HVAC System Name | |
Applicability |
All system types |
---|---|
Units | Text, unique |
Input Restrictions | When applicable, this input should match the tags that are used on the plans. |
Baseline Rules | None |
System Type | |
Applicability | All system types |
---|---|
Definition | A unique descriptor which identifies the following attributes of an HVAC System:
|
Units | None |
Input Restrictions | As designed |
Baseline Rules | Based on the prescribed system type (see [bookref id="hvac-mapping"]). The baseline system types are shown in the table below. |
[table title="Baseline Building System Type" id="baseline-building-system-type"]
Baseline Building System | System Type |
System 1 – PTAC | Single Zone Heating and Cooling |
System 2 – PTHP | Single Zone Heating and Cooling |
System 3 – PSZ-AC | Single Zone Heating and Cooling |
System 4 – PSZ-HP | Single Zone Heating and Cooling |
System 5 – Packaged VAV with Reheat | Single Duct VAV |
System 6 – Packaged VAV with PFP boxes | Single Duct VAV |
System 7 – VAV with Reheat | Single Duct VAV |
System 8 – VAV with PFP boxes | Single Duct VAV |
Total Cooling Capacity | |
Applicability |
All system types |
---|---|
Definition | The installed cooling capacity of the project. This includes all:
|
Units | Cooling tons (12,000 Btu/h per ton) |
Input Restrictions | As designed. This could be calculated by the program from the proposed design building description or a separate load calculation may be used. Unmet load hours for the simulation shall not exceed 300 annually. Weather conditions used in sizing runs shall be based on 1% dry-bulb and 1% wet-bulb cooling design temperatures. |
Baseline Rules | Autosize. The cooling capacity shall be oversized by 15%. If the number of unmet load hours of the proposed design exceeds the number of unmet load hours of the baseline by more than 50, decrease the cooling capacity as indicated in [bookref id="calculation-process-for-tax-deductions-and-green-building-ratings"] and [bookref id="procedure-for-adjusting-equipment-hvac-sizes-in-the-baseline-building"]. |
HVAC System Name | |
Applicability |
All system types |
---|---|
Units | Text, unique |
Input Restrictions | When applicable, this input should match the tags that are used on the plans. |
Baseline Rules | None |
System Type | |
Applicability | All system types |
---|---|
Definition | A unique descriptor which identifies the following attributes of an HVAC System:
|
Units | None |
Input Restrictions | As designed |
Baseline Rules | Based on the prescribed system type (see Table 6.7.1-1). The baseline system types are shown in the table below. |
Table 6.7.1-1: Baseline Building System Type
Baseline Building System | System Type |
System 1 – PTAC | Single Zone Heating and Cooling |
System 2 – PTHP | Single Zone Heating and Cooling |
System 3 – PSZ-AC | Single Zone Heating and Cooling |
System 4 – PSZ-HP | Single Zone Heating and Cooling |
System 5 – Packaged VAV with Reheat | Single Duct VAV |
System 6 – Packaged VAV with PFP boxes | Single Duct VAV |
System 7 – VAV with Reheat | Single Duct VAV |
System 8 – VAV with PFP boxes | Single Duct VAV |
System 9 – Heating and Ventilation | Constant Volume Heat/Vent (no cooling) |
System 10 – Heating and Ventilation | Constant Volume Heat/Vent (no cooling) |
Total Cooling Capacity | |
Applicability |
All system types |
---|---|
Definition | The installed cooling capacity of the project. This includes all:
|
Units | Cooling tons (12,000 Btu/h per ton) |
Input Restrictions | As designed. This could be calculated by the program from the proposed design building description or a separate load calculation may be used. Unmet load hours for the simulation shall not exceed 300 annually. Weather conditions used in sizing runs shall be based on 1% dry-bulb and 1% wet-bulb cooling design temperatures. |
Baseline Rules | Autosize. The cooling capacity shall be oversized by 15%. |
HVAC System Name |
|
---|---|
Applicability |
All system types |
Units |
Text, unique |
Input Restrictions |
When applicable, this input should match the tags that are used on the plans. |
Baseline Rules |
None |
System Type |
|
---|---|
Applicability |
All system types |
Definition |
A unique descriptor which identifies the following attributes of an HVAC System:
|
Units |
List |
Input Restrictions |
System types listed in Table 3.7-1, plus others supported by the software such as the following:
|
Baseline Rules |
The baseline building HVAC system is determined based on the building and space use, size and heating source. See Table 3.7-1. |
Air Distribution Type |
|
---|---|
Applicability |
All system types |
Definition |
Type of air distribution system that is coupled with the HVAC system. The choices are (overhead) mixing ventilation system, underfloor air distribution system (UFAD), and displacement ventilation system (DV). |
Units |
List: Mixing, UFAD, DV |
Input Restrictions |
As designed. |
Baseline Rules |
Mixing |
Thermal Zone List |
|
---|---|
Applicability |
All system types |
Definition |
