|
Cooling Supply Air Temperature |
|
|---|---|
|
Applicability |
Applicable to all systems |
|
Definition |
The supply air temperature setpoint at design cooling conditions |
|
Units |
Degrees Fahrenheit (°F) |
|
Input Restrictions |
As designed |
|
Baseline Rules |
20°F below the space setpoint |
|
Cooling Supply Air Temperature Control |
|
|---|---|
|
Applicability |
Any cooling system |
|
Definition |
The method of controlling the supply air temperature. Choices are:
|
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Rules |
For baseline building systems 1 through 4, the SAT control is fixed. For systems 5 through 8, the air temperature for coolingshall be reset higher by 5°F under the minimum cooling load conditions using a reset by warmest zone, flow first strategy This strategy sets the cooling coil temperature each hour to adequately cool the zone with the highest temperature. find the lowest supply air flow rate that will satisfy all the zone cooling loads at the maximum setpoint temperature. If this flow is greater than the maximum, the flow is set to the maximum and the setpoint temperature is reduced to satisfy the cooling loads. The airflow first strategy minimizes zone reheat coil energy (or overcooling) and central chiller energy consumption at the cost of possible increased fan energy. This SAT reset may driven back to the design SAT if a maximum humidity setpoint is not met. For system 9 and 10 (heating and ventilation) this input is not applicable. |
|
Cooling Reset Schedule by OSA |
|
|---|---|
|
Applicability |
When the proposed design resets SAT by outside air dry-bulb temperature |
|
Definition |
A linear reset schedule that represents the SAT setpoint as a function of outdoor air dry-bulb temperature. This schedule is defined by the following data points (see figures below:
Figure 3.7.2-1: SAT Cooling Setpoint Reset based on Outdoor Air Temperature (OAT) |
|
Units |
Data structure (two matched pairs of SAT and OAT, see above) |
|
Input Restrictions |
As designed. |
|
Baseline Rules |
The schedule defaults to: Supply Air High = Supply Air Low + 5 Supply Low = (greater of SAT or 50F) Outside High = 80°F Outside Low = 60°F |
|
Cooling Supply Air Temperature |
|
|---|---|
|
Applicability |
Applicable to all systems |
|
Definition |
The SAT setpoint at design cooling conditions |
|
Units |
Degrees Fahrenheit (°F) |
|
Input Restrictions |
As designed |
|
Baseline Building |
20°F below the zone temperature setpoint, except in laboratories, where it is to be set at 17°F below the zone temperature |
|
Cooling Supply Air Temperature Control |
|
|---|---|
|
Applicability |
Any cooling system |
|
Definition |
The method of controlling the SAT. Choices are:
|
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
For baseline building systems 1 through 4, there is no SAT control. The cooling coil modulates based on the zone thermostat setpoint. For systems 5 through 8, the air temperature for cooling shall be reset higher by 5°F under the minimum cooling load conditions using a reset by warmest zone, airflow first strategy. For system 11, the supply air temperature setpoint shall be reset from minimum supply air temperature at 50% cooling load to space temperature at 0% cooling load. For systems 9, 10, 12, and 13 (heating and ventilation and single zone systems), this input is not applicable. |
|
Cooling Reset Schedule by Outside Air Temperature |
|
|---|---|
|
Applicability |
When the proposed design resets SAT by outside air dry-bulb temperature |
|
Definition |
A linear reset schedule that represents the SAT setpoint as a function of outdoor air dry-bulb temperature. This schedule is defined by the following data points (see Figure 9):
Figure 9. SAT Cooling Setpoint Reset based on Outdoor Air Temperature (OAT) |
|
Units |
Data structure (two matched pairs of SAT and OAT, see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
Not applicable |
|
Cooling Supply Air Temperature |
|
|---|---|
|
Applicability |
Applicable to all systems |
|
Definition |
The SAT setpoint at design cooling conditions |
|
Units |
Degrees Fahrenheit (°F) |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations 20°F below the zone temperature setpoint, except in laboratories, where it is to be set at 17°F below the zone temperature. G3.3 Minor Alterations Same as proposed. |
|
Cooling Supply Air Temperature Control |
|
|---|---|
|
Applicability |
Any cooling system |
|
Definition |
The method of controlling the SAT. Choices are:
|
|
Units |
List (see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations For baseline building systems 1 through 4, there is no SAT control. The cooling coil modulates based on the zone thermostat setpoint. For systems 5 through 8, the air temperature for cooling shall be reset higher by 5°F under the minimum cooling load conditions using a reset by warmest zone, airflow first strategy. For system 11, the supply air temperature setpoint shall be reset from minimum supply air temperature at 50% cooling load to space temperature at 0% cooling load. For systems 9, 10, 12, and 13 (heating and ventilation and single zone systems), this input is not applicable. G3.3 Minor Alterations Baseline shall be modeled as minimally compliant with Standard 90.1-2022 Section 6.5.3.5. Standard 90.1-2022 Section 6.5.3.5 requires that multiple zone HVAC systems be modeled to automatically reset the supply air temperature in response to representative building loads or outdoor air temperature. The controls should be modeled to reset the supply air temperature at least 25% of the difference between the design supply air temperature and the design room air temperature. Controls that adjust the reset based on zone humidity are allowed to be modeled in Climate Zones 0B, 1B, 2B, 3B, 3C, and 4 through 8. HVAC zones that are expected to experience relatively constant loads should be modeled to have a maximum air-flow to accommodate the fully reset supply air temperature. Exceptions to 6.5.3.5:
Exception: the cooling supply air temperature control should be modeled the same in the baseline and proposed if, based on the requirements of 90.1-2022 Section 6.1.4 and the scope of the alteration, 90.1-2022 Section 6.5.3.5 requirements are inapplicable. |
|
Cooling Reset Schedule by Outside Air Temperature |
|
|---|---|
|
Applicability |
When the proposed design resets SAT by outside air dry-bulb temperature |
|
Definition |
A linear reset schedule that represents the SAT setpoint as a function of outdoor air dry-bulb temperature. This schedule is defined by the following data points (see Figure 9):
Figure 9. SAT Cooling Setpoint Reset based on Outdoor Air Temperature (OAT) |
|
Units |
Data structure (two matched pairs of SAT and OAT, see above) |
|
Input Restrictions |
As designed |
|
Baseline Building |
G3.2 New Construction/Major Alterations Not applicable G3.3 Minor Alterations See the Cooling Supply Air Temperature Control descriptor for baseline requirements. |

