This section contains building descriptors required to model four-pipe fan coil systems. Note that this system requires an outside air ventilation source to serve the zones and that an airside economizer is not available. Note that additional HVAC components (chiller, boiler, pumps) are needed to fully define this system.
Capacity Control Method | |
Applicability |
Four-pipe fan coil systems |
Definition |
The control method for the fan coil unit at the zone. The following choices are available:
|
Units |
List (with choices above) |
Input Restrictions |
Not a User Input – Derived from building descriptors for fan control and chiller loop flow control |
Baseline Building |
Not Applicable |
This section contains building descriptors required to model four-pipe fan coil systems. Note that this system requires an outside air ventilation source to serve the zones and that an airside economizer is not available. Note that additional HVAC components (chiller, boiler, pumps) are needed to fully define this system.
Capacity Control Method |
|
Applicability |
Four-pipe fan coil systems |
Definition |
The control method for the fan coil unit at the zone. The following choices are available:
|
Units |
List (with choices above) |
Input Restrictions |
Not a user input – derived from building descriptors for fan control and chiller loop flow control |
Baseline Building |
Four pipe fan coil systems are applicable for proposed buildings with the system type defined in Table 72. The capacity control for the baseline building will be specified as “Constant Fan Constant Flow.” |
Table 72. Baseline Systems Using Fan Coil Units
Proposed |
Baseline System Type |
|
Heating |
Cooling |
|
Boiler/Electric Resistance or Gas Furnace |
Purchased Chilled Water |
Proposed buildings qualifying for System 1 and 2 will be constant volume fan coil units |
Purchased Heat |
Purchased Chilled Water |
Proposed buildings qualifying for System 1 will be constant volume fan coil units |