Maximum Outside Air Ratio |
|
|---|---|
|
Applicability |
All systems with modulating outside air dampers |
|
Definition |
The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
|
Units |
Ratio |
|
Input Restrictions |
As designed. Maximum of 1.0. |
|
Baseline Building |
1.0 for all systems with economizers. For others, equal to the ratio of required outdoor air to the peak supply airflow at design conditions. |
|
Design Outside Airflow |
|
|---|---|
|
Applicability |
All systems with outside air dampers |
|
Definition |
The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside airflow for each of the zones served by the system. |
|
Units |
cfm |
|
Input Restrictions |
As designed |
|
Baseline Building |
Same as proposed. This input along with occupant density determines if the zones served by this system are required to have demand control ventilation. This value might also be different for buildings using the ASHRAE 62.1 Ventilation Rate Procedure as described in Section 3.6.5.5 of this document. See Section 3.6.5.4 of this document for ventilation control method at the zone level. |
|
Outdoor Air Control Method |
|
|---|---|
|
Applicability |
All HVAC systems that deliver outside air to multiple zones. (These requirements don’t apply to systems supplying air to single zones.) |
|
Definition |
The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system reports its outside air requirements hourly. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information hourly. Options include:
The quantity of outside air can be controlled in a number of ways, but a common method is to install a flow station at the outside air supply that modulates the position of the outside air and return dampers to maintain the desired outside airflow. With the average flow, a CO2 sensor in the return air duct is another way to control the position of the outside air and return dampers. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
Same as proposed. See Section 3.6.5.5 for details. |
|
Outdoor Air Minimum Flow Schedule |
|
|---|---|
|
Applicability |
All HVAC systems that deliver outside air |
|
Definition |
The schedule shall allow the system to provide the minimum system outdoor air requirements based on a time of day schedule. This input is specifically helpful when ventilation intake needs to be modified for fan cycling operation during unoccupied hours. This schedule would be an “on/off” schedule that determines when the design outside air is supplied by the system. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
In the following cases minimum design ventilation will be provided based on the HVAC availability schedule and outside air dampers shall be closed during night cycle and morning warm-up:
In all other cases outside air shall be provided anytime the system operates. |
|
Maximum Outside Air Ratio |
|
|---|---|
|
Applicability |
All systems with modulating outside air dampers |
|
Definition |
The descriptor is used to limit the maximum amount of outside air that a system can provide as a percentage of the design supply air. It is used where the installation has a restricted intake capacity. |
|
Units |
Ratio |
|
Input Restrictions |
As designed. Maximum of 1.0. |
|
Baseline Building |
1.0 for all systems with economizers. For others, equal to the ratio of required outdoor air to the peak supply airflow at design conditions. |
|
Design Outside Airflow |
|
|---|---|
|
Applicability |
All systems with outside air dampers |
|
Definition |
The rate of outside air that needs to be delivered by the system at design conditions. This input may be derived from the sum of the design outside airflow for each of the zones served by the system. |
|
Units |
cfm |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations Same as proposed unless exceptions in 90.1 G3.2.2.4 apply. This input along with occupant density determines if the zones served by this system are required to have demand control ventilation. This value might also be different for buildings using the ASHRAE 62.1 Ventilation Rate Procedure as described in Section 3.6.5.5 of this document. See Section 3.6.5.4 of this document for ventilation control method at the zone level. G3.3 Minor Alterations The baseline shall be modeled as minimally compliant with Standard 90.1-2022 Section 6.5.3.8 with the same feature as the proposed design. Where the proposed design does not include one of these features it is recommended that the baseline be modeled according to Standard 90.1-2022 Section 6.5.3.8 option a with no more than 135% of the required minimum outdoor air rate modeled in the baseline. Standard 90.1-2022 Section 6.5.3.8 states that the required minimum outdoor air rate is the larger of the minimum outdoor air rate or the minimum exhaust air rate required by Standard 62.1, Standard 62.2, Standard 170, or applicable codes or accreditation standards. The section also requires that outdoor air ventilation systems comply with one of the following: a. Design minimum system outdoor air provided shall not exceed 135% of the required minimum outdoor air rate. b. Dampers, ductwork, and controls shall be provided that allow the system to supply no more than the required minimum outdoor air rate with a single set-point adjustment. c. The system includes exhaust air energy recovery complying with Section 6.5.6.1.
Exception: the minimum outdoor air ventilation rate should be modeled the same in the baseline and proposed if, based on the requirements of 90.1-2022 Section 6.1.4 and the scope of the alteration, the 90.1-2022 Section 6.5.3.8 requirements are inapplicable.
If the following conditions are met,
then ventilation air flow may differ between the baseline and proposed due to DCV. See the Design Ventilation Rate: Demand Control Ventilation descriptor for the requirements of 6.4.3.8. |
|
Outdoor Air Control Method |
|
|---|---|
|
Applicability |
All HVAC systems that deliver outside air to multiple zones. (These requirements don’t apply to systems supplying air to single zones.) |
|
Definition |
The method of determining the amount of outside air that needs to be delivered by the system. Each of the zones served by the system reports its outside air requirements hourly. The options for determining the outside air at the zone level are discussed above. This control method addresses how the system responds to this information hourly. Options include:
The quantity of outside air can be controlled in a number of ways, but a common method is to install a flow station at the outside air supply that modulates the position of the outside air and return dampers to maintain the desired outside airflow. With the average flow, a CO2 sensor in the return air duct is another way to control the position of the outside air and return dampers. |
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
Same as proposed. See Section 3.6.5.5 for details. |
|
Outdoor Air Minimum Flow Schedule |
|
|---|---|
|
Applicability |
All HVAC systems that deliver outside air |
|
Definition |
The schedule shall allow the system to provide the minimum system outdoor air requirements based on a time-of-day schedule. This input is specifically helpful when ventilation intake needs to be modified for fan cycling operation during unoccupied hours. This schedule would be an “on/off” schedule that determines when the design outside air is supplied by the system. |
|
Units |
List (see above) |
|
Input Restrictions |
Schedules for HVAC system fans that provide outdoor air for ventilation shall run continuously whenever spaces are occupied and shall be cycled ON and OFF to meet heating and cooling loads during unoccupied hours. Exceptions:
|
|
Baseline Building |
Same as proposed. |