G3.2 New Construction/Major Alterations
This section only applies to projects following Standard 90.1-2022 Section G3.2. This is because alterations are exempt from the on-site renewable energy requirements in Standard 90.1-2022 Section 10.5.1.
The PCIt (performance cost index target) equation in Standard 90.1-2022 Section 4.2.1.1 includes a term to account for proposed building performance excluding any renewable energy systems in the proposed design and including an on-site renewable energy system that meets but does not exceed the requirements of Section 10.5.1.1 modeled following the requirements for a budget building design in Table 12.5.1, row 15 (PBPpre). Recall, for a project following 90.1 2022 Appendix G to be considered minimally compliant with 90.1 2022 the PCI performance cost index (PCI) needs to be less than or equal to the PCIt. The descriptors below are for modeling PBPpre when no on-site generation systems are specified in the proposed design.
|
Shading Objects |
|
|---|---|
|
Applicability |
PV systems when no on-site renewable systems are specified in the proposed design. |
|
Definition |
A unique identifier that can be used to reference shading objects. |
|
Units |
Text, Unique |
|
Input Restrictions |
None.Unshaded. |
|
Baseline Building |
None (PV not modeled for the baseline building) |
|
Size |
|
|---|---|
|
Applicability |
PV systems when no on-site renewable systems are specified in the proposed design. |
|
Definition |
The size describes the rated capacity of the PV system. |
|
Units |
Power, kW or Btuh. |
|
Input Restrictions |
Established per Standard 90.1-2022 Section 10.5.1.1 which requires that the building site shall have equipment for on-site renewable energy with a rated capacity of not less than 0.50 W/ft2 or 1.7 Btu/ft2 multiplied by the sum of the gross conditioned floor area for all floors up to the three largest floors. The following exceptions apply:
|
|
Baseline Building |
None (PV not modeled for the baseline building) |
|
Module Type and Efficiency |
|
|---|---|
|
Applicability |
PV systems when no on-site renewable systems are specified in the proposed design. |
|
Definition |
The type and efficiency of the PV system. |
|
Units |
Text and Ratio. |
|
Input Restrictions |
Crystalline silicon panel with a glass cover, 19.1% nominal efficiency; performance shall be based on a reference temperature of 77°F and irradiance of 317 Btu/ft2·h. |
|
Baseline Building |
None (PV not modeled for the baseline building) |
|
Module Temperature Coefficient |
|
|---|---|
|
Applicability |
PV systems when no on-site renewable systems are specified in the proposed design. |
|
Definition |
Temperature coefficient measures the percentage of power output that is lost by a specific solar panel as the temperature rises. |
|
Units |
%/°F. |
|
Input Restrictions |
–0.19%/°F |
|
Baseline Building |
None (PV not modeled for the baseline building) |
|
Nominal Operating Cell Temperature (NOCT) |
|
|---|---|
|
Applicability |
PV systems when no on-site renewable systems are specified in the proposed design. |
|
Definition |
The normal operating cell temperature, typically between 45°C and 55°C |
|
Units |
Degrees Celsius (°F) |
|
Input Restrictions |
103°F |
|
Baseline Building |
None (PV not modeled for the baseline building) |
|
Total System Losses |
|
|---|---|
|
Applicability |
PV systems when no on-site renewable systems are specified in the proposed design. |
|
Definition |
System losses are the losses in power output from the conversion from direct current to alternating current. |
|
Units |
Ratio, power lost/total power |
|
Input Restrictions |
11.3% |
|
Baseline Building |
None (PV not modeled for the baseline building) |
|
Tilt |
|
|---|---|
|
Applicability |
PV systems when no on-site renewable systems are specified in the proposed design. |
|
Definition |
The tilt angle is the angle from horizontal of the photovoltaic modules in the array. The tilt angle is the angle from horizontal of the array where 0° = horizontal, and 90° = vertical. |
|
Units |
Degrees (°) |
|
Input Restrictions |
0-degrees (mounted horizontally) |
|
Baseline Building |
None (PV not modeled for the baseline building) |
|
Azimuth |
|
|---|---|
|
Applicability |
PV systems when no on-site renewable systems are specified in the proposed design. |
|
Definition |
The azimuth angle is the angle clockwise from true north describing the direction that the array faces. An azimuth angle of 180° is for a south-facing array, and an azimuth angle of 0° is for a north-facing array. |
|
Units |
Degrees (°) |
|
Input Restrictions |
180-degrees. |
|
Baseline Building |
None (PV not modeled for the baseline building) |