Ventilation Source |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The source of ventilation for an HVAC system. The choices are:
|
Units |
List: natural or mechanical |
Input Restrictions |
As designed. |
Baseline Rules |
For residential units, set to natural, for all other occupancies, set equal to mechanical. |
Ventilation Control Method |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
The baseline building shall use the same ventilation control method as the proposed design except for the following: When the proposed design in systems with outdoor air capacity less than or equal to 3000 cfm serving areas with an average design capacity of 100 people per 1000 ft² or less use demand control ventilation, the baseline building shall be modeled as fixed ventilation (G3.1.2.5 exception 1). |
Design Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The quantity of ventilation air that is provided to the space for the specified thermal block at maximum occupancy. |
Units |
cfm or cfm/occupant |
Input Restrictions |
As designed. Appendix B provides default values. |
Baseline Rules |
Same as the proposed design except in the following cases:
For systems serving kitchens, the minimum outside air ventilation rate is the exhaust air ventilation rate minus available transfer air. Refer to building description ‘Kitchen Exhaust’. |
Minimum Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The minimum quantity of ventilation air that must provided to the space when the HVAC system is operating. This ventilation rate must be provided whether or not the space is occupied. |
Units |
cfm or cfm/ft² |
Input Restrictions |
As designed |
Baseline Rules |
Same as the proposed design |
Exhaust Fan Schedule |
|
---|---|
Applicability |
All HVAC zones |
Definition |
Demand control ventilation (DCV) is required for spaces larger than 500 ft2 and with a design occupancy for ventilation of greater than 40 people per 1000 ft2 of floor area and served by systems with one or more of the following: a.an air-side economizer, b.automatic modulating control of the outdoor air damper, c.a design outdoor airflow greater than 3000 cfm. Exceptions: a.Systems with the exhaust air energy recovery complying with Standard 90.1 2010 Section 6.5.6.1. b.Multiple-zone systems without DDC of individual zones communicating with a central control panel. c.Systems with a design outdoor airflow less than 1200 cfm. Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm. |
Units |
CFM or CFM/occupant |
Input Restrictions |
As designed. DCV is a mandatory requirement for spaces larger than 500 sq.ft, with a design occupancy of more than 40 people per 1000 sq.ft unless any of the exceptions specified above apply. |
Baseline Rules |
Same as proposed for spaces or systems where DCV is required as described above. For other spaces and systems DCV is not modeled. |
Outdoor Air Ventilation Source |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The source of outdoor air ventilation for an HVAC system. The choices are:
|
Units |
List: Natural or mechanical |
Input Restrictions |
As designed |
Baseline Building |
Ventilation is set to mechanical for the baseline building |
Minimum Outdoor Air Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The minimum quantity of outdoor ventilation air that must be provided to the space when it is occupied |
Units |
cfm or cfm/ft² |
Input Restrictions |
As designed |
Baseline Building |
Minimum ventilation system outdoor air intake flow shall be the same for the proposed and baseline building designs. Except in the following conditions:
|
Example |
Example 1: Should DCV be required in the following case? Can a savings credit be taken?
Answer: No the design does not meet the exceptions listed above, therefor both designs should be modeled with DCV. If the design airflow of the system in question was less than 3000 CFM then DCV would only be modeled in the proposed case and credit could be taken. |
Design Outdoor Air Ventilation Rate and Schedule |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The quantity of outdoor air ventilation that is provided to the space for the specified thermal zone at maximum occupancy |
Units |
cfm or cfm/occupant |
Input Restrictions |
The outdoor air ventilation rate would be as designed. Outdoor air ventilation schedule for proposed building can be either of the two: a. As designed b. The outdoor air ventilation schedule follows the HVAC availability schedule. In this case outdoor air isn’t supplied during unoccupied times or during night cycling operation. Some proposed building designs might bring in ventilation air during unoccupied hours for night flush or economizer operation. Due to these reasons, an option for user input of schedule for outdoor air availability is provided. |
Baseline Building |
Same as proposed, except:
|
Ventilation Control Method |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
Baseline building shall be modeled with a fixed ventilation rate which would be equal to the design ventilation rate (see above). No ventilation control methods shall be modeled for the baseline building design except for the following:
|
Design Ventilation Rate: Demand Control Ventilation |
|
---|---|
Applicability |
All HVAC zones |
Definition |
Demand control ventilation is required for spaces larger than 500 ft2 and with a design occupancy for ventilation of greater than or equal to 25 people per 1000 ft2 of floor area and served by systems with one or more of the following: a. An air-side economizer b. Automatic modulating control of the outdoor air damper c. A design outdoor airflow greater than 3000 cfm Exceptions: a. Systems with the exhaust air energy recovery complying with Standard 90.1-2019, Section 6.5.6.1 b. Multiple-zone systems without dynamic demand control (DDC) of individual zones communicating with a central control panel c. Systems with a design outdoor airflow less than 750 cfm a. Spaces where >75% of the space design outdoor airflow is required for makeup air that is exhausted from the space or transfer air that is required for makeup air that is exhausted from other spaces. b. Spaces with one of the following occupancy categories as defined in ASHRAE Standard 62.1: correctional cells, daycare sickrooms, science labs, barbers, beauty and nail salons, and bowling alley seating. |
Units |
cfm or cfm/occupant |
Input Restrictions |
As designed. DCV is a mandatory requirement for spaces larger than 500 ft2, with design occupancy of more than 25 people per 1000 ft2 unless any of the exceptions specified above apply. |
Baseline Building |
DCV is not modeled for the baseline building except for zones served by systems with outdoor air greater than or equal to 3000 cfm and occupant density of 100 people per 1000 ft2 or less |