Ventilation Source |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The source of ventilation for an HVAC system. The choices are:
|
Units |
List: natural or mechanical |
Input Restrictions |
As designed. |
Baseline Rules |
For residential units, set to natural, for all other occupancies, set equal to mechanical. |
Ventilation Control Method |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Rules |
The baseline building shall use the same ventilation control method as the proposed design except for the following: When the proposed design in systems with outdoor air capacity less than or equal to 3000 cfm serving areas with an average design capacity of 100 people per 1000 ft² or less use demand control ventilation, the baseline building shall be modeled as fixed ventilation (G3.1.2.5 exception 1). |
Design Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The quantity of ventilation air that is provided to the space for the specified thermal block at maximum occupancy. |
Units |
cfm or cfm/occupant |
Input Restrictions |
As designed. Appendix B provides default values. |
Baseline Rules |
Same as the proposed design except in the following cases:
For systems serving kitchens, the minimum outside air ventilation rate is the exhaust air ventilation rate minus available transfer air. Refer to building description ‘Kitchen Exhaust’. |
Minimum Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The minimum quantity of ventilation air that must provided to the space when the HVAC system is operating. This ventilation rate must be provided whether or not the space is occupied. |
Units |
cfm or cfm/ft² |
Input Restrictions |
As designed |
Baseline Rules |
Same as the proposed design |
Exhaust Fan Schedule |
|
---|---|
Applicability |
All HVAC zones |
Definition |
Demand control ventilation (DCV) is required for spaces larger than 500 ft2 and with a design occupancy for ventilation of greater than 40 people per 1000 ft2 of floor area and served by systems with one or more of the following: a.an air-side economizer, b.automatic modulating control of the outdoor air damper, c.a design outdoor airflow greater than 3000 cfm. Exceptions: a.Systems with the exhaust air energy recovery complying with Standard 90.1 2010 Section 6.5.6.1. b.Multiple-zone systems without DDC of individual zones communicating with a central control panel. c.Systems with a design outdoor airflow less than 1200 cfm. Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm. |
Units |
CFM or CFM/occupant |
Input Restrictions |
As designed. DCV is a mandatory requirement for spaces larger than 500 sq.ft, with a design occupancy of more than 40 people per 1000 sq.ft unless any of the exceptions specified above apply. |
Baseline Rules |
Same as proposed for spaces or systems where DCV is required as described above. For other spaces and systems DCV is not modeled. |
Outdoor Air Ventilation Source |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The source of outdoor air ventilation for an HVAC system. The choices are:
|
Units |
List: Natural or mechanical |
Input Restrictions |
As designed |
Baseline Building |
Ventilation is set to mechanical for the baseline building |
Minimum Outdoor Air Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The minimum quantity of outdoor ventilation air that must be provided to the space when it is occupied |
Units |
cfm or cfm/ft² |
Input Restrictions |
As designed |
Baseline Building |
Minimum ventilation system outdoor air intake flow shall be the same for the proposed and baseline building designs. Except in the following conditions:
|
Example |
Example 1: Should DCV be required in the following case? Can a savings credit be taken?
Answer: No the design does not meet the exceptions listed above, therefor both designs should be modeled with DCV. If the design airflow of the system in question was less than 3000 CFM then DCV would only be modeled in the proposed case and credit could be taken. |
Design Outdoor Air Ventilation Rate and Schedule |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The quantity of outdoor air ventilation that is provided to the space for the specified thermal zone at maximum occupancy |
Units |
cfm or cfm/occupant |
Input Restrictions |
The outdoor air ventilation rate would be as designed. Outdoor air ventilation schedule for proposed building can be either of the two: a. As designed b. The outdoor air ventilation schedule follows the HVAC availability schedule. In this case outdoor air isn’t supplied during unoccupied times or during night cycling operation. Some proposed building designs might bring in ventilation air during unoccupied hours for night flush or economizer operation. Due to these reasons, an option for user input of schedule for outdoor air availability is provided. |