Comprehensive list of all thermal zones served by a given HVAC system. |
Units |
Cooling tons (12,000 Btu/h per ton) |
Input Restrictions |
As designed. |
Baseline Rules |
For systems 1, 2, 3, 4, 9, and 10, each zone shall have its own system. For systems 5, 6, 7, and 8, all zones on each floor shall be assigned to a single system. |
Total Cooling Capacity |
|
---|---|
Applicability |
All system types |
Definition |
The installed cooling capacity of the project. This includes all:
|
Units |
Cooling tons (12,000 Btu/h per ton) |
Input Restrictions |
As designed. This could be calculated by the simulation program from the proposed design building description or a separate load calculation may be used. Unmet load hours for the simulation shall not exceed 300 annually. Weather conditions used in sizing runs shall be based on 1% dry-bulb and 1% wet-bulb cooling design temperatures. |
Baseline Rules |
Autosize. The cooling capacity shall be oversized by 15%. If the number of unmet load hours exceeds 300, increase the cooling capacity according to the procedures in Chapter 2. |
Total Heating Capacity |
|
---|---|
Applicability |
All system types |
Definition |
The installed heating capacity of the project. This includes all:
|
Units |
Btu/h |
Input Restrictions |
As designed. |
Baseline Rules |
Autosize. The cooling capacity shall be oversized by 25%. If the number of unmet load hours exceeds 300, increase the heating capacity according to the procedures in Chapter 2. |
HVAC System Name | |
---|---|
Applicability | All system types |
Definition | A unique descriptor for each HVAC system |
Units | Text, unique |
Input Restrictions | When applicable, this input should match the tags that are used on the plans |
Baseline Building | None |
System Type | |||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability | All system types | ||||||||||||||||||||||||||||||||||||||||||||||||||||
Definition |
A unique descriptor that identifies the following attributes of an HVAC system: · Number of air decks (one to three); · Constant or variable airflow; · Type of terminal device; and · Fan configuration for multiple deck systems. |
||||||||||||||||||||||||||||||||||||||||||||||||||||
Units |
List: · PTAC – Packaged Terminal Air Conditioner · PTHP – Packaged Terminal Heat Pump · PSZ-AC – Packaged Single Zone Air Conditioner · PSZ-HP – Packaged Single Zone Heat Pump · PVAV – Packaged VAV with Reheat · VAV – VAV with Reheat · PSZVAV – Packaged Single Zone VAV · PSZVAVHP – Packaged Single Zone VAV Heat Pump · HV – Heating and Ventilation Only · CRAC – Computer Room Air Conditioner · CRAH – Computer Room Air Handler · FPFC – Four-Pipe Fan Coil · TPFC- Two Pipe Fan Coil · SFDD – Single Fan Dual Duct · DFDD – Dual-Fan Dual Duct · RADFLR – Radiant Floor Heating And Cooling · WSHP – Water-Source Heat Pump · ACB- Active Chilled Beams · PCB- Passive chilled Beams · Other |
||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions | As designed | ||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Building |
Based on the prescribed system type in the HVAC system map. The baseline system types are shown in the table below. Table 51. Baseline Building System Type
|
HVAC System Name | |
Applicability |
All system types |
---|---|
Units | Text, unique |
Input Restrictions | When applicable, this input should match the tags that are used on the plans. |
System Type | |
Applicability | All system types |
---|---|
Definition | A unique descriptor which identifies the following attributes of an HVAC System:
|
Units | None |
Input Restrictions | As designed |
Total Cooling Capacity | |
Applicability |
All system types |
---|---|
Definition | The installed cooling capacity of the project. This includes all:
|
Units | Cooling tons (12,000 Btu/h per ton) |
Input Restrictions | As designed. This could be calculated by the program from the proposed design building description or a separate load calculation may be used. Unmet load hours for the simulation shall not exceed 300 annually. Weather conditions used in sizing runs shall be based on 1% dry-bulb and 1% wet-bulb cooling design temperatures. |
HVAC System Name | |
Applicability |
All system types |
---|---|
Units | Text, unique |
Input Restrictions | When applicable, this input should match the tags that are used on the plans. |
System Type | |
Applicability | All system types |
---|---|
Definition | A unique descriptor which identifies the following attributes of an HVAC System:
|
Units | None |
Input Restrictions | As designed |
Total Cooling Capacity | |
Applicability |
All system types |
---|---|
Definition | The installed cooling capacity of the project. This includes all:
|
Units | Cooling tons (12,000 Btu/h per ton) |
Input Restrictions | As designed. This could be calculated by the program from the proposed design building description or a separate load calculation may be used. Unmet load hours for the simulation shall not exceed 300 annually. Weather conditions used in sizing runs shall be based on 1% dry-bulb and 1% wet-bulb cooling design temperatures. |