This section describes a floor-based radiant cooling system and the inputs required.
Hydronic Tubing Length |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The length of the hydronic tubing in the slab |
Units |
ft |
Input Restrictions |
As designed |
Baseline building |
Not applicable |
Hydronic Tubing Inside Diameter |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The inside diameter of the hydronic tubing in the slab |
Units |
ft |
Input Restrictions |
As designed, between a minimum of ½” and a maximum of ¾” |
Baseline building |
Not applicable |
Temperature Control Type |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, ODB, OWB |
Units |
None |
Input Restrictions |
Fixed at Mean Air Temperature for calculations |
Baseline building |
Not applicable |
Rated Flow Rate |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, ODB, OWB |
Units |
None |
Input Restrictions |
Fixed at Mean Air Temperature for calculations |
Baseline building |
Not applicable |
Cooling Control Temperature |
|
Applicability |
Variable Flow Systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, ODB, OWB |
Units |
None |
Input Restrictions |
Fixed at Mean Air Temperature for calculations |
Baseline building |
Not applicable |
Condensation Control Type |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, ODB, OWB |
Units |
None |
Input Restrictions |
Fixed at Mean Air Temperature for calculations |
Baseline building |
Not applicable |
Condensation Control Dewpoint Offset |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature difference above dewpoint that is the minimum cold water supply temperature |
Units |
None |
Input Restrictions |
Fixed at 2°F above dewpoint |
Baseline building |
Not applicable |
Rated Pump Power Consumption |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The rated pump power at design conditions |
Units |
Watts |
Input Restrictions |
As Designed |
Baseline building |
Not applicable |
Motor Efficiency |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The pump motor efficiency |
Units |
Decimal fraction |
Input Restrictions |
As Designed |
Baseline building |
Default motor efficiency from Standard 90.1-2010 Table 10.8 (Table numbering may change) based on motor nameplate hp |
Fraction of Motor Heat to Fluid |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
Fraction of the heat from the motor inefficiencies that enters the fluid stream |
Units |
none |
Input Restrictions |
As designed. Default is 0. |
Baseline building |
Not applicable |
Cooling High Water Temperature |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The high temperature used for control. If the water temperature is above the high temperature, the control temperature is set to the low control temperature. |
Units |
°F |
Input Restrictions |
As designed |
Baseline building |
Not applicable |
Cooling Low Water Temperature |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control of the water temperature. If the water temperature of the radiant cooling is below this temperature, cooling is disabled. |
Units |
°F |
Input Restrictions |
Fixed at 55°F |
Baseline building |
Not applicable |
Condensation Control Type |
|
Applicability |
Floor-based radiant cooling systems |
Definition |
The simulation program may have a means of detecting when condensation is likely to occur on floor surfaces in the space. When this occurs, the simulation can shut off the system to prevent condensation from occurring. |
Units |
List: None, Simple, Variable |
Input Restrictions |
As designed |
Baseline building |
Not applicable |
This section describes a floor-based radiant cooling system and the inputs required for Standard 90.1-2019 evaluation.
Hydronic Tubing Length |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The length of the hydronic tubing in the slab |
Units |
ft |
Input Restrictions |
As designed |
Baseline Building |
Not applicable |
Hydronic Tubing Inside Diameter |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The inside diameter of the hydronic tubing in the slab |
Units |
ft |
Input Restrictions |
As designed, between a minimum of 1/2 in. and a maximum of 3/4 in. |
Baseline Building |
Not applicable |
Temperature Control Type |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, TODB, TOWB) |
Units |
None |
Input Restrictions |
Fixed at mean air temperature for calculations |
Baseline Building |
Not applicable |
Rated Flow Rate |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, ODB, OWB) |
Units |
None |
Input Restrictions |
Fixed at mean air temperature for calculations |
Baseline Building |
Not applicable |
Cooling Control Temperature |
|
---|---|
Applicability |
Variable flow systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, ODB, OWB) |
Units |
None |
Input Restrictions |
Fixed at mean air temperature for calculations |
Baseline Building |
Not applicable |
Condensation Control Type |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, ODB, OWB) |
Units |
None |
Input Restrictions |
Fixed at mean air temperature for calculations |
Baseline Building |
Not applicable |
Condensation Control Dewpoint Offset |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature difference above dewpoint that is the minimum cold water supply temperature |
Units |
None |
Input Restrictions |
Fixed at 2°F above dewpoint |
Baseline Building |
Not applicable |
Rated Pump Power Consumption |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The rated pump power at design conditions |
Units |
Watts |
Input Restrictions |
As designed |
Baseline Building |
Not applicable |
Motor Efficiency |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The pump motor efficiency |
Units |
Decimal fraction |
Input Restrictions |
As designed |
Baseline Building |
Default motor efficiency from Standard 90.1-2019, Table G3.9.1 based on motor nameplate hp |
