Ventilation Source |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The source of ventilation for an HVAC system. The choices are:
|
Units |
List: natural or mechanical |
Input Restrictions |
As designed. |
Baseline Rules |
For residential units, set to natural, for all other occupancies, set equal to mechanical. |
Ventilation Control Method |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
The baseline building shall use the same ventilation control method as the proposed design except for the following: When the proposed design in systems with outdoor air capacity less than or equal to 3000 cfm serving areas with an average design capacity of 100 people per 1000 ft² or less use demand control ventilation, the baseline building shall be modeled as fixed ventilation (G3.1.2.5 exception 1). |
Design Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The quantity of ventilation air that is provided to the space for the specified thermal block at maximum occupancy. |
Units |
cfm or cfm/occupant |
Input Restrictions |
As designed. Appendix B provides default values. |
Baseline Rules |
Same as the proposed design except in the following cases:
For systems serving kitchens, the minimum outside air ventilation rate is the exhaust air ventilation rate minus available transfer air. Refer to building description ‘Kitchen Exhaust’. |
Minimum Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The minimum quantity of ventilation air that must provided to the space when the HVAC system is operating. This ventilation rate must be provided whether or not the space is occupied. |
Units |
cfm or cfm/ft² |
Input Restrictions |
As designed |
Baseline Rules |
Same as the proposed design |
Exhaust Fan Schedule |
|
---|---|
Applicability |
All HVAC zones |
Definition |
Demand control ventilation (DCV) is required for spaces larger than 500 ft2 and with a design occupancy for ventilation of greater than 40 people per 1000 ft2 of floor area and served by systems with one or more of the following: a.an air-side economizer, b.automatic modulating control of the outdoor air damper, c.a design outdoor airflow greater than 3000 cfm. Exceptions: a.Systems with the exhaust air energy recovery complying with Standard 90.1 2010 Section 6.5.6.1. b.Multiple-zone systems without DDC of individual zones communicating with a central control panel. c.Systems with a design outdoor airflow less than 1200 cfm. Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm. |
Units |
CFM or CFM/occupant |
Input Restrictions |
As designed. DCV is a mandatory requirement for spaces larger than 500 sq.ft, with a design occupancy of more than 40 people per 1000 sq.ft unless any of the exceptions specified above apply. |
Baseline Rules |
Same as proposed for spaces or systems where DCV is required as described above. For other spaces and systems DCV is not modeled. |