Baseline Building |
Same as proposed, except:
|
Ventilation Control Method |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
Baseline building shall be modeled with a fixed ventilation rate which would be equal to the design ventilation rate (see above). No ventilation control methods shall be modeled for the baseline building design except for the following:
|
Design Ventilation Rate: Demand Control Ventilation |
|
---|---|
Applicability |
All HVAC zones |
Definition |
Demand control ventilation is required for spaces larger than 500 ft2 and with a design occupancy for ventilation of greater than or equal to 25 people per 1000 ft2 of floor area and served by systems with one or more of the following: a. An air-side economizer b. Automatic modulating control of the outdoor air damper c. A design outdoor airflow greater than 3000 cfm Exceptions: a. Systems with the exhaust air energy recovery complying with Standard 90.1-2019, Section 6.5.6.1 b. Multiple-zone systems without dynamic demand control (DDC) of individual zones communicating with a central control panel c. Systems with a design outdoor airflow less than 750 cfm a. Spaces where >75% of the space design outdoor airflow is required for makeup air that is exhausted from the space or transfer air that is required for makeup air that is exhausted from other spaces. b. Spaces with one of the following occupancy categories as defined in ASHRAE Standard 62.1: correctional cells, daycare sickrooms, science labs, barbers, beauty and nail salons, and bowling alley seating. |
Units |
cfm or cfm/occupant |
Input Restrictions |
As designed. DCV is a mandatory requirement for spaces larger than 500 ft2, with design occupancy of more than 25 people per 1000 ft2 unless any of the exceptions specified above apply. |
Baseline Building |
DCV is not modeled for the baseline building except for zones served by systems with outdoor air greater than or equal to 3000 cfm and occupant density of 100 people per 1000 ft2 or less |
Outdoor Air Ventilation Source |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The source of outdoor air ventilation for an HVAC system. The choices are:
|
Units |
List: Natural or mechanical |
Input Restrictions |
As designed |
Baseline Building |
G3.2 New Construction/Major Alterations Ventilation is set to mechanical for the baseline building G3.3 Minor Alterations Same as proposed design except if modeling credit for natural ventilation according to Standard 90.1 Table G3.1 #4 Baseline Building Performance column exceptions 1-3. |
Minimum Outdoor Air Ventilation Rate |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The minimum quantity of outdoor ventilation air that must be provided to the space when it is occupied |
Units |
cfm or cfm/ft² |
Input Restrictions |
As designed |
Baseline Building |
G3.2 New Construction/Major Alterations Minimum ventilation system outdoor air intake flow shall be the same for the proposed and baseline building designs. Except in the following conditions:
G3.3 Minor Alterations The baseline shall be modeled as minimally compliant with Standard 90.1-2022 Section 6.5.3.8 with the same feature as the proposed design. Where the proposed design does not include one of these features it is recommended that the baseline be modeled according to Standard 90.1-2022 Section 6.5.3.8 option a with no more than 135% of the required minimum outdoor air rate modeled in the baseline. Standard 90.1-2022 Section 6.5.3.8 states that the required minimum outdoor air rate is the larger of the minimum outdoor air rate or the minimum exhaust air rate required by Standard 62.1, Standard 62.2, Standard 170, or applicable codes or accreditation standards. The section also requires that outdoor air ventilation systems comply with one of the following: a. Design minimum system outdoor air provided shall not exceed 135% of the required minimum outdoor air rate. b. Dampers, ductwork, and controls shall be provided that allow the system to supply no more than the required minimum outdoor air rate with a single set-point adjustment. c. The system includes exhaust air energy recovery complying with Section 6.5.6.1.
Exception: the minimum outdoor air ventilation rate should be modeled the same in the baseline and proposed if, based on the requirements of 90.1-2022 Section 6.1.4 and the scope of the alteration, the 90.1-2022 Section 6.5.3.8 requirements are inapplicable.
If the following conditions are met,
then ventilation air flow may differ between the baseline and proposed due to DCV. See the Design Ventilation Rate: Demand Control Ventilation descriptor for the requirements of 6.4.3.8.
|
Example |
Standard 90.1 G3.2 Example 1: Should DCV be required in the following case? Can a savings credit be taken?