Fraction of Motor Heat to Fluid |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
Fraction of the heat from the motor inefficiencies that enters the fluid stream |
Units |
None |
Input Restrictions |
As designed. Default is 0. |
Baseline Building |
Not applicable |
Cooling High Water Temperature |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The high temperature used for control. If the water temperature is above the high temperature, the control temperature is set to the low control temperature. |
Units |
°F |
Input Restrictions |
As designed |
Baseline Building |
Not applicable |
Cooling Low Water Temperature |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control of the water temperature. If the water temperature of the radiant cooling is below this temperature, cooling is disabled. |
Units |
°F |
Input Restrictions |
Fixed at 55°F |
Baseline Building |
Not applicable |
Condensation of Control Type |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The simulation program may have a means of detecting when condensation is likely to occur on floor surfaces in the space. When this occurs, the simulation can shut off the system to prevent condensation from occurring. |
Units |
List: None, Simple, Variable |
Input Restrictions |
As designed |
Baseline Building |
Not applicable |
This section describes a floor-based radiant cooling system and the inputs required for Standard 90.1-2022 evaluation.
Hydronic Tubing Length |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The length of the hydronic tubing in the slab |
Units |
ft |
Input Restrictions |
As designed |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as the proposed design. |
Hydronic Tubing Inside Diameter |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The inside diameter of the hydronic tubing in the slab |
Units |
ft |
Input Restrictions |
As designed, between a minimum of 1/2 in. and a maximum of 3/4 in. |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as the proposed design. |
Temperature Control Type |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
Can be “constant”, “outside air-based reset” or “demand-based reset” |
Units |
None |
Input Restrictions |
None |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as the proposed design. |
Rated Flow Rate |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The rated GPM flow rate of the system. |
Units |
GPM |
Input Restrictions |
None |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations The GPM for the baseline design shall be sized proportionally to the capacities in the proposed design based on sizing runs. |
Cooling Control Temperature |
|
---|---|
Applicability |
Variable flow systems |
Definition |
The temperature used for control (operative temperature, mean air temperature, mean radiant temperature, ODB, OWB) |
Units |
None |
Input Restrictions |
None |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as the proposed design. |
Condensation Control Dewpoint Offset |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature difference above dewpoint that is the minimum cold water supply temperature |
Units |
None |
Input Restrictions |
As design. Default: Fixed at 2°F above dewpoint |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as proposed. |
Rated Pump Power Consumption |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The rated pump power at design conditions |
Units |
Watts |
Input Restrictions |
As designed |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations For pumps included in the scope of the retrofit, as designed except with a motor efficiency minimally compliant with Standard 90.1-2022 Section 10.4.1 based on motor nameplate hp. Pumps not included in the scope of the alteration should be modeled the same in the baseline and proposed. |
Motor Efficiency |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The pump motor efficiency |
Units |
Decimal fraction |
Input Restrictions |
As designed |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations For pump motors included in the scope of the retrofit, motor efficiency minimally compliant with Standard 90.1-2022 Section 10.4.1. based on motor nameplate hp. Pumps not included in the scope of the alteration should be modeled the same in the baseline and proposed. |
Fraction of Motor Heat to Fluid |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
Fraction of the heat from the motor inefficiencies that enters the fluid stream |
Units |
None |
Input Restrictions |
As designed. Default is 0. |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as proposed. Default is 0. |
Cooling High Water Temperature |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The high temperature used for control. If the water temperature is above the high temperature, the control temperature is set to the low control temperature. |
Units |
°F |
Input Restrictions |
As designed |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as proposed. |
Cooling Low Water Temperature |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The temperature used for control of the water temperature. If the water temperature of the radiant cooling is below this temperature, cooling is disabled. |
Units |
°F |
Input Restrictions |
As designed. Default: Fixed at 55°F |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as proposed. |
Condensation of Control Type |
|
---|---|
Applicability |
Floor-based radiant cooling systems |
Definition |
The simulation program may have a means of detecting when condensation is likely to occur on floor surfaces in the space. When this occurs, the simulation can shut off the system to prevent condensation from occurring. |
Units |
List: None, Simple, Variable |
Input Restrictions |
As designed |
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations Same as proposed. |