Baseline Building |
Same as proposed except for the unoccupied periods, where systems serving laboratory spaces shall reduce the exhaust and makeup air volume during unoccupied periods to the largest of 50% of zone peak airflow, the minimum outdoor airflow rate, or the airflow rate required to comply with applicable codes or accreditation standards |
Outdoor Air Ventilation Source |
|
Applicability |
All HVAC zones |
Definition |
The source of outdoor air ventilation for an HVAC system. The choices are:
|
Units |
List: Natural or mechanical |
Input Restrictions |
As designed |
Baseline Building |
Ventilation is set to mechanical for the baseline building |
Minimum Outdoor Air Ventilation Rate |
|
Applicability |
All HVAC zones |
Definition |
The minimum quantity of outdoor ventilation air that must be provided to the space when it is occupied |
Units |
cfm or cfm/ft² |
Input Restrictions |
As designed |
Baseline Building |
Minimum ventilation system outdoor air intake flow shall be the same for the proposed and baseline building designs. Except in the following conditions:
|
Example |
Example 1: Should DCV be required in the following case? Can a savings credit be taken?
Answer: No the design does not meet the exceptions listed above, therefor both designs should be modeled with DCV. If the design airflow of the system in question was less than 3000 CFM then DCV would only be modeled in the proposed case and credit could be taken. |
Design Outdoor Air Ventilation Rate and Schedule |
|
Applicability |
All HVAC zones |
Definition |
The quantity of outdoor air ventilation that is provided to the space for the specified thermal zone at maximum occupancy |
Units |
cfm or cfm/occupant |
Input Restrictions |
The outdoor air ventilation rate would be as designed. Outdoor air ventilation schedule for proposed building can be either of the two:
Some proposed building designs might bring in ventilation air during unoccupied hours for night flush or economizer operation. Due to these reasons, an option for user input of schedule for outdoor air availability is provided. |
Baseline Building |
Same as proposed, except:
|
Ventilation Control Method |
|
Applicability |
All HVAC zones |
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
Baseline building shall be modeled with a fixed ventilation rate which would be equal to the design ventilation rate (see above). No ventilation control methods shall be modeled for the baseline building design except for the following:
|
Design Ventilation Rate: Demand Control Ventilation |
|
Applicability |
All HVAC zones |
Definition |
Demand control ventilation is required for spaces larger than 500 ft2 and with a design occupancy for ventilation of greater than or equal to 25 people per 1000 ft2 of floor area and served by systems with one or more of the following:
Exceptions:
|
Units |
cfm or cfm/occupant |
Input Restrictions |
As designed. DCV is a mandatory requirement for spaces larger than 500 ft2, with design occupancy of more than 25 people per 1000 ft2 unless any of the exceptions specified above apply. |
Baseline Building |
DCV is not modeled for the baseline building except for zones served by systems with outdoor air greater than or equal to 3000 cfm and occupant density of 100 people per 1000 ft2 or less |
Ventilation Standard |
|
Applicability |
All projects |
Definition |
The ventilation standard used for the calculation of minimum ventilation rate required. The ventilation rates are defined based on the ventilation standard selected. This should be specified at the project level. |
Units |
List. ASHRAE Standard 62.1, IMC-2012, Title-24-2013, ASHRAE 170, Other |
Input Restrictions |
No restrictions. Any of the defined standards can be selected. |
Baseline Building |
Same as proposed The baseline rules for determining the use of DCV are defined according to Standard 90.1-2019, for any specified standard, including ‘Other’. |
Ventilation Specification Method |
|
Applicability |
All HVAC zones |
Definition |
The method used to calculate total ventilation rates to a zone. The input must be either “Sum,” “Maximum,” or “No Ventilation.”
|
Units |
List: Sum, Maximum, No Ventilation |
Input Restrictions |
As designed. For ventilation standard specified as = “62.1” and “IMC-2012,” the only available specification method would be “Sum.” For “T24-2013,” the only available specification method is “Maximum.” For ventilation standard specified as “Other,” the specification method can be specified as either Sum or Maximum, and includes all components. |
Baseline Building |
Same as proposed |
Zone Air Distribution Effectiveness |
|||||||||||||||||||||||
Applicability |
All HVAC zones and spaces |
||||||||||||||||||||||
Definition |
The zone air distribution effectiveness (Ez) shall be no greater than the default value determined using Table 40. Table 40. Air Distribution Effectiveness (ASHRAE Standard 62.1-2010)
|
||||||||||||||||||||||
Units |
None |
||||||||||||||||||||||
Input Restrictions |
As designed |
||||||||||||||||||||||
Baseline Building |
Same as proposed |
Ventilation Multiplier |
|
Applicability |
All projects |
Definition |
The ventilation multiplier is defined at the project level. This multiplier is applied to the user’s design component ventilation rates (Ra and Rp) to uniformly increase the component ventilation rates entered. The principal purpose of the multiplier is to facilitate simulating a uniform increase in proposed design ventilation rates, such as for buildings pursuing the LEED credit for 30% increased ventilation. |
Units |
No units |
Input Restrictions |
As designed. The default value is 1. |
Baseline Building |
The ventilation multiplier is always 1 for the baseline building |
Ventilation Rates |
|
Applicability |
All HVAC zones |
Definition |
The method used to calculate total ventilation rates to a zone. The input must be either flow/person, flow/area, flow/zone, air changes/hour, sum, or maximum.
|
Units |
List: Flow/Person, Flow/Area, Air Changes per Hour |
Input Restrictions |
As designed. If the user specifies ventilation standard as ‘Other’ and DCV is used, a non-zero value for Rp must be specified for the ventilation air flow to vary with occupancy. |
Baseline Building |
The ventilation rates for the baseline building are determined by the ventilation standard and the space function. For zones/spaces with ventilation standard specified as ‘Other’
|
Total Design Zone Ventilation Airflow |
|||
Applicability |
All HVAC zones |
||
Definition |
The total design outdoor air supplied to a zone (Vz-design). Minimum outdoor air supplied to a zone (Vbz-min) is calculated based on the user input values of the ventilation multiplier (Vm), Ez, Ra and Rp. The method used to calculate total minimum ventilation airflow to a zone is specified below-
Where, Vbz-min = Total Breathing Zone Outdoor Airflow (CFM) Vm = Ventilation Multiplier Rp = Outdoor Airflow Rate per Person (CFM/person) Ra = Outdoor Airflow Rate per unit Area (CFM/ft2) Pz = Zone Population: The number of people in the zone during typical occupancy Az = Zone Floor Area (ft2): the net occupiable floor area of the zone. |
||
Units |
List: CFM |
||
Input Restrictions |
As designed. The total design ventilation airflows should also include the impact of Ez and the ventilation multiplier. The user entered value for space/zone design ventilation airflow is required to be within 3% of the value calculated from the user entered Ra, Rp, Ez and Vm values. The user is required to modify the values for Ra, Rp or Ez such that the total airflow calculated from the components and the user defined airflow is within the tolerance limit. Similarly, if DCV controls are used in the proposed building design, the user entered value for Vz-design should be within 3% tolerance of the value calculated by the design area rate component (Ra) and Ez. Exhaust airflows are checked at the building story level. If the sum of proposed total design ventilation airflows for all spaces on a building story level (excluding spaces with ventilation standard specified as ‘Other’) is not within 10% of the calculated total code minimum ventilation airflow. To proceed, either the ventilation airflows for spaces that are under-ventilated, need to be increased or alternatively, the ventilation standard should be specified as ‘Other’ for spaces that are under-ventilated. For zones/spaces with DCV controls, the minimum ventilation airflow is the airflow when the space is unoccupied, calculated using the area component and Ez. |
||
Baseline Building |
The baseline design ventilation airflow rates for all spaces/thermal zones equal the proposed with the exception of the following:
|
Total System Design Ventilation Airflow |
|
Applicability |
All HVAC systems. |
Definition |
The design outdoor air intake at the system level (Vs-design) |
Units |
CFM |
Input Restrictions |
As designed Software tools are required to verify the input value for Vs-design. For all the zones served by the system, software tools are required to sum the zone level ventilation (Vbz-min) to calculate the minimum ventilation at the system level (Vs-min). If the design outdoor air intake (Vs-design) is less than the minimum ventilation airflow (Vs-min), the input should be flagged and the user should be required to increase the value for Vs-design until it is equal to or greater thanVs-min. |
Baseline Building |
The total system ventilation airflow for the baseline building is the sum of the zone level ventilation for the baseline building |
System Ventilation Efficiency |
|||
Applicability |
All HVAC systems |
||
Definition |
The efficiency of the ventilation system (Ev). This is the ratio of the design ventilation airflow to the minimum system ventilation airflow.
|
||
Units |
Ratio (unitless) |
||
Input Restrictions |
Calculated by software tool Software tools are required to calculate and verify the input value for Ev. The maximum value of Ev=1 (for single zone systems). If Ev is greater than 1, an error should be displayed to the user and the user is required to increase the value of Vs-design until the value of Ev is less than or equal to 1. |
||
Baseline Building |
Same as proposed for all zones served by the proposed system. In the scenario where the building has a multizone system in the proposed case, but single zone system in the baseline case, all the zones served by the Multizone system in the proposed case have Ev same as the proposed system. Similarly, if the proposed system is single zone and the baseline building has multizone systems, then the corresponding zones would have Ev specified as 1, same as the proposed building. This approach ensures that the ventilation rates are the same between the baseline and the proposed building. |
VAV Air Flow
This group of building descriptors applies to proposed design systems that vary the volume of air at the zone level. The building descriptors are applicable for baseline building systems 5 through 8.
Design Airflow | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The air delivery rate at design conditions |
Units | cfm |
Input Restrictions | As designed. If the unmet load hours in the proposed design are greater than 300, the building descriptor may need to be modified to meet the criterion. |
Terminal Minimum Stop | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The minimum airflow that will be delivered by a terminal unit before reheating occurs |
Units | Unitless fraction airflow (cfm) or specific airflow (cfm/ft²) |
Input Restrictions | This input must be greater than or equal to the outside air ventilation rate. |
Fan Powered Boxes
Fan Powered Box Type | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition |
Defines the type of fan-powered induction box. This is either:
|
Units | List (see above) |
Input Restrictions | As designed |
Fan Power | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The rated power input of the fan in a fan-powered box. |
Units | W or W/cfm |
Input Restrictions | As designed |
Fan Power Box Induced Air Zone | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | Zone from which a series or parallel fan-powered box draws its air |
Units | List (of zones) |
Input Restrictions | As designed |
Parallel PIU Induction Ratio | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The ratio of induction-side airflow of a fan-powered box at design heating conditions to the primary airflow |
Units | Ratio |
Input Restrictions | As designed |
Parallel Fan Box Thermostat Setpoint | |
Applicability | HVAC zones that have parallel fan powered boxes |
---|---|
Definition | The temperature difference above the heating setpoint at which the parallel fan is turned on |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | 2°F above the heating setpoint schedule |
Zone Exhaust
This group of building descriptors describes the rate of exhaust and the schedule or control for this exhaust. An exhaust system can serve one thermal block or multiple thermal blocks. Energy is summed for the exhaust system level, not the thermal block level.
Exhaust Fan Name | |
Applicability | All HVAC zones |
---|---|
Definition | A reference to an exhaust fan system that serves the thermal block |
Units | Text or other unique reference to an exhaust fan system defined in the secondary systems section. |
Input Restrictions | As designed |
Exhaust Air Flow Rate | |
Applicability | All HVAC zones |
---|---|
Definition | Rate of exhaust from a thermal block |
Units | cfm |
Input Restrictions | As designed |
Exhaust Fan Schedule | |
Applicability | All HVAC zones |
---|---|
Definition | Schedule indicating the pattern of use for exhaust air from the thermal block. This input should consider the position of fume hood sash opening. For toilets and other exhaust applications, the schedule may coincide with the operation of the exhaust fan system. |
Units | Data structure: schedule, fraction |
Input Restrictions | As designed |
Outdoor Air Ventilation
Ventilation Source | |
Applicability | All HVAC zones |
---|---|
Definition |
The source of ventilation for an HVAC system. The choices are:
|
Units | List: natural or mechanical |
Input Restrictions | For residential units and hotel/motel guest rooms, as designed. For all other occupancies, set to mechanical. |
Design Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The quantity of ventilation air that is provided to the space for the specified thermal block at maximum occupancy |
Units | cfm or cfm/occupant |
Input Restrictions | For green building ratings and Design to Earn ENERGY STAR, the COMNET values from Table 4 of Appendix B shall be used as a default. Other values may be used with appropriate documentation. |
Minimum Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The minimum quantity of ventilation air that must provided to the space when the HVAC system is operating |
Units | cfm or cfm/ft² |
Input Restrictions | As designed |
Ventilation Control Method | |
Applicability | All HVAC zones |
---|---|
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units | List (see above) |
Input Restrictions | As designed |
VAV Air Flow
This group of building descriptors applies to proposed design systems that vary the volume of air at the zone level. The building descriptors are applicable for baseline building systems 5 through 8.
Design Airflow | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The air delivery rate at design conditions |
Units | cfm |
Input Restrictions | As designed. If the unmet load hours in the proposed design are greater than 300, the building descriptor may need to be modified to meet the criterion. |
Terminal Minimum Stop | |
Applicability | Systems that vary the volume of air at the zone level |
---|---|
Definition | The minimum airflow that will be delivered by a terminal unit before reheating occurs |
Units | Unitless fraction airflow (cfm) or specific airflow (cfm/ft²) |
Input Restrictions | This input must be greater than or equal to the outside air ventilation rate. |
Fan Powered Boxes
Fan Powered Box Type | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition |
Defines the type of fan-powered induction box. This is either:
|
Units | List (see above) |
Input Restrictions | As designed |
Fan Power | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The rated power input of the fan in a fan-powered box. |
Units | W or W/cfm |
Input Restrictions | As designed |
Fan Power Box Induced Air Zone | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | Zone from which a series or parallel fan-powered box draws its air |
Units | List (of zones) |
Input Restrictions | As designed |
Parallel PIU Induction Ratio | |
Applicability | HVAC zones that have fan powered boxes |
---|---|
Definition | The ratio of induction-side airflow of a fan-powered box at design heating conditions to the primary airflow |
Units | Ratio |
Input Restrictions | As designed |
Parallel Fan Box Thermostat Setpoint | |
Applicability | HVAC zones that have parallel fan powered boxes |
---|---|
Definition | The temperature difference above the heating setpoint at which the parallel fan is turned on |
Units | Degrees Fahrenheit (°F) |
Input Restrictions | 2°F above the heating setpoint schedule |
Zone Exhaust
This group of building descriptors describes the rate of exhaust and the schedule or control for this exhaust. An exhaust system can serve one thermal block or multiple thermal blocks. Energy is summed for the exhaust system level, not the thermal block level.
Exhaust Fan Name | |
Applicability | All HVAC zones |
---|---|
Definition | A reference to an exhaust fan system that serves the thermal block |
Units | Text or other unique reference to an exhaust fan system defined in the secondary systems section. |
Input Restrictions | As designed |
Exhaust Air Flow Rate | |
Applicability | All HVAC zones |
---|---|
Definition | Rate of exhaust from a thermal block |
Units | cfm |
Input Restrictions | As designed |
Exhaust Fan Schedule | |
Applicability | All HVAC zones |
---|---|
Definition | Schedule indicating the pattern of use for exhaust air from the thermal block. This input should consider the position of fume hood sash opening. For toilets and other exhaust applications, the schedule may coincide with the operation of the exhaust fan system. |
Units | Data structure: schedule, fraction |
Input Restrictions | As designed |
Outdoor Air Ventilation
Ventilation Source | |
Applicability | All HVAC zones |
---|---|
Definition |
The source of ventilation for an HVAC system. The choices are:
|
Units | List: natural or mechanical |
Input Restrictions | For residential units and hotel/motel guest rooms, as designed. For all other occupancies, set to mechanical. |
Design Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The quantity of ventilation air that is provided to the space for the specified thermal block at maximum occupancy |
Units | cfm or cfm/occupant |
Input Restrictions | For green building ratings and Design to Earn ENERGY STAR, the COMNET values from Table 4 of Appendix B shall be used as a default. Other values may be used with appropriate documentation. |
Minimum Ventilation Rate | |
Applicability | All HVAC zones |
---|---|
Definition | The minimum quantity of ventilation air that must provided to the space when the HVAC system is operating |
Units | cfm or cfm/ft² |
Input Restrictions | As designed |
Ventilation Control Method | |
Applicability | All HVAC zones |
---|---|
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units | List (see above) |
Input Restrictions | As designed |