Answer: No, the design does not meet the exceptions listed above, therefore both designs should be modeled with DCV. If the design airflow of the system in question was less than 3000 CFM or the average design occupant density was 100 people per 1000 ft2 or less, then DCV would only be modeled in the proposed case and credit could be taken. |
Design Outdoor Air Ventilation Rate and Schedule |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The quantity of outdoor air ventilation that is provided to the space for the specified thermal zone at maximum occupancy |
Units |
cfm or cfm/occupant |
Input Restrictions |
The outdoor air ventilation rate would be as designed. Outdoor air ventilation schedule for proposed building can be either of the two: a. As designed b. The outdoor air ventilation schedule follows the HVAC availability schedule. In this case outdoor air isn’t supplied during unoccupied times or during night cycling operation. Some proposed building designs might bring in ventilation air during unoccupied hours for night flush or economizer operation. Due to these reasons, an option for user input of schedule for outdoor air availability is provided. |
Baseline Building |
G3.2 New Construction/Major Alterations Same as proposed, except:
G3.3 Minor Alterations The baseline shall be modeled as minimally compliant with Standard 90.1-2022 Section 6.5.3.8 with the same feature as the proposed design. Where the proposed design does not include one of these features it is recommended that the baseline be modeled according to Standard 90.1-2022 Section 6.5.3.8 option a with no more than 135% of the required minimum outdoor air rate modeled in the baseline. Standard 90.1-2022 Section 6.5.3.8 states that the required minimum outdoor air rate is the larger of the minimum outdoor air rate or the minimum exhaust air rate required by Standard 62.1, Standard 62.2, Standard 170, or applicable codes or accreditation standards. The section also requires that outdoor air ventilation systems comply with one of the following: a. Design minimum system outdoor air provided shall not exceed 135% of the required minimum outdoor air rate. b. Dampers, ductwork, and controls shall be provided that allow the system to supply no more than the required minimum outdoor air rate with a single set-point adjustment. c. The system includes exhaust air energy recovery complying with Section 6.5.6.1.
Exception: the minimum outdoor air ventilation rate should be modeled the same in the baseline and proposed if, based on the requirements of 90.1-2022 Section 6.1.4 and the scope of the alteration, the 90.1-2022 Section 6.5.3.8 requirements are inapplicable. If the following conditions are met,
then ventilation air flow may differ between the baseline and proposed due to DCV. See the Design Ventilation Rate: Demand Control Ventilation descriptor for the requirements of 6.4.3.8. |
Ventilation Control Method |
|
---|---|
Applicability |
All HVAC zones |
Definition |
The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:
|
Units |
List (see above) |
Input Restrictions |
As designed |
Baseline Building |
G3.2 New Construction/Major Alterations Baseline building shall be modeled with a fixed ventilation rate which would be equal to the design ventilation rate (see above). No ventilation control methods shall be modeled for the baseline building design except for the following:
G3.3 Minor Alterations Baseline building shall be modeled with a fixed ventilation rate which would be equal to the design ventilation rate unless demand control ventilation is required by Standard 90.1-2022 Section 6.1.4, based on the scope of the alteration, according to Standard 90.1-2022 Section 6.4.3.8. See the Design Ventilation Rate: Demand Control Ventilation descriptor for the requirements of 6.4.3.8. |
Design Ventilation Rate: Demand Control Ventilation |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Applicability |
All HVAC zones |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Definition |
Demand control ventilation is a mandatory requirement for spaces larger than the floor area in Table 43 based on an occupant outdoor airflow component in cfm per 1000 ft2 and served by systems with one or more of the following: a. An air-side economizer b. Automatic modulating control of the outdoor air damper c. A design outdoor airflow greater than 3000 cfm The occupant outdoor airflow component in cfm per 1000 ft2 in Table 43 is required to be calculated as the product of the default occupant density and outdoor airflow rate per occupant(Rp) as shown in ASHRAE Standard 62.1, Table 6.2.2.1. Exceptions: a. Multiple-zone systems without dynamic demand control (DDC) of individual zones communicating with a central control panel b. Spaces where >75% of the space design outdoor airflow is required for makeup air that is exhausted from the space or transfer air that is required for makeup air that is exhausted from other spaces. c. Spaces with one of the following occupancy categories as defined in ASHRAE Standard 62.1: correctional cells, daycare sickrooms, science labs, barbers, beauty and nail salons, and bowling alley seating. d. Spaces where the requirements of ASHRAE Standard 170, applicable codes, or applicable accreditation standards do not allow the reduction of outdoor airflow. Table 43. Demand Control Ventilation Floor Area Thresholds
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Units |
cfm or cfm/occupant |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Input Restrictions |
As designed. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Baseline Building |
G3.2 New Construction/Major Alterations DCV is not modeled for the baseline building except for zones served by systems with outdoor air greater than or equal to 3000 cfm and occupant density of 100 people per 1000 ft2 or less. G3.3 Minor Alterations Demand control ventilation shall be modeled for spaces as required by Standard 90.1-2022 Section 6.4.3.8 if applicable based on the scope of the alteration and the language in Standard 90.1-2022 Section 6.1.4. See the Definition for this descriptor for the requirements of 6.4.3.8. Where Standard 90.1-2022 Section 6.4.3.8 is not applicable based on the scope of the alteration and the language in Standard 90.1-2022 Section 6.1.4 DCV should be modeled identically in the baseline and proposed